• 제목/요약/키워드: High voltage insulation material

검색결과 206건 처리시간 0.023초

154 kV급 HTS 케이블의 절연설계 및 굴곡시험 (Design of Insulation and Bending Test for a 154 kV Class HTS Cable)

  • 최진욱;최재형;임응춘;김해종;조전욱;김상현
    • 한국전기전자재료학회논문지
    • /
    • 제21권11호
    • /
    • pp.1024-1028
    • /
    • 2008
  • It is important that study on cryogenic electrical insulation design to develop the cold dielectric(CD) type HTS cable because the cable is operated under the high voltage environment in cryogenic temperature. This paper proposes two types of insulation design to carry out the maximum insulation design for 154 kV-class HT cable. The proposed insulation design method takes into consideration AC and lightning impulse withstand voltage so as to prevent AC breakdown for power frequency operating voltage during operating the cable and breakdown for lightning impulse voltage. The final insulation thickness is determined by selecting high value out of two insulation thickness calculated through the two insulation design methods. And we researched electrical insulation characteristics of HTS cable according to bending ratio and the number of bending.

고압케이블의 절연열화 특성 (Characteristics of Insulation Aging in High Voltage Cables)

  • 김경열
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2010년도 하계학술대회 논문집
    • /
    • pp.88-88
    • /
    • 2010
  • High Voltage cross-linked polyethylene (XLPE) cables are widely used in a thermal power plant. These cables had been in service for 26 years. The insulation condition of six 6 kV XLPE cables was estimated by insulation diagnostic analyzer (IDA) with voltage amplifier. IDA was measured dissipation factor and capacitance of the whole cable as a function of frequency and voltage. This system measures in the frequency range from 0.1 to 10 Hz at each voltage level. Six XLPE cables are judged good condition, but three cables are analyzed at an aged condition.

  • PDF

고압전동기 고정자 권선 절연재료의 미세구조 특성 (Microstructure Property of High Voyage Motor Stator Insulation)

  • 김희동;주영호
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1999년도 춘계학술대회 논문집
    • /
    • pp.513-517
    • /
    • 1999
  • High voltage motor(rated 6.6kV and 448kw) has failed in the stator endwinding area during normal service. Experiments on microstructure property were conducted using the control and aged insulations, which were drawn out from stator windings of the high voltage motor. The analyses were characterized using stereozoom microscope(SM), scanning electron microscope(SEM) and energy dispersive X-ray spectroscopy(EDS). SM result shows that large voids are present in the interface between turn insulation and groundwall insulation. SEM results indicated that the groundwall insulation is rarely thermal stress. EDS results showed that chemical elements in the high voltage motor stator insulations were Al, Si, O, K and Fe.

  • PDF

Double Pancake Coil형 고온초전도 변압기의 전기적 절연 특성 (Dielectric Insulation Properties of Double Pancake Coil Type HTS Transformer)

  • 백승명;정종만;이현수;한철수;김상현
    • 한국전기전자재료학회논문지
    • /
    • 제16권2호
    • /
    • pp.151-156
    • /
    • 2003
  • High temperature superconductor can only be applied against an engineering specofication that has to be determined for each particular application form the design requirements for economic viability and for operation margins in service. However, in order to realize the HTS transformer, it is necessary to establish the high voltage insulation technique in cryogenic temperature. Therefore, the composite insulation of double pancake coil type transformer are described and AC breakdown voltage characteristics of liquid nitrogen(LN$_2$) under HTS pancake coil electrode made by Bi-2223/Ag are studied. The Breakdown of LN$_2$ is dominated electrode shape and distance. The influence of pressure on breakdown voltage is discussed with th different electrode. For the electrical insulation design of turn-to-turn insulation for the HTS transformer, we tested breakdown strength of insulation sheet under varying pressure. And we investigated surface flashover properties of LN$_2$ and complex conition of cryogenic gaseous nitrogen(CGN$_2$) obove a LN$_2$ surface. The surface voltage of GFRP was measured as a function of thickness and electrode distance in LN$_2$ and complex condition of CGN$_2$ above a LN$_2$ surface. this research presented information of electrical insulation design for double pancake coil(DPC) type HTS transformer.

전력케이블 열화진단기법의 현장적용 (Field Application of Power Cable Diagnosis System)

  • 김주용;한재홍;송일근;김상준;이재봉;오재형
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 일렉트렛트 및 응용기술
    • /
    • pp.148-151
    • /
    • 2002
  • In order to prevent the failures of underground distribution power cables we need to measure insulation condition in the field. Until now we used DC high voltage as a power source for the cable diagnosis but it was not proper method to the XLPE insulation cables because DC high voltage can affect sound insulation and can't diagnose exactly insulation degradation. For these reasons we imported isothermal relaxation current measurement system called by KDA-1 from germany but it's reliability did not proved in our URD cables. DC voltage decay measurement system was developed by domestic company but they don't have field experience. In this paper we tried to prove reliability of these two systems in the field. Through the field diagnosis and Ac breakdown test the two systems showed similar results.

  • PDF

6.6 kV급 고압전동기 고정자 권선의 절연열화 평가 (Assessment of Insulation Aging in 6.6 kV Class High Voltage Motor Stator Windings)

  • 김희동;김병한
    • 한국전기전자재료학회논문지
    • /
    • 제19권11호
    • /
    • pp.1067-1071
    • /
    • 2006
  • Prior to destructive testing, diagnostic tests were performed in ten high voltage motors. Diagnostic tests included polarization infer, ac current, dissipation factor$(tan{\delta})$ and partial discharge magnitude. The rewind of motet slater insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 8 motor failed near rated voltage of 19.0 kV. The breakdown voltage of No. 4 motet was 7.0 kV which is lower that expected for good quality coils in 6.6 kV class motors. The failure was located in a line-end coil at the exit from the core slot. These two motors began operation in 1994. While testing No. 7 motor, flashover occurred between the stator winding and the stator frame at 15 kV. The relationship between the diagnostic test and the drop in insulation breakdown voltage was analyzed.

고압전동기 고정자 권선의 절연열화 분석 (Analysis of Insulation Aging in High Voltage Motor Stator Windings)

  • 김희동;공태식;이영준
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2006년도 하계학술대회 논문집 Vol.7
    • /
    • pp.200-203
    • /
    • 2006
  • Prior to destructive testing, diagnostic tests were performed in eight high voltage motors. Diagnostic tests included polarization index, ac current, dissipation factor($tan{\delta}$) and partial discharge magnitude. The rewind of motor stator insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 1 motor failed near rated voltage of 12.96 kV. The breakdown voltage of No. 4 motor was 6.99 kV which is lower that expected for good quality coils in 6.6 kV class motors. The failure was located in a line-end coil at the exit from the core slot. These two motors began operation in 1994. While testing No. 7 motor, flashover occurred between the stator winding and the stator frame at 15 kV. The relationship between the diagnostic test and the drop in insulation breakdown voltage was analyzed.

  • PDF

Double Pancake형 고온초전도 변압기의 전기적 절연 특성 (Dielectric Insulation properties of Double Pancake coil type HTS Transformer)

  • 백승명;정종만;이정원;김상현
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 하계학술대회 논문집
    • /
    • pp.494-498
    • /
    • 2002
  • HTS transformer experimentally. High temperature superconductors can only be applied against an engineering specification that has to be determined for each particular application form the design requirements for economic viability and for operation margins in service. High temperature superconducting(HTS) power apparatus are very promising candidates for application. Especially, these advantages make superconducting transformers very promising candidates for application in electrical power engineering and locomotives. In order to realize the HTS transformer, it is necessary to establish the high voltage insulation technique in cryogenic temperature. So far, insulation research of Pancake type HTS transformer is lacking nothing but insulation research of . solenoid type transformer consisted. Therefore, the composite insulation of double pancake coil type transformer are described and ac breakdown voltage characteristics of liquid nitrogen(LN$_2$) under HTS pancake coil electrode made by Bi-2223/Ag are studied. Breakdown in LN$_2$ is dominated electrode shape and distance. The relation between surface flashover voltage is considered for FRP. This research presented basis information of electrical insulation design for double pancake coil type HTS transformer.

  • PDF

실리콘 폴리머의 내전압 및 절연특성에 관한 연구 (A Study on Dielectric Strength and Insulation Properly of PDMS)

  • 지원영
    • 한국전기전자재료학회논문지
    • /
    • 제14권11호
    • /
    • pp.941-946
    • /
    • 2001
  • The fundamental study on HTV silicone for insulation material has been performed. In order to estimate the chemical behavior of siloxane under high voltage, H-NMR, GPC and vinyl contents measurement were used. As an experimental results, after high voltage stress, the molecular weight of siloxane are increased, the vinyl contents of siloxane are decreased. The dielectric strength of vinyl group containing siloxane was lower than only methyl containing siloxane.

  • PDF

온도와 습도에 따른 초고압 변압기용 앵글링 프레스보드 특성 (Angle Ring Press Board Characteristic in Accordance with Temperature and Humidity for High Voltage Transformer)

  • 서왕벽
    • 한국전기전자재료학회논문지
    • /
    • 제33권1호
    • /
    • pp.60-64
    • /
    • 2020
  • In this study, to develop angle ring pressboards for high voltage transformers, the radius and thickness are modified under the conditions of temperature and humidity. In particular, a pressboard with a thickness of 6 mm and a radius at the angled part were investigated based on the simulation of the principal stress from the angled optimization profile shape. As a result, by the appropriate application of a higher temperature, the solid insulation can be improved to reduce the moisture content for an optimized profile angle of a high voltage transformer. This also results in the improvement of the safety factor by 25%. It is determined that the electrical insulation properties of pressboards in high voltage transformers can be enhanced by improving their properties.