• 제목/요약/키워드: HVAC Noise

검색결과 72건 처리시간 0.025초

흡음재가 부착된 직방형 소음기의 전달 손실 예측 (Prediction of transmission loss of parallelepiped plenum chambers with liner)

  • 김회전;이정권;박철민
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2003년도 춘계학술대회논문집
    • /
    • pp.383-386
    • /
    • 2003
  • This paper deals with transmission loss of 3-dimensional rectangular plenum lined chamber. There are three kinds of rectangular plenum lined chamber: throughflow type, flow-reversal type, and end-in/side-out type. The combination of above three types of rectangular plenum lined chamber is used for the commercial HVAC system and automobile exhaust system. However, the ambiguity and complexity of sound absorbing material property and 3-dimensional property have impeded research. In this paper, the transmission loss of three kinds of rectangular plenum lined chamber is derived and calculated. The effect of increase of sound absorbing material is also considered. Analytical solution is calculated by using the locally-reacting property of sound absorbing material.

  • PDF

유전프로그래밍에 의한 초고압 송전선로 환경설계용 코로나 소음 예측계산식 개발 (Development of Audible Noise Prediction Formulas Applied to HVAC Transmission Lines Design by Using Genetic Programming)

  • 양광호;황기현;박준호;박종근
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제50권5호
    • /
    • pp.234-240
    • /
    • 2001
  • Audible noise (AN) produced by corona discharges from high voltage transmission lines is one of the more important considerations in line design. Therefore, line designers must pre-determine the AN using prediction formulas. This paper presents the results of applying evolutionary computation techniques using AN data from lines throughout the world to develop new, highly accurate formulas for predicting a A-weighted AN during heavy rain and stable rain from overhead ac lines. Calculated ANs using these new formulas and existing formulas are compared with measured data.

  • PDF

실험계획법을 이용한 차량공조시스템의 음질 특성 분석 (Analysis of Subjective Sound Quality Characteristics for the HVAC using the Design of Experiments : Sharp, Annoy)

  • 윤태건;심현진;이정윤;오재응;김성수
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2005년도 춘계학술대회논문집
    • /
    • pp.634-637
    • /
    • 2005
  • A subjective index of sound quality when it hit him is required since human listening is very sensitive and complex. Sound quality evaluation it leads consequently rightly in each situation and it composes a sound quality factor. But one of the levels in interest frequency range is substitute we cannot see the tendency of frequency substitute at whole that is executes a clear voice evaluation. Design of experiment is used and dividing 12 equally in frequency domain, the sound quality using sharpness and annoyance is performed by modifying each of frequency domains. Design of experiment method reduces much number experiment very effectively and each main effect of domain solution analysis, such as a case of sharpness and annoyance, the change of domain (increase and decrease of sound pressure level, or change nil) can grasp a type of effect should have influenced to a sound quality, and it will be able to select the objective frequency domain which hits to the sound quality. Through these obtained results the physical changes of level at arbitrary frequency domain sensitivity can be adapted.

  • PDF

UPS 기능을 갖는 A/C Blower용 인버터 시스템 개발 (Development of the Inverter System with UPS Function for the Air-Conditioning Blower)

  • 임승범;이윤하;목형수;지준근
    • 전력전자학회논문지
    • /
    • 제16권3호
    • /
    • pp.302-308
    • /
    • 2011
  • 현재 철도 차량용 공조 시스템은 3상 AC 380V를 입력으로 받아 온/오프 제어만 하고 있어 효율 저감 및 소음 등의 문제점을 가지고 있으며 AC 전원 공급이 차단될 경우 blower 동작이 멈추는 문제점을 가지고 있다. 본 논문에서는 UPS 기능을 갖는 A/C blower용 인버터 시스템을 제안한다. 제안한 인버터 시스템은 입력으로 AC 전원과 DC 전원을 받아서 blower 구동용 유도전동기의 V/F 제어를 하며, CAN통신을 이용하여 속도, 모드 및 Soft-Start 시간 등을 제어한다. 또한 CAN 통신 고장시에는 정비용으로 RS-232통신을 이용해서도 제어할 수 있고 조작자가 직접 하드웨어적으로 제어할 수도 있어 기존의 문제점을 보완할 수 있다. 시뮬레이션과 실험을 통해 제안한 인버터 시스템의 유용성을 입증한다.

도시철도의 전동차와 PSD 인터페이스 고찰 (Study for Interface Between EMU and PSD in Metro)

  • 선종민;조은제;양동석;박희철
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2011년도 정기총회 및 추계학술대회 논문집
    • /
    • pp.1397-1404
    • /
    • 2011
  • Metro serves more than a basic function of transporting passengers between short distances but became a crucial part of civic culture due to the fact that citizens demand various facilities for better life style. Therefore, domestic metro cuts off train noise and air dust, provides pleasant platform surroundings by offering effective HVAC, and establishes PSD (Platform Screen Door) system to prevent falls into train tracks. To control and interlock EMU Door and PSD to avoid passenger complaint and revenue service obstructions, stability and reliability of on-board & wayside equipment are required foremost and each line needs to build optimum interface between on-board & wayside equipment. To control PSD, we would like to introduce examples of Busan Metro(BTC : Busan Transportation Corporation) which already utilizes interface between on-board & wayside equipment in various ways and consider optimum interface between on-board & wayside equipment in future PSD system.

  • PDF

UPS 기능을 갖는 A/C Blower용 Inverter 시스템 개발 (Development of the Inverter System with UPS Function for the Air-Conditioning Blower)

  • 임승범;이윤하;지준근;목형수;홍순찬
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2010년도 추계학술대회
    • /
    • pp.345-346
    • /
    • 2010
  • The HVAC(Heating Ventilation and Air Conditioning) system is only controlled by turn on/turn off operations against to AC 380V input. Therefore, the efficiency of the system is reduced and noise occurs. Also, the blower is shut down at the AC power failure. In this paper, the inverter system with UPS function for the A/C(Air Conditioning) blower is proposed. Proposed inverter system which is powered from the AC and DC voltage can control speed, operation mode, and soft-start time using CAN communication. In case of the CAN communication failure, RS-232 communication could be used to control the hardware directly by the engineer that can solve existing problems. To verify the validity of proposed inverter system, simulations and experiments are carried out.

  • PDF

PWAM 방식을 이용한 공조시스템용 인버터의 THD 저감 방법 (PWAM Based THD Reduction of Inverter for Air-Conditioning Blower)

  • 임승범;이윤하;전찬용
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2011년도 전력전자학술대회
    • /
    • pp.97-98
    • /
    • 2011
  • The HVAC(Heating Ventilation and Air conditioning) system is controlled by two ways, one is ON/OFF control and the other is PWM inverter with V/F. Control of blower with the use of PWM inverter has quite some benefits such as the capability of changing speed, high efficiency and reduced noise level compared with ON/OFF control. But if blower is operated at low speed, high THD generated by decrease of ma, and output voltage lowered in proportion to frequency. To solve these problems, filter should be installed at the output stage of inverter, which can decrease THD but has problems such as increase of volume size and additional braking resistance. This paper proposes the PWAM method which can reduce THD instead of installing the filter at the output stage of inverter. The proposed PWAM method is an inverter modulation method that fixes the modulation index of inverter to reduce THD by varying DC link voltage of inverter unlike conventional PWM method. Finally, the validity of proposed PWAM methods verified by experiments.

  • PDF

실험적 모드해석을 이용한 방사광 가속기 건물의 진동평가 (Vibration Estimation of Synchrotron Light Source Building Using Experimental Modal Analysis)

  • 박상규;이홍기;권형오
    • 소음진동
    • /
    • 제5권3호
    • /
    • pp.413-421
    • /
    • 1995
  • 냉난방용 회전기기에 의한 방사광가속기 건물의 진동은 내부에 설치되어 있는 광학장치나 전자장비의 성능에 영향을 미치기 때문에 건설단계에서 부터 건물 진동에 대한 평가가 매우 중요하다. 본 연구에서는 방사광가속기 건물의 진동을 평가 하기 위해서 실험적 모우드해석법을 이용하여 냉난방기기가 위치한 바닥의 동적특성 을 구하고, 하중응답 모사법을 통해 진동응답치를 계산하였다. 평가결과, 건물바닥의 진동치는 기준치를 상회하고 있으며 이를 해결하기 위해 이중방진 시스템을 설계 제작하여 냉난방기기와 바닥 사이에 설치함으로써 바닥의 진동을 허용한도 이내로 감소시켰다.

  • PDF

Rayleigh-Ritz 방법에 의한 흡음재가 부착된 직방형 소음기의 전달 손실 예측 (Prediction of the Transmission Loss of Rectangular Lined Plenum Chamber by the Rayleigh-Ritz Method)

  • 김회전;이정권
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2005년도 춘계학술대회논문집
    • /
    • pp.869-872
    • /
    • 2005
  • The purpose of this study is on the prediction of the acoustic performance of the lined rectangular plenum chamber which can be used in the HVAC systems. The lined plenum chamber is modeled as a piston driven rectangular tube without mean flow and the acoustic pressure in the lined chamber is obtained by superposing the three dimensional pressure due to each of uniformly and harmonically fluctuating pistons. The arbitrary locations of inlet/outlet ports as well as the acoustic higher order modes generated at the area discontinuities of the port chamber interfaces are taken into consideration. The four-pole parameters can be derived by imposing the proper boundary conditions on each inlet and outlet ports. The lining material on the internal wall is assumed to be a bulk-reacting model. A single weak variation statement which satisfies the fluctuating rigid piston condition and the pressure and displacement continuity condition at the interface between the lining material and the airway was developed. The set of cosine functions were used as the admissible function when applying the Rayleigh-Ritz method. Computed results are compared with those predicted by using the locally-reacting lining material and experimental results, respectively. There are a good agreement shown between the results by the Rayleigh-Ritz method and the experiment results. The derived transfer matrices can be easily combined with other four-pole parameters of different types of mufflers for the calculation of the whole system performance.

  • PDF

보건의료시설의 실내 예상 평균 온열감(PMV), 이산화탄소 농도, 소음도, 조도의 통합실내쾌적도(IEQh)를 통한 연간 실내 쾌적도 평가 (Evaluation of Annual Indoor Environment Quality in Hospitals using Various Comfort-related Factors)

  • 이보람;이대엽;반현경;이세원;김규상;이기영
    • 한국환경보건학회지
    • /
    • 제43권3호
    • /
    • pp.214-222
    • /
    • 2017
  • Objectives: A hospital is a complex building that serves many different purposes. The indoor environment in a hospital plays a major role in patient well-being and the work efficiency of the hospital staff. This study was conducted to evaluate overall comfort in two major hospitals over the course of one year. Methods: Various indoor environmental conditions were measured in two general hospitals for one year (April 2014 to April 2015). Monitoring alternated between the hospitals at one month per respective monitoring session. The indoor air temperature, relative humidity (RH), mean radiant temperature and air velocity were measured in order to calculate the predicted mean vote (PMV). Carbon dioxide concentration, noise level and illumination level were concurrently measured and applied to the overall IEQ acceptance model for the hospitals (IEQh). Results: The IEQh at the two general hospitals was different at five spaces within a building. The IEQh for summer and winter were significantly different. Real-time IEQh demonstrated that indoor comfort was affected by the hospital's operating hours due to operation of the HVAC system. The percentage of indoor comfort in the hospitals was higher using PMV than IEQh. Conclusion: IEQh in the hospitals was different at locations with different purposes. Indoor comfort assessment using IEQh was stricter than with PMV. Additional research is needed in order to optimize the IEQh model.