• Title/Summary/Keyword: Heat absorption

Search Result 944, Processing Time 0.03 seconds

Performance Characteristic of the Compression-Absorption Hybrid Heat Pump Cycles (흡수압축 하이브리드 히트펌프 사이클의 성능특성)

  • Yoon J. I.;Kwon O. K.;Yang Y. M.
    • Journal of the Korean Institute of Gas
    • /
    • v.3 no.1
    • /
    • pp.14-20
    • /
    • 1999
  • This study describes the results of Coefficient of Performance(COP) analysis by cycle simulation for two types of absorption-compression hybrid cycle using the Water/Lithium Bromide solution pair. These types are basic hybrid systems introducing a mechanical compression process into the refrigerant vapor phase of the single effect absorption cycle. In absorption-compression hybrid cycles, coefficient of performance is improved compared with absorption cycle. Hybrid cycle Type 2 is considered as a key technology to support energy utilization system, given its capability of utilizing waste heat to drive system with a high level of efficiency.

  • PDF

Effects of Operation Conditions on the Performance of Type II LiBr-H2O Absorption Heat Pump (제 2종 LiBr-H2O 흡수식 히트펌프의 운전 변수에 따른 성능 특성 수치 해석)

  • Yoon, Jun Seong;Kwon, Oh Kyung;Cha, Dong An;Bae, Kyung Jin;Kim, In Gwan;Kim, Min Soo;Park, Chan Woo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.29 no.1
    • /
    • pp.7-14
    • /
    • 2017
  • This study carried out a numerical analysis of the effects of hot waste water supply on the performance of a Type II absorption heat pump. There are two types of hot waste water supply, regular series flow and reverse series flow. Also it investigated the interaction between each type of flow and heat exchange solutions. As the effectiveness of heat exchange solutions increase, the steam generation and (COP) increase as well. If the effectiveness of a heat exchange solution is lower than 0.566, the steam generation rate of the reverse flow is lower than that of the regular series flow. A high effectiveness of heat exchange solution is therefore required to make a larger amount of steam in reverse series flow than with ordinary series flow. The COP difference between the two types of flow decreases with the increasing effectiveness of the heat exchange solution. Thus, a reverse flow type absorption heat pump can match the high steam generation rate and COP of the ordinary flow type when a highly effective heat exchange solution is applied.

Design of an Absorption Heat Transformer with Methanol-Glycerine System as a Working Fluid (메탄올-글리세린 계를 작동유체로 하는 변형흡수식 열펌프 설계)

  • Chung, Chan-Kyo;Min, Byong-Hun
    • Clean Technology
    • /
    • v.11 no.1
    • /
    • pp.13-19
    • /
    • 2005
  • An absorption heat transformer for energy recovery has been investigated using methanol-glycerine. The simulated calculation of theoretical thermal efficiency was performed based on the thermodynamic properties of the working fluid over various operating conditions. The thermal efficiency of higher than 0.4 was obtained by raising industrial waste heat, $70-80^{\circ}C$, by $40^{\circ}C$ in this system.

  • PDF

Evaluation of water absorption and thermal insulation properties of flooring board (플로어링보드의 흡수성 및 단열성 평가)

  • Park, Cheul-Woo;Lim, Nam-Gi;Lee, Dong-Gun;Jo, Young-Bin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2021.11a
    • /
    • pp.178-179
    • /
    • 2021
  • Comparing the absorption volume of test pieces immersed over time in room temperature moisture with weight, WF absorbed about 40% more than PLAIN, and PLAIN stopped absorbing after 10 minutes, but WF continued to absorb. It is thought that the woven fabric layer of the core material continued to absorb moisture. In the heat transfer test, the test piece to which only WF was applied had a temperature difference of about 2℃ compared to PLAIN, and when the insulating liquid was sprayed, there was a difference in heat transfer properties of up to 5℃. This is judged to have low heat transfer properties of the basic woven fabric, but the heat insulating liquid also further reduces heat transfer properties.

  • PDF

Numerical analysis of the coupled heat and mass transfer phenomena in a metal hydride hydrogen storage reactor(I) - Model development of analyzation for hydrogen absorption reaction using the $LaNi_5$ bed (금속수소화물 수소저장 용기 내부의 열 및 물질전달 현상에 대한 수치적 연구(I) - $LaNi_5$ 베드를 이용한 수소 흡장반응 해석 모델 개발)

  • Nam, Jinmoo;Ju, Hyunchul
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2010.06a
    • /
    • pp.225.1-225.1
    • /
    • 2010
  • Within recent years attention has been focused on the method of hydrogen storage using metal hydride reactor due to its high energy density, durability, safety and low operating pressure. In this paper, a numerical study is carried out to investigate the coupled heat and mass transfer process for absorption in a cylindrical metal hydride hydrogen storage reactor using a newly developed model. The simulation results demonstrate the evolution of temperature, equilibrium pressure, H/M atomic ratio and velocity distribution as time goes by. Initially, hydrogen is absorbed earlier from near the wall which sets the cooling boundary condition owing to that absorption process is exothermic reaction. Temperature increases rapidly in entire region at the beginning stage due to the initial low temperature and enough metal surface for hydrogen absorption. As time goes by, temperature decreases slowly from the wall region due to the better heat removal. Equilibrium pressure distribution appears similarly with temperature distribution for reasons of the function of temperature. This work provides a detailed insight into the mechanism and corresponding physicochemical phenomena in the reactor during the hydrogen absorption process.

  • PDF

Characteristics of Absorption and Heat Transfer for Film Falling along a Vertical Inner Tube (3rd. Report, Refrigerating Capacity in Evaporator and Heating Capacity in Absorber) (수직관(수직관)내를 흘러내리는 액막식흡수기(液膜式吸收器)의 흡수(吸收) 및 열전달(熱傳達) 특성(特性) (제(第)3보(報), 증발기(蒸發器)의 냉동능력(冷凍能力)과 흡수기(吸收器)의 난방능력(暖房能力)))

  • Ohm, K.C.;Kashiwagi, Takao;Seo, J.Y.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.6 no.3
    • /
    • pp.175-181
    • /
    • 1994
  • This paper deals with the correlation of absorption rate in absorber and evaporation rate in evaporator. The evaporator consists of a copper tube of 10mm dia, and 600mm long and chilled water flowing through the tube is fed by the chilled water circulator. The flowrate of LiBr-water solution in the absorber plays a significant role in determining the magnitude of the heat transfer rate from chilled water to refrigerant There exists a flowrate of solution which has a maximum value of heat transfer. It is interesting to note that the absorption rate of absorber increases with increasing the heat transfer rate of the evaporator. Also, absorption rate increases with evaportation rate, and the ratio(the former/the other) depends on the inlet temperature of LiBr-water solution in the absorber. The heating capacity in the absorber is higher than the refrigerating capacity in the evaporator.

  • PDF

Numerical Study on the change of Absorption Characteristics by Change of Flow pattern in the Vertical Falling Film Absorber (수직 액막 흡수관의 유동변화에 따른 흡수성능 변화에 관한 해석적 연구)

  • Kim, Jung-Kuk;Cho, Keum-Nam
    • Proceedings of the KSME Conference
    • /
    • 2003.11a
    • /
    • pp.90-96
    • /
    • 2003
  • Numerical analyses have been performed to obtain the absorption heat and mass transfer coefficients and the absorption mass flux from a falling film of LiBr solution. In the present study, the behavior of laminar-wavy falling film in the vertical absorber was studied analytically and experimentally. The change of absorption performance on mean film thickness, wave amplitude, wave celerity was analysed. The heat and mass transfer equations are solved simultaneously to give the temperature and concentration variations at the LiBr solution/refrigeration vapor interface and at the wall. Effects of uniform film, wavy film and film Reynolds number on the heat and mass transfer coefficients have been estimated. The analytical results of the uniform and wavy falling film in the bare tube was higher than experimental result for $Rd_{t}<100$. The absorption performance showed the maximum at the wavy film by the insert device(spring).

  • PDF

Design of a High Temperature Production Heat Pump System Using Geothermal Water at Moderate Temperature (중온 지열수를 이용한 고온제조 열펌프 시스템 해석 및 설계)

  • Kim, Min-Sung;Baik, Young-Jin;Park, Seong-Ryong;Chang, Ki-Chang;Lee, Young-Soo;Ra, Ho-Sang
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2008.05a
    • /
    • pp.638-641
    • /
    • 2008
  • Geothermal water at moderate temperature in a range between 30 to $50^{\circ}C$ exists sparse in surroundings. Mostly they are utilized as heat or water source at spar zones in Korea. However, a large portion of used water is discarded due to its poor recovery quality and inferior application technologies. In this research, an innovative heat pump system based on the hybrid concept that combinate compression cycle and absorption cycle was investigated mathematically. The hybrid heat pump aims to recycle various kind of the heat sources at moderate temperature including geothermal water effectively. The prime objective of the simulation is to design a compression/absorption hybrid heat pump system which can make high temperature above the level of $90^{\circ}C$ and low temperature of $20^{\circ}C$ as well at the same using $50^{\circ}C$ geothermal heat water. As a result, primitive data was provided as a basis to design a prototype 3 RT class hybrid heat pump.

  • PDF

A Study on Absorber in Absorption Heat Pump with Methanol-Glycerine System as a Working Fluid (메탄올-글리세린계를 작동유체로 하는 흡수열펌프에서 흡수기 연구)

  • Min, Byong-Hun
    • Applied Chemistry for Engineering
    • /
    • v.17 no.1
    • /
    • pp.111-117
    • /
    • 2006
  • The improvement of energy conservation mandates decrease consumption of fossil fuels and minimize negative impacts on the environment, which originates from large cooling and heating demand. The absorption heat pump technology has a large potential for energy saving in this respect. Adsorption heat pump is a means to upgrade waste heat without addition of extra thermal energy. The increase of absorbed amount is of great importance for absorption heat pump cycle. In this study, in order to improve the performance of absorber, the absorbers of two different types have been investigated using methanol-glycerine as a working fluid. The former was tangential feed of liquid phase without spiral tube in the absorber and the latter was with spiral tube in the absorber. The latter was found to be more effective in enhancing the mass and heat transfer to increase the absorption performance.

Visualization of Marangoni Convection Behavior between Two Surfactant Dropwises in the Process of Steam Absorption (증기흡수시(蒸氣吸收時) 계면활성제액적간(界面活性劑液滴間)에 발생(發生)하는 마랑고니대류거동(對流擧動)의 가시화(可視化))

  • Rie, D.H.;Choi, K.K.;Kashiwagi, T.;Seo, J.Y.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.4 no.2
    • /
    • pp.65-71
    • /
    • 1992
  • In most absorption machines, absorption enhancement has been achieved by adding small amount of surfactant additive, which introduced the surface tension difference between absorbent and surfactant droplets in the vapor absorption. The aim of this study is to understand a basic mechanism of Marangoni convection and its effectiveness in the vapor absorption enhancement. In this study, nonflowing aqueous solution of LiBr 60 mass% was exposed to saturated water vapor under the condition that two dropwises surfactant were fixed on the absorbent surface. Our experiments achieved to visualize the enhanced heat and mass transfer phenomena by the effect of Marangoni convection through the laser holographic interferometry. Also, Marangoni convection behavior was obtained by using tracer method.

  • PDF