• Title/Summary/Keyword: High voltage relay

Search Result 77, Processing Time 0.026 seconds

Analysis of the Bouncing Phenomenon due to the Deterioration of the Relay Contact (릴레이 접점 열화에 따른 바운싱 현상 분석)

  • Ryu, Jae-Man;Choi, Sun-Ho;Park, Ki-Hoon;Huh, Chang-Su
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.27 no.6
    • /
    • pp.383-388
    • /
    • 2014
  • The relay used is gradually increased. Because it is possible to easily control the high voltage and current. Bounce phenomenon is generated in contact during operation relay. As the result, arc is generated at the contact, thereby shortening the contact lifetime. In this study, we analyzed the bouncing phenomenon due to deterioration. It can be seen from the experimental results, and it is minimized at about 100,000 times. Bouncing phenomenon to increase again after the minimization. Consequently, the bouncing related to contact weight and shape of contact surface.

Analysis of the Bounce Phenomenon According to the Load of the Relay Contact (릴레이 접점의 부하에 따른 바운스 현상 분석)

  • Choi, Sun-Ho;Kim, Kwan-Sik;Ryu, Jae-Man;Huh, Chang-Su
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.28 no.2
    • /
    • pp.115-119
    • /
    • 2015
  • The power relay can be easily controlled with high voltage and current through the contacts. For this reason, has become widely used range in a variety of applications. In this study, we measured the contact resistance between the bouncing phenomenon of contact due to the change of load. The results of the experiment, the contact resistance increases with the deterioration of the contact, it is possible to predict the life of the relay contacts through the contact resistance. And relay bounce duration time have occurred in 3.5 ms or less. In addition, it is possible to use the results to design an arc suppression circuit device.

Development of an Algorithm for Detecting High Impedance Fault in Low Voltage DC Distribution System using Accumulated Energy of Fault Current (고장전류의 누적 에너지를 이용한 저압직류 배전계통의 고저항 지락고장 검출 알고리즘 개발)

  • Oh, Yun-Sik;Noh, Chul-Ho;Kim, Doo-Ung;Gwon, Gi-Hyeon;Han, Joon;Kim, Chul-Hwan
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.5
    • /
    • pp.71-79
    • /
    • 2015
  • Recently, new Low Voltage DC (LVDC) power distribution systems have been constantly researched as uses of DC in end-user equipment are increased. As in conventional AC distribution system, High Impedance Fault (HIF) which may cause a failure of protective relay can occur in LVDC distribution system as well. It, however, is hard to be detected since change in magnitude of current due to the fault is too small to detect the fault by the protective relay using overcurrent element. In order to solve the problem, this paper presents an algorithm for detecting HIF using accumulated energy in LVDC distribution system. Wavelet Singular Value Decomposition (WSVD) is used to extract abnormal high frequency components from fault current and accumulated energy of high frequency components is considered as the element to detect the fault. LVDC distribution system including AC/DC and DC/DC converter is modeled to verify the proposed algorithm using ElectroMagnetic Transient Program (EMTP) software. Simulation results considering various conditions show that the proposed algorithm can be utilized to effectively detect HIF.

Effect on the Relay Contact Characteristics According to the Presence of Electrical Connection (릴레이 접점 특성에 미치는 전기적 접속의 영향)

  • Jin, In-Young;Choi, Sun-Ho;Kim, Kwan-Sik;Huh, Chang-Su
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.29 no.10
    • /
    • pp.647-651
    • /
    • 2016
  • The power relay can easily control high voltage and high current through metallic contacts. In addition, it has the advantage in reasonable price. So it has been used in many applications. But the power relay has a weak point by mechanical movements. These mechanical movements cause the bouncing phenomenon. Arc and bouncing phenomenon are the main causes of electric abrasion and material erosion. In this study, mechanical repetitive experiments and repetitive experiments in electrically connected state are conducted. Then these two experimental results in terms of bouncing phenomenon and changes in the contact surface are compared. In all number of repetitions, contacts in an electrically connected state cause smaller number of bounce. Also, It has lower contents of silver on eroded surface than the other. The experimental results would be helpful to the further study of contacts life span.

Variable Charger of Vehicle using Relay (릴레이를 이용한 차량용 배터리의 가변 충전기)

  • Song, Sung-Geun;Chung, Seung-Tae;Kang, Sung-Gu;Lee, Sang-Hun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.9
    • /
    • pp.47-56
    • /
    • 2012
  • This research is to develop satiable battery charger with a variety of capacity and voltage specifications of battery. For this, voltage or current were controlled through buck converter which is DC voltage that already received three-phase at primary side and passed bridge rectifier diode. And, it was comprised of full-bridge converter and HFTR for insulation and a square wave AC. The transformer primary side was comprised in series to divide certain charging current and the secondly side was comprised of 6 fixed transformers so that they can generate certain amount of power and various output voltage through relay parallel compound 6 DC Link outputs. To confirm such structure's verification and validity, simulation with PSIM was conducted, and validity of proposed variable charger system was verified through 3kW stack production.

Study on the Ground Fault Protection in 6.6KV Ungrounded Power System SGR Malfunction or Non-Tripping (선택지락보호계전기 오.부동작에 관한 연구)

  • Kim, Byung-Tae;Lee, Dal-Woo;Jeon, Myung-Soo
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.3
    • /
    • pp.296-301
    • /
    • 2008
  • This paper presents a study on the ground fault protection in 6.6KV ungrounded power system relay(SGR) malfunction or non-tripping. Ground test had made on 6.6KV HV(high voltage) system, Some of domestic and oversea's SGR products are different from their own specific characteristics. This study on the ground protection relay 6.6KV power supply system is focused to protect human.

Method for improving the accuracy of a voltage transformer considering hysteresis characteristics (히스테리시스 특성을 고려한 전압 변성기 오차 개선 방법)

  • Kang, Yong-Cheol;Lee, Byung-Eun;Park, Jong-Min;Cha, Sun-Hee;Jang, Sung-Il;Kim, Yong-Guen
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.208-209
    • /
    • 2006
  • Voltage Transformer is used to transform high voltage into low voltage to input signal of protection relay. Most of the Voltage Transformers use the iron core which maximizes the flux linkage. The ratio of the Voltage Transformer depends on the transformer turns ratio. The current which flows in the Voltage Transformer has non-linear characteristic caused by hysteresis of the iron core, it causes a voltage loss in the winding impedances which makes measurement errors. This paper describes an error compensation method considering hysteresis characteristic. The proposed compensation method improves error by calculating the primary current from the exciting current of the hysteresis loop in the Voltage Transformer, compensating the voltage loss.

  • PDF

Development of Current-based Compact Digital Protective Relay for Induction Motor Protection (중용량 전동기보호를 위한 전류형 디지털 보호계전기 개발)

  • Jung, Jong-Jin;Kim, Joong-Pyo;Shin, Jong-Han;Park, Jang-Soo
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.140-142
    • /
    • 2005
  • This paper describes the current- based compact digital motor protective relay for low and high voltage induction motors, which are widely used in industrial and commercial power systems. The existing protective relays for motor protection had only overload, short circuit, reverse phase, open circuit and grounding protective elements, and measurement, start/stop control function. But in present day, for automation system, various functions are required, especially motor management and sequence control function and more. To meet these requirements, we developed an economic current-based compact digital motor protective relay which had various function to control, manage and monitor the induction motor.

  • PDF

Dynamic Property of Ground Overvoltage Relay in Large Turbine Generator (대용량 터빈발전기에서 접지과전압 계전기의 동작 특성)

  • Kim, Hee-Dong;Lee, Young-Jun;Kim, Byong-Han;An, Joon-Young;Chae, Gyu-Jin
    • Proceedings of the KIEE Conference
    • /
    • 1999.11d
    • /
    • pp.1044-1047
    • /
    • 1999
  • This paper deals with the dynamic property of ground overvoltage relay in large turbine generator. Relay operation is based on detecting the fundamental voltages originating from the generator. Calculations of fault voltage and current are reviewed for the neutral ground resistance. The frequency, ampitude and waveform of individual harmonics were measured using power quality analyzer and memory hi-corder at the secondary side of ground potential transformer. The ac and dc high-potential tests were applied to evaluate the condition of generator, main and auxiliary transformer, isolated phase bus, potential transformer, surge capacitor and arrester.

  • PDF

Fault Location Estimation for High Impedance Fault using Wavelet Transform (Wavelet 변환을 이용한 고저항 지락사고 고장점 추정)

  • Kim, Hyun;Kim, Chul-Hwan
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.8
    • /
    • pp.369-373
    • /
    • 2000
  • High impedance fault(HIF) is defined as a fault that the general overcurrent relay can not detect or interrupt. Especially when HIF occurs in residential areas, energized high voltage conductor results in fire hazard, equipment damage or personal threat. This paper proposes a fault location estimation algorithm for high impedance fault using wavelet transform. The algorithm is based on the wavelet analysis of the fault voltage and current signals. The performance of the proposed algorithm is tested on a typical 154kV korean transmission line system under various fault conditions. From the tests presented in this paper it can be concluded that a fault location estimation algorithm using wavelet transform can precisely calculate the fault point for HIF.

  • PDF