• Title/Summary/Keyword: Insulation Degradation

Search Result 230, Processing Time 0.026 seconds

Condition Diagnosis by the Complex Accelerating Degradation for Fault Prediction & Estimation of Reliability on the Traction Motor - Dielectric loss and PD Properties according to High Voltage (견인전동기의 고강예측 및 신뢰성 평가를 위한 복합가속열화 상태진단 - 고전압 인가에 따른 유전손실 및 부분방전 특성 연구)

  • Wang, Jong-Bae;Baek, Jong-Hyen;Byun, Yoon-Sub;Park, Hyun-Jun
    • Proceedings of the KIEE Conference
    • /
    • 2000.07b
    • /
    • pp.1371-1373
    • /
    • 2000
  • In this paper, the complex accelerating degradation of traction motor driven with VVVF controlled inverter were performed on the form coil samples with the 200 Class insulation system. in order to evaluate the reliability and the long-term life. After aging, the dielectric and PD properties were investigated on the 10 cycles aging sample in the range of $20{\sim}160[^{\circ}C]$ and AC $250{\sim}2250[V]$ to diagnosis the condition of end-life and find the dominative factors of degradation.

  • PDF

Electrical Degradation Properties of EPR Cable Partially Irradiated by $^{60}Co-{\gamma}$ Rays (부분적으로 $^{60}Co-{\gamma}$선 조사된 EPR 케이블의 절연열화 특성에 관한 연구)

  • Lee, Sung-Ill
    • Elastomers and Composites
    • /
    • v.33 no.4
    • /
    • pp.238-245
    • /
    • 1998
  • In this paper, the electric property was investigated for insulation diagnosis of radiation of EPR electric power cables by partially irradiation with $^{60}Co-{\gamma}$ rays. As the rate of radiation increased from 100Mrad to 200Mrad, charging current and discharging current were increased from $1.03{\times}10^{-7}$(A) to $4.3{\times}10^{-9}$(A). In addition, we found charging current and discharging current of cables subjected to 50% and 16.7% irradiation changed the length of the part 1/2 to 1/6 as in comparison with cables degraded by 100% irradiation. For 22m and 66m of cables which had not been degraded yet, we realized the value of charging current and discharging current of 66m cables is three times higher than 22m cables. From these results, it is demonstrated that the possibility of utilizing charging current and discharging current as the diagnosis method of insulation degradation with irradiating EPR cables by $^{60}Co-{\gamma}$ rays.

  • PDF

Analysis on the electrical degradation characteristics of 2G HTS wires with respect to the electrical breakdown voltages

  • Kang, Jong O;Lee, Onyou;Mo, Young Kyu;Kim, Junil;Bang, Seungmin;Lee, Hongseok;Lee, Jae-Hun;Jang, Cheolyeong;Kang, Hyoungku
    • Progress in Superconductivity and Cryogenics
    • /
    • v.17 no.3
    • /
    • pp.37-40
    • /
    • 2015
  • Recently, the electrical insulation design for electrical apparatuses is important to cope with the tendency of high voltage. The degradation characteristics of a superconducting coil due to an electrical breakdown should be considered to design a high voltage superconducting coil. In this paper, the degradation characteristics of 2G high temperature superconducting (HTS) wires are studied with respect to electrical breakdown tests. To analyze the dependency of the degradation characteristics of 2G HTS wires, the electrical breakdown tests are performed with AC(alternating current) and DC(direct current) voltage. All tests are performed by applying various magnitudes of AC and DC breakdown voltages. To verify the degradation characteristics of 2G HTS wires, the tests are performed with various 2G HTS wires with respect to stabilizer materials. The degradation characteristics of 2G HTS wires, such as Ic(critical current) and index number are measured by performing electrical breakdown tests. It is found that the characteristics such as Ic and index number can be degraded by an electrical breakdown. Moreover, it is concluded that the degradation characteristics of 2G HTS wires are affected by the stabilizer material and applied voltages. The cross-sectional view of 2G HTS wires is observed by using a scanning electron microscope (SEM). As results, it is found that the degradation characteristics of 2G HTS wires are concerned with hardness and electrical conductivity of stabilizer layers.

Analysis on the dielectric characteristics of a composite insulation system composed of LN2 and GN2

  • Kim, Junil;Lee, Onyou;Mo, Young Kyu;Bang, Seungmin;Kang, Jong O;Lee, Hongseok;Nam, Seokho;Kang, Hyoungku
    • Progress in Superconductivity and Cryogenics
    • /
    • v.17 no.3
    • /
    • pp.33-36
    • /
    • 2015
  • A liquid nitrogen ($LN_2$) is usually used to be a coolant and insulant for a HTS coil system. HTS wires for a superconducting apparatus may be surrounded by gaseous nitrogen ($GN_2$) due to film boiling generated by a quench or voids occurred by electrical breakdown. The increased maximum electric field intensity at $GN_2$ may result in the degradation of dielectric strength of a HTS coil system. In this paper, a study on the dielectric characteristics of a composite insulation system composed of $LN_2$ and $GN_2$ is performed. A sphere-to-plane electrode system made with stainless steel is used to perform the experiments under AC and lightning impulse voltage condition. A sphere electrode is surrounded by $GN_2$ and a plane electrode is immersed into $LN_2$ to conduct dielectric experiments with a composite insulation system. The dielectric experiments are performed according to the level of $LN_2$ from the plane electrode to a sphere electrode. It is found that the dielectric characteristics of a composite insulation system are dependent on the level of $LN_2$ and the field utilization factor of an electrode system.

The Investigation on Thermal Aging Characteristics of Oil-Paper Insulation in Bushing

  • Liao, Rui-jin;Hu, En-de;Yang, Li-jun;Xu, Zuo-ming
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.1114-1123
    • /
    • 2015
  • Bushing is the key link to connect outer and inner insulating systems and also the essential electric accessory in electric power system, especially in the high voltage engineering (AC 1000kV, DC 800kV). This paper presented the experimental research of thermal aging characteristic of oil-paper insulation used in bushing. A thermally accelerated aging experiment at 90℃ was performed. The bushing models containing five layers of paper were sealed into the aging vessels and further aged for 250 days. Then several important parameters associated with the aging were observed and evaluated. The results showed that the degree of polymerization (DP) of papers gradually decreased. The DP values of outermost layer and middle layer fit well into the second-order kinematic model and first-order kinematic model, respectively. Less deterioration speed of the inter-layer paper than outer layer was confirmed by the variation of DP. Hydrolysis was considered as the main cause to this phenomenon. In addition, the logarithm of the furfural concentrations in insulation oil was found to have good linear relationship with DP of papers. Interestingly, when the aging time is about 250 days and DP is 419, the aging process reaches an inflection point at which the DP approaches the leveling off degree of polymerization (LODP) value. Both tanδ and acid number of oils increased, while surface and volume resistivity of papers decreased. The obtained results demonstrated that thermal aging and moisture absorbed in papers brought great influence to the degradation of insulating paper, leading to rapid decrease of DP and increase of the tanδ. Thus, the bushing should be avoided from damp and real-time monitoring to the variation of tanδ and DP values of paper is an effective way to evaluate the insulation status of bushing.

PD Signal Time-Frequency Map and PRPD Pattern Analysis of Nano SiO2 Modified Palm Oil for Transformer Insulation Applications

  • Arvind Shriram, R.K.;Chandrasekar, S.;Karthik, B.
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.2
    • /
    • pp.902-910
    • /
    • 2018
  • In recent times, development of nanofluid insulation for power transformers is a hot research topic. Many researchers reported the enhancement in dielectric characteristics of nano modified mineral oils. Considering the drawbacks of petroleum based mineral oil, it is necessary to understand the dielectric characteristics of nanofluids developed with natural ester based oils. Palm oil has better insulation characteristics comparable to mineral oil. However very few research reports is available in the area of nanofluids based on palm oil. Partial discharge (PD) is one of the major sources of insulation performance degradation of transformer oil. It is essential to understand the partial discharge(PD) characteristics by collecting huge data base of PD performance of nano modified palm oil which will increase its confidence level for power transformer application. Knowing these facts, in the present work, certain laboratory experiments have been performed on PD characteristics of nano $SiO_2$ modified palm oil at different electrode configurations. Influence of concentration of nano filler material on the PD characteristics is also studied. Partial discharge inception voltage, Phase resolved partial discharge (PRPD) pattern, PD signal time-frequency domain characteristics, PD signal equivalent timelength-bandwidth mapping, Weibull distribution statistical parameters of PRPD pattern, skewness, repetition rate and phase angle variations are evaluated at different test conditions. From the results of the experiments conducted, we came to understand that PD performance of palm oil is considerably enhanced with the addition of $nano-SiO_2$ filler at 0.01%wt and 0.05%wt concentration. Significant reduction in PD inception voltage, repetition rate, Weibull shape parameter and PD magnitude are noticed with addition of $SiO_2$ nanofillers in palm oil. These results will be useful for recommending nano modified palm oil for power transformer applications.

A Change of Surface Structure with Insulation Cover and Outdoor Cross-linked Polyethylene Insulated Wire Degraded by Salt Water (염수에 의해 열화된 절연커버 및 옥외용 가교폴리에틸렌 절연전선의 표면구조변화)

  • Choi, Chung-Seog;Gil, Hyoung-Jun;Kim, Hyang-Kon;Han, Woon-Ki
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1897-1899
    • /
    • 2004
  • In this paper, in order to analyze the characteristics of degradation by salt water with insulation cover and OC wire(outdoor cross-linked polyethylene insulated wire) used in power receiving system, an experimental apparatus has been designed and fabricated. An insulation cover and OC wire were installed in an experimental apparatus, and degraded in each case of 2%, 5%, 10% salinity during 12 weeks. An optical microscope was used to observe a changing process of sample surface, and an electrical safety was analyzed by measuring dielectric breakdown voltages of samples. As salinity increased, so ununiformity of sample surface increased. The breakdown wasn't produced to 50kV about samples regardless of salinity, testing period.

  • PDF

Surface Discharge Characteristics in Dry-Air on Laminated Epoxy Solid Dielectrics and Conductive Particle (적층된 에폭시 고체유전체와 도전성 파티클에 대한 Dry-Air의 연면방전특성)

  • Lim, Dong-Young;Jeon, Jong-Cheul;Bae, Sungwoo;Lee, Kwang-Sik;Park, Won-Zoo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.30 no.2
    • /
    • pp.93-101
    • /
    • 2016
  • This paper presents the surface discharge characteristics in Dry-Air on laminated epoxy solid dielectrics and conductive particles in order to provide the valuable information for the insulation design of eco- friendly gas insulated switchgear. To improve insulation performance, the three types of the laminated epoxy solid dielectrics were proposed, and it was revealed that their surface discharge characteristics were similar to the bakelite dielectrics of same-laminated types. From the surface discharge characteristics of dry air, it was demonstrated that the effect of conductive particles on surface discharge voltage was dominant when there are this particles at the shortest electrode gap and that the degradation of insulation performance on the conductive particles was evident in epoxy than teflon. These phenomena were interpreted in terms of particle-triggered discharge mechanism and electric field of triple junction, respectively.

Improvement on Property of Insulation in PT of Epoxy Mold Type (에폭시 몰드형 PT의 절연특성 개선)

  • Song, Jae-Joo;Kim, Sung-Hong;Choi, Myeong-Ho;Lee, Jae;Lim, Sung-Hun;Han, Byung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.09a
    • /
    • pp.67-71
    • /
    • 2001
  • PT of epoxy mold type have tendency to occur dielectric breakdown in high voltage system. These are using for measurement of voltage or protection of system and application voltage is 25.8kV. Therefore, for improving a lots of problems like as partial discharge, we had analyze on the destroyed Epoxy molded type PT and processing of production. As a results, we concluded that the reason of dielectric breakdown was defect of processing and degradation of insulation by electrical stress. In this work, We presented a method of solution in processing of production. which is reduction of the PO which was occurred at the insulation material. so we must many try to remove faults, these problems are mainly to winding methods of 1st coil. the other side, Reformation of 1st coil improved property of PD and we could prove it with experiments.

  • PDF

A Diagnostic Technique for Power Distribution Line Facilities by the Corona Detector (코로나 검출기를 이용한 배전설비 진단기법)

  • Cho, Yong-Sang;Song, Gyu-So;Choi, Yu-Seong;Park, Tae-Seong
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.3
    • /
    • pp.588-593
    • /
    • 2011
  • The airpollutant may accelerate degradation of power line facilities, and may reduce the life of the electric facilities. In case of korea, there are a tendency that the density of air pollution may be increased by industrial development. while lack of research activity and establishment of a countermeasure on this issue. Recently the occurrence of electricity failure have been reduced on the power transmission and distribution lines. but the occurrence of electricity failure by insulator itself has been increased. It means that we should have develop more clear technique for detection of the wrong insulator. In this study to provide a method for detection of the insulator failure or effective management of the troubled insulator, we analyze the chemical composition of the insulator which used on power distribution line at the sea side locations. To define the relation between insulation and corona intensity, we design and develop an corona detector. We define the variation of insulation by pollution changes on the insulator and verify quantitative relation between corona and insulations using the corona detector.