• Title/Summary/Keyword: Hot water radiant heating system

Search Result 27, Processing Time 0.022 seconds

Experimental Study on a Low-Temperature Hot Water Capillary Radiant Floor Heating System (저온온수 모세유관 바닥복사 난방시스템의 성능에 관한 실험적 연구)

  • Cho, Jinkyun;Park, Beungyong;Lee, Yongjun;Chong, Wonho
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.30 no.2
    • /
    • pp.68-82
    • /
    • 2018
  • Radiant floor heating systems with capillary tubes are energy saving systems in which hot water is circulated into capillary tube with a small diameter. In this study, the heating performance of capillary tube system is investigated in an experimental study and a simulation model. The results of the study showed that, the capillary tube radiant floor heating system maintains a more stable floor surface temperature in comparison a PB pipe system. In terms of energy consumption, the capillary tube radiant floor heating system proved to be more efficient than the PB pipe heating system at $40^{\circ}C$ of low temperature hot water supply. The difference between water temperature and room temperature can be held low for heating which saves energy. Low temperature radiant floor heating system with capillary tubes have significant advantages such as health improvement, low energy cost, optimum use of heat source(boiler) and higher operational efficiency.

The Effects of Hot Water Supply on Energy Consumption for Floor Radiant Heating System (바닥복사 난방시스템의 공급온수특성에 따른 에너지 소비특성 연구)

  • Song, Jae-Yeob;Ahn, Byung-Cheon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.15 no.4
    • /
    • pp.32-38
    • /
    • 2019
  • In this study, the effect of hot water supply flow rates on energy consumption for radiant floor heating system in apartment were researched by computer simulation. The parametric study of different hot water supply flow rates was done with regard to energy performance and control characteristics, respectively. Also the effect of different hot water supply flow rates on the hot water supply temperatures is studied. As a result, energy consumption were reduced but the response time is increased by reducing the supply flow rate. And energy consumption can be saved by adjusting the hot water supply temperatures with different supply flow rates.

The Effects of Hot Water Supply Temperature on Indoor Thermal Characteristics for Floor Radiant Heating System (바닥복사 난방시스템의 공급온수온도가 실내 열환경에 미치는 영향)

  • Ahn, Byung-Cheon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.14 no.4
    • /
    • pp.13-19
    • /
    • 2018
  • The Effects of hot water supply temperature on indoor thermal characteristics for floor radiant heating system in residential apartment were researched by computer simulation. The parametric study on hot water supply temperatures with different outdoor air temperatures was done with regard to energy performance and control characteristics, respectively. As a result, the maximum overshoot of indoor air temperature and energy consumption were reduced by adjusting the hot water supply temperatures with outdoor air temperatures.

Research on the actual condition of 'Under Floor Radiant Heating for Apartment Housing' (주거용건물의 바닥복사 난방방식에 대한 실태조사 연구)

  • Woo, Byung-Kwan;Lee, Sung;Kim, Sam-uel
    • KIEAE Journal
    • /
    • v.7 no.5
    • /
    • pp.81-86
    • /
    • 2007
  • The research analyzes the arrangement of boiler and hot water header, the method of radiator pipe setting, hot water supply control, hourly heating situation of each room for underfloor radiant heating systems in Korea and suggests an alternative to improve to efficient heating method. One of the best options for install position of hot water distributor is under kitchen sink which is center point of all rooms, according to previous research of the energy saving strategies. When the radiator pipes are arranged to each individual room instead of bedrooms through livingroom and kitchen, it has energy saving effects. For rooms without occupancy according to a time period, hot water supply method should be intermittent heating rather than continuous heating. For this intermittent heating method, individual control of hot water supply is more practical, and it can lead to massive energy savings. The intermittent heating system has time-lag, so it is more effective in energy saving with mild and comfort condition if the spaces are preheated by automatic control equipment prior to required time.

An Experimental Study on Two Parameter Control for Radiant Floor Heating System

  • Cho, Sung-Hwan;Tae, Choon-Seob;Jang, Chel-Yong
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.6
    • /
    • pp.136-147
    • /
    • 1998
  • An experimental facility consisting of two 3$\times$4.4$\times$2.8m rooms identical in construction is built. Each room has a control system and storage tank supplying hot water to the radiant floor heating system. The facility enables simultaneous comparison of two different control strategies each implemented in a separate room. The operating performance of three kinds of flow control scheme is tested and compared in this study: (ⅰ) conventional on-off control based on feedback from room air temperature (ⅱ) TPSC(two parameter switching control )(ⅲ) TPOC(two parameter on-off control). Results show that TPSC and TPOC using room air and surface temperature sequentially as feedback signal to control hot water supply is the better temperature regulation scheme than conventional control based on feedback from only room air temperature. They are good candidates for the room with radiant floor heating system under continuous and intermittent heating mode.

  • PDF

Performance Evaluation of the Capillary Tube Radiant Floor Cooling & Heating System (모세유관 바닥복사 냉·난방 시스템의 성능평가)

  • Seo, Yu-jin;Kim, Taeyeon;Leigh, Seung-bok
    • KIEAE Journal
    • /
    • v.12 no.4
    • /
    • pp.89-95
    • /
    • 2012
  • At present, many countries are trying to reduce green gas emissions to mitigate the effects of these gases on climate change. Year after year, there have been efforts to cut energy use for heating and cooling. Heating and cooling systems, common in all forms of housing, are increasing due to the constant supply of new housing resulting from improvements in economic growth and the quality of life. Thus, studies related to the design of cooling and heating systems to improve energy efficiency are expanding. Among the new designs, radiant floor cooling and heating systems which use capillary tubes are becoming viable means of reducing energy use. Radiant floor cooling and heating systems which use capillary tubes are creative and sustainable systems in which cool and hot water is circulated into capillary tube which has small diameter. In this study, the cooling and heating performance of this type of capillary tube system is investigated in an experimental study and a simulation using TRNSYS. The results of the experimental study show that under a peak load, a capillary tube radiant floor cooling system using geothermal energy can achieve desired indoor temperature without an additional heat source. The set room air temperature is maintained while the floor surface temperature, PMV and PPD remain within the comfort range. Also, this system is more economic than a packaged air conditioner system due to its higher COP. The results of the simulation show that the capillary tube radiant floor heating system maintains set temperature more stable than a PB pipe radiant floor heating system due to its lower supply temperature of hot water. In terms of energy consumption, the capillary tube radiant floor heating system is more efficient than the PB pipe radiant floor heating system.

A Study on the Heating Characteristics of Radiant Floor Panel Using Heat Pipes with the Double Wick (이중 윅 타입 히트파이프를 이용한 바닥복사패널의 난방특성 연구)

  • Kim, Yong-Ki;Lee, Tae-Won
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.2
    • /
    • pp.183-189
    • /
    • 2012
  • Most of the domestic residential buildings have used the traditional radiant heating system, circulating hot water through the cross-linked polyethylene(PE-X) pipe buried in the floor panel of the heating space. New type of the heating panel was recently developed using heat pipes with double wicks. Some experiments were carried out in this study to verify the thermal characteristics of this heating system at the unit heating space which surrounded by outer space whose temperature of air be maintained scheduled value with time. Through the various experiments with several parameters, such as flow rate, inlet and outlet temperatures of hot water and the heating duration and so on, we found that the floor heating system with heat pipes was able to reduce the pumping power for hot water circulation by 4~31% compared with the conventional panel heating system using PE-X pipe. These results could be used for optimal design and efficient operation of the heating system as well as improvement of thermal comfort.

Experimental Study on the Indoor Thermal Characteristics for Floor Radiant Heating System (바닥복사 난방시스템의 실내 열환경 특성에 대한 실험적 연구)

  • Song, Jae-Yeob;Ahn, Byung-Cheon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.17 no.3
    • /
    • pp.1-12
    • /
    • 2021
  • In this study, the effects of various operational conditions for floor radiant heating system were researched by experiments. Hot water supply set temperature, indoor air set temperature and supply water flowrate were considered as operational conditions. The control method for this system is On-Off control of automatic thermostatic valve. The purpose of this study is to evaluate indoor thermal control characteristics and energy performance, respectively. As a result, if lower supply water temperature is applied, the supply and return temperature difference is reduced and energy consumption of heat supply is also reduced.

An analysis of the thermal characteristics for optimal design and operation of the radiant heating panels (복사난방패널의 설계 및 운전을 위한 열적 특성 분석)

  • Lee, T.W.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.9 no.2
    • /
    • pp.180-188
    • /
    • 1997
  • The theoretical analysis and experiment with simulator were performed to obtain the temperature distributions in radiant heating panel and heat supply from hot water to heating space for the purpose of the development of comfortable living space from a point of view of the improvement of air quality and the enhancement of system efficiency. The relations of various parameters, such as pipe pitch, room temperature as well as flow rate and temperature of hot water and so on, with the rate of heat supplied, mean temperature and maximum temperature difference at panel surface were discussed. The effects of these parameters were also verified on the thermal performance of heating panel using the relations which could be used for the optimal design and operation of the radiant heating panel.

  • PDF

A Study on the Performance of Automatic Thermostatic Valves for Hot Water Heating System in Residential Buildings (공동주택 난방용 자동온도조절기의 성능해석 연구)

  • Ahn, Byung-Cheon;Lee, Tae-Won;Kim, Yong-Ki;Song, Jae-Yeob
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.457-462
    • /
    • 2005
  • In this study, the performance of automatic thermostatic valves according to each heating method of a large scale residential building were researched by simulation. The flow characteristics of the entire pipe networks of the hot water radiant heating system is analized by using linear analysis method. For the analysis of unsteady heat transfer phenomena in each household, the method of using electric equivalent R-C circuit is applied.

  • PDF