PWAM Based THD Reduction of Inverter for Air-Conditioning Blower

PWAM 방식을 이용한 공조시스템용 인버터의 THD 저감 방법

  • Published : 2011.07.05

Abstract

The HVAC(Heating Ventilation and Air conditioning) system is controlled by two ways, one is ON/OFF control and the other is PWM inverter with V/F. Control of blower with the use of PWM inverter has quite some benefits such as the capability of changing speed, high efficiency and reduced noise level compared with ON/OFF control. But if blower is operated at low speed, high THD generated by decrease of ma, and output voltage lowered in proportion to frequency. To solve these problems, filter should be installed at the output stage of inverter, which can decrease THD but has problems such as increase of volume size and additional braking resistance. This paper proposes the PWAM method which can reduce THD instead of installing the filter at the output stage of inverter. The proposed PWAM method is an inverter modulation method that fixes the modulation index of inverter to reduce THD by varying DC link voltage of inverter unlike conventional PWM method. Finally, the validity of proposed PWAM methods verified by experiments.

Keywords