Evaluation of Artificially Contaminated Suspension Insulators for Transmission

송전용 현수애자의 인공오손 평가

  • Published : 2002.08.24

Abstract

This paper presented the results of evaluation of artificially contaminated suspension insulators for transmission lines. The suspension insulators were contaminated with kaolin and clay which were included various amount of natural salt. The degree of contamination were evaluated by measuring equivalent salt deposit density(ESDD). Then, the leakage currents were measured as a function of applied voltage, degree of contamination, humidity.

Keywords