HVDC 500kV PPLP MI 케이블시스템 개발 (Development of HVDC 500kV PPLP MI cable systems in Korea)

  • 이수봉;조동식;김성윤;이태호;이수길;전승익
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.1202-1203
    • /
    • 2015
  • This paper describes the development of HVDC ${\pm}500kV$ polypropylene laminated paper (PPLP) mass-impregnated (MI) type cable system for HVDC transmission lines. As you know, mass-impregnated type cable generally has only insulating layer with the Kraft paper impregnated with a high-viscosity insulating compound. But polypropylene laminated paper is made of a layer of extruded polypropylene (PP) film sandwiched between two layers of Kraft paper. Thanks to PP film and its combination with Kraft paper, PPLP has higher AC, Impulse (Imp.) and DC breakdown (BD) strengths as well as lower dielectric loss than conventional Kraft paper insulation. In addition, Kraft MI cable has a limitation for the maximum conductor temperature as $55^{\circ}C$ But this PPLP MI cable has higher maximum conductor temperature than that of Kraft MI cable due to advantage of oil drainage characteristics. It is the most economic type of cable for HVDC transmission. Also HVDC ${\pm}500kV$ PPLP MI cable system was developed including land joints and outdoor-terminations. In order to prove the mechanical and electrical performances, the type test was carried out according to CIGRE recommendations. A full scale cable system has been tested successfully. And additional load cycle and polarity reversal tests on the cable system showed a higher performance compared with a similar mass impregnated paper cable.

  • PDF

345kV CV 케이블 접속함의 Proto Type 선정 (Determination of Proto Type for 345kV CV Cable Accessories)

  • 이수길;김인태;손시호;최수걸;허근도;박완기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1629-1631
    • /
    • 1998
  • Crosslinked polyethylene (XLPE) insulated cables are now widely used all over the world for extra-high voltage underground transmission systems. Prefabricated type (compression type) joint has developed in order to shorten the assembly time and lower the possibility of contamination at site by many companies in the world. For outdoor termination, to control the electric field distribution as uniform as possible, especially for the use of extra-high voltage system. much of products are adopting the oil-impregnated condensor cone type instead of electric field control element which uses the permitivity of it only (not capacitance). For Gas-immersed termination, dimension of outer insulation bushing was determined by IEC Publication 859. The highest voltage of underground power cable system is 345kV now, in Korea. We have much of experiences of the development of prefabricated type accessories for CV cable systems (154kV, 161kV, 230kV level). So it was possible to inspect the proto type of accessories for 345kV CV cable system and seems that the need time for the development of products is reduced.

  • PDF

AE(Acoustic Emission) 센서를 이용한 오차에 강인한 부분방전 위치추정 알고리즘에 관한 연구 (A Study on Algorithm Robust to Error for Estimating partial Discharge Location using Acoustic Emission Sensors)

  • 조성민;신희상;김재철;이양진;김광화
    • 조명전기설비학회논문지
    • /
    • 제22권10호
    • /
    • pp.69-75
    • /
    • 2008
  • 본 논문에서는 오차에 강인하게 초음파센서를 이용한 부분방전 위치를 추정하는 알고리즘을 제시하였다. 변압기 내부는 유온이 균일하지 않기 때문에 초음파의 절연유에서 전달 속도를 정확하게 산정하기 힘들다. 그렇기 때문에 처리 과정에서 일정 오차가 발생하게 된다. 따라서 점검자에게 유용한 정보를 제공하기 위해 부분방전의 위치추정 알고리즘은 이런 오차를 충분히 반영하여야 한다. 기존의 위치추정 기법은 좌표로 부분방전 발생 위치를 나타내었지만 본 논문에서 제시하는 Lookup-Table(LUT)를 이용한 기법은 부분방전 발생 위치를 지도형태로 나타내도록하여 점검자에게 충분히 유용한 정보를 제공할 수 있도록 하였다. 또한 임의로 데이터에 오차를 일으켜 기존 기법과 제시한 기법의 성능을 비교하였다.

ATH 고충진 실리콘 고무의 절연특성 연구 (Study on the Insulation Properties of Silicone Rubber)

  • 강동필;박효열;안명상;김대환;명인혜;이후범;오세호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1442-1444
    • /
    • 2003
  • 폴리머 애자용 shed 재료의 전기방전에 대한 열화내성과 표면이 오염된 조건하에서도 우수한 발수성 유지는 제품의 장기성능에 있어서 가장 중요한 인자들이다. 내트래킹성 확보를 위한 보강재로는 ATH가 주로 사용되고 있으며 ATH의 첨가량이 많을 수록 내트래킹성은 대체로 향상되는 것으로 되어 있다. 그러나 애자 제조시 무결점 성형성의 만족이 대단히 중요하기 때문에 ATH를 고충진하는 경우 사용하는 process oil들의 종류 및 첨가량을 고려한 ATH 첨가량의 최적화는 필요하다. 본 논문에서는 ATH를 170 part로 다량으로 첨가하면서 화학적 구조와 점도가 다른 몇 가지 실리콘 fliud들을 사용하여 무결점 성형에 적합한 가소도를 갖는 컴파운드를 제조하여 기본물성과 초고압 옥외절연물의 shed 재료로서 장기성능에 영향을 주는 방전열화내성과 표면발수성의 회복특성을 평가하였다. 컴파운드의 성형작업성과 관련이 큰 가소도는 fluid 점도에 따라 상당한 차이를 보이므로 실리콘 fluid 종류의 선택과 첨가량의 최적화에는 성형작업성, 발수성 회복특성, 열화내성 등의 고려가 필요하다. 무결점 애자성형을 위한 진공 사출에서 고무 컴파운드의 가소도가 중요한데 동일한 ATH첨가조건에서 일정한 가소도를 갖게 하는데 필요한 양은 fluid들의 종류에 따라서 상당한 차이가 있었다. 코로나 처리후 발수성 회복특성은 fluid들의 분자크기와 반응기의 종류에 따라 상당히 영향을 받았으며 분자가 클수록 초기회복속도는 다소 느렸지만 평상시에 늘 유지되는 상시발수성은 다소 높게 유지되었다. 아크와 트래킹 방전에 의한 무게 감소는 ATH가 과량으로 첨가되어 상당히 적었으며 fluid의 분자가 크면서 페닐기를 가진 fluid들이 첨가된 고무가 우수한 특성을 보였다.

  • PDF

180kV HVDC 해저케이블 기계적/전기적 특성 평가 (Mechanical and Electrical Performance of 180kV HVDC Submarine Cable System)

  • 김남열;이태호;지봉기;이상진;김정년;전승익;윤희석;정수길;강채홍;안용호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.616-618
    • /
    • 2007
  • This paper describes the mechanical and electrical test on HVDC submarine cable, Flexible Repair Joint and termination for 180kV. This HVDC submarine cable was manufactured using LS cable's unique skill and would be applied the HVDC submarine cable system in korea. The performance test consist of mechanical test and electrical test. The tensile bending test and tensile test was done as the mechanical test and Electrical test is DC voltage and Impulse test. The tensile bending test carried out 6 times(double of specified times) for maximum reliability. The DC test voltage is $\pm$400kV/1hr. We estimate the lower limit of DC breakdown voltage is 600kV. The impulse test voltage is $\pm$800kV/10shots. The type of developed cables is the MI type. Its insulation consist of paper tapes impregnated with a high viscosity oil. The development of new HVDC cable is available for HVDC underground or submarine power transmission. The developed HVDC cable, FRJ and termination have passed the mechanical and electrical test successfully and showed excellent performance.

  • PDF

Study on Decomposition Gas Characteristics and Condition Diagnosis for Gas-Insulated Transformer by Chemical Analysis

  • Kim, Ah-Reum;Kwak, Byeong Sub;Jun, Tae-Hyun;Park, Hyun-Joo
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제6권4호
    • /
    • pp.447-454
    • /
    • 2020
  • Since SF6 gas was discovered in the early 1900s, it has been widely used as an insulation material for electrical equipment. While various indicators have been developed to diagnose oil-immersed transformers, there are still insufficient indicators for the diagnosis of gas-insulated transformers. When necessary, chemical diagnostic methods can be used for gas-insulated transformers. However, the field suitability and accuracy of those methods for transformer diagnosis have not been verified. In addition, since various types of decomposition gases are generated therein, it is also necessary to establish appropriate analysis methods to cover the variety of gases. In this study, a gas-insulated transformer was diagnosed through the analysis of decomposition gases. Reliability assessments of both simple analysis methods suitable for on-site tests and precise analysis methods for laboratory level tests were performed. Using these methods, a gas analysis was performed for the internal decomposition gases of a 154 kV transformer in operation. In addition, simulated discharge and thermal fault experiments were demonstrated. Each major decomposition gas generation characteristics was identified. The results showed that an approximate diagnosis of the inside of a gas-insulated transformer is possible by analyzing SO2, SOF2, and CO using simple analysis methods on-site. In addition, since there are differences in the types of decomposition gas generation patterns with various solid materials of the internal transformer, a detailed examination should be performed by using precise analysis methods in the laboratory.

딸기재배 온실의 현장조사 분석 -서부경남 지역을 중심으로- (Field Survey of Greenhouse for Strawberry Culture -Case Study Based on Western Gyeongnam Area-)

  • 정영균;이종구;윤성욱;김현태;윤용철
    • 생물환경조절학회지
    • /
    • 제27권3호
    • /
    • pp.253-259
    • /
    • 2018
  • 본 연구에서는 딸기의 생육 및 환경관련 데이터를 활용하여 딸기 재배 온실의 최적 환경 구현을 위한 시스템을 선정하고 생산성 향상에 대한 연구를 위한 기초자료로 활용할 목적으로 서부 경남 지역 중 딸기 재배로 유명한 지역의 온실을 대상으로 현장조사를 실시하였다. 이 결과를 바탕으로 경상대학교 내에 딸기 재배용 테스트 베드 온실을 설치하여 연구를 실시하고자 본 연구를 수행하였다. 그 결과 재배농가의 연령대를 보면, 상대적으로 50대 및 60대가 가장 많았지만, 50대 이하가 27개 농가로서 전체의 약 67.5%정도이었고, 60대 이상은 32.5%정도인 것으로 나타났다. 재배경력의 경우, 10년 이하가 주류를 이루고 있지만 30년 이상인 경우도 있었다. 대상농가 모두가 단동온실로서 대부분이 아치 형태인 것으로 나타났으며, 양액재배 농가가 약 75%정도로 토경재배보다 많은 것으로 나타났다. 양액재배의 경우, 전체 농가가 고설재배를 하고 있었다. 단동온실의 폭, 측고 및 동고는 조사지역에 관계없이 각각 7.5~8.5m, 1.3~1.8m 및 2.5~3.5m정도 이었다. 서까래 간격도 0.7~0.8m정도인 것으로 나타났다. 고설재배의 경우, 고설재배 베드의 폭, 높이 및 간격은 각각 0.25m전후, 1.2m전후 및 1.0m전후인 것으로 조사되었다. 딸기 품종의 경우, 국산이 약 97.5%를 차지하고 있었고, 이 중 설향이 약 65.0%로서 가장 선호하고 있는 것으로 나타났다. 온실 내부 환경요인으로 38개 농가가 온도와 상대습도만 계측하였다. 2개 농가는 최근에 국산 제품인 스마트 팜 시스템을 도입한 농가도 있었다. 양액재배의 경우는 양액제어 시스템을 이용하고 있었다. 이 외에도 관비기를 사용하거나 환기 및 유동 팬을 사용하고 있는 농가도 있었다. 온습도 조절은 스마트 팜 시스템을 도입한 농가를 제외하고 약 85%인 34개 농가에서 측창이나 환기팬을 작동시키는 제어패널만을 이용하여 조절하였고, 수동으로 측창을 개폐하고 있는 농가도 10%정도인 4개 농가가 있었다. 보온 및 난방의 경우, 전체 대상 농가가 수막을 이용하고 있었다. 이 외에 필요에 따라 기름 및 전기보일러, 방열 램프 및 부직포 등을 병행하여 이용하는 농가도 다수 있었다.

블라인드 내장형 창호시스템의 에너지 성능 및 경제성 평가에 관한 연구 (Study on Energy Performance And Economic Evaluation of Windows System with Built-in Type Blinds)

  • 조원화;임남기
    • 한국건축시공학회지
    • /
    • 제10권2호
    • /
    • pp.97-104
    • /
    • 2010
  • 본 연구에서는 전열해석 프로그램인 피지벨(PHYSIBEL)을 사용하여 블라인드 내장형 창호시스템의 일사차단성능 및 단열성능에 따른 에너지 성능을 평가하였다. 피지벨 해석시 창호별 구성 재료의 열적특성과 해석조건을 결정하기 위해서 Mock-up시험을 실시하였으며, 컴퓨터 시뮬레이션을 통한 결과를 바탕으로 공동주택 기준층 1개 세대(33평형)를 대상으로 연간에너지 소비특성, 연간전열량, 연간 냉난방 비용을 분석하였다. 실험결과, 연간전열량은 일반 창호시스템 대비 블라인드 내장형 창호시스템에서 블라인드를 올린 경우 냉방시 10%, 난방시 11% 절감할 수 있으며, 블라인드를 내린 경우 냉방시 25%, 난방시 30%정도를 절감할 수 있는 것으로 나타났다. 블라인드 내장형 창호시스템의 냉 난방 부하 절감량은 일반 창호시스템에 비해 냉방시 283.3KWh, 난방시 76.3KWh 로 냉 난방 에너지 절감효과는 단위세대당 359.6KWh 절감시킬 수 있는 것으로 나타났으며, 이것은 단위세대당 연간 에너지원단위(TOE) 약 0.078toe, 이산화탄소톤($tCO_2$) $0.16tCO_2$을 절감시킬 수 있어 온실가스 저감에도 유리할 것으로 판단된다. 또한, 블라인드 내장형 창호시스템의 냉 난방비용 절감액은 일반창호시스템과 비교하여 연간 냉방비용 10만원, 난방비용 5만원으로 연간 냉 난방 비용을 약 15만원 정도 절감시킬 수 있는 것으로 나타났다.