• Title/Summary/Keyword: HV motor

Search Result 16, Processing Time 0.016 seconds

Assessment of Insulation Deterioration in Stator Windings of High Voltage Motor (고압전동기 고정자 권선의 절연열화 평가)

  • Kim, Hee-Dong;Kong, Tae-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.5
    • /
    • pp.711-716
    • /
    • 2012
  • To assess the insulation deterioration of stator windings, diagnostic and AC breakdown tests were performed on the eleven high voltage (HV) motors rated at 6kV. After completing the diagnostic tests, the AC overvoltage test was performed by gradually increasing the voltage applied to the stator windings until electrical insulation failure occurred, to obtain the breakdown voltage. Stator winding of motors 1, 3, and 8 failed at above rated voltage at 14 kV, 13.8kV, and 16.4kV, respectively. The breakdown voltage of three motors was higher than expected for good quality windings in 6kV motors. Based on deterioration evaluation criteria, the stator winding insulation of eleven HV motors are confirmed to be in good condition. The turning point of the current, $P_{i2}$, in the AC current vs. voltage characteristics occurred between 5kV and 6kV, and the breakdown voltage was low between 13.8kV and 16.4kV. There was a strong correlation between the breakdown voltage and various electrical characteristics in diagnostic tests including Pi2.

Development of Deterioration Detecting System for Aged ACSR-OC Conductors in HV Overhead Distribution Lines (고압 가공배전선의 노화된 ACSR-OC 도체에 대한 열화검출시스템 설계)

  • Kim, Sung-Duck;Lee, Seung-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2000.11a
    • /
    • pp.232-235
    • /
    • 2000
  • Design and experiments of a nondestructive system to inspect deterioration of ACSR-OC (ACSR Outdoor Cross-linked Polyethylene Insulated Wire usually used in HV overhead distribution lines presented in this paper. ACSR-OC conductor built to pollutants air for a long period would be easily progress to corrode so that it may lead to the reduction of the effective cross section area of conductors. A fault diagnosis system consisting of a solenoid sensor, a constant current source with RF frequency signal processing unit and a motor driver/controller designed and implemented. This instrument can dot the sensor output variation due to deterioration corrosion, continuously. As a result, it was shown such corrosion detector can readily be utilized estimating the diameter change due to deterioration overhead distribution lines and in giving an warning or inform before severe aged conductor lead to fail.

  • PDF

Field analysis of end_turn coil of HV induction motor (고압 회전기에서 코일 단부의 전계 해석)

  • Park, Seung-Bae;Kim, Do-Wan;Jung, Hyun-Kyo
    • Proceedings of the KIEE Conference
    • /
    • 1998.11a
    • /
    • pp.70-72
    • /
    • 1998
  • Because of using PWM inverters and converters. The problems of insulation breakdown is emerging in both high voltage motors and general motors. In conventional methods, the viewpoint of surge problems is wave propagation with or without cable and inverter. For the purpose of knowing the situation of insulation breakdown, the end-turn coil of windings in the motor winding insulation structure is modelled by FEM, and field analysis of that is done. For first step, only end-turn coil is modelled and the model is simulated with FEM by approximating the resistivity of metallic foil surrounding insulation layers with having nonlinear property. Next, the result of simulation with nonlinear resistivity are compared with the result of linear resistivity. Because of microscope analysis, there is the problem of generalization but the situation of corona discharge in end-turn coil will be explained from this simulation.

  • PDF

Aging Diagnosis of Model Coil of HV Induction Motor Using HFPD and Neural Networks (HFPD 및 신경회로망을 이용한 고압 유도전동기 모델코일 열화진단)

  • Kim, Deok-Geun;Im, Jang-Seop;Yeo, In-Seon
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.51 no.8
    • /
    • pp.361-367
    • /
    • 2002
  • Many failures in high voltage equipment are preceded by partial discharge activity. In this paper deals with the application of the high frequency partial discharge measurement technique in motorette. HFPD measurement is very effective method to detect the PD occurred in motorette which is the called name of test specimen for accelerating test of stator winding[1] In this study, CT type HFPD sensor is used to detect the partial discharges and a measured HFPD pattern is analyzed by fractal mathematics. The neural network algorithm is used to pattern recognition and ageing diagnosis. As a result of this study, the fractal dimensions are increased along to applied voltage and HFPD pattern recognition using neural network shown excellent recognition rate. Also, the ageing diagnosis of motorette has been Possible.

Development of Deterioration Diagnosis System for Aged ACSR-OC Conductors in HV Overhead Distribution Lines (고압 가공배전선의 노화된 ACSR-OC 도체에 대한 열화진단시스템 개발)

  • 김성덕;이승호
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.14 no.6
    • /
    • pp.43-50
    • /
    • 2000
  • Design and experiments of a nondestructive testing system with a solenoid eddy current sensor to inspect deterioration of ASCR-OC (ACSR Outdoor Cross-linked Polyethylene Insulated Wires) usually used in HV overhead distribution lines in domestic areas in presented in this paper. Through corrosion mechanisms and deterioration results for ACSR-OC conductors are examined, it is shown that corrosion may lead to the reduction of the effective cross section area of conductors is proposed. The measurement system consisting of a constant current source with a RF frequency, a signal processing unit and a motor driver/ controller is designed and implemented. This instrument has such capabilities as detecting the sensor output and estimating diameter change of the testing conductors, continuously. As a result, it was verified that such corrosion detector system with an eddy current sensor can be shown good effectiveness for estimating the serious faults due to deterioration in overhead distribution lines and giving an early warming before severe aged conductor may lead to fail.

  • PDF

Heat Treatment Characteristics of a Press Draw Mold by Using High Power Diode Laser (고출력 다이오드 레이저를 이용한 프레스 드로우금형의 열처리 특성)

  • Hwang, Hyun-Tae;So, Sang-Woo;Kim, Jung-Do;Kim, Young-Kuk;Kim, Byeong-Hun
    • Journal of the Korean Society for Heat Treatment
    • /
    • v.22 no.6
    • /
    • pp.339-344
    • /
    • 2009
  • Recently, Laser surface treatment technologies have been used to improve wear charactenitics and fatigue resistance of metal molding. When the laser beam is irradiated on the surface and laser speed is appropriate, the laser focal position is rapidly heated and the thermal energy of surface penetrates the material after irradiation, finally imbuing it with a new mechanical characteristic by the process of self-quenching. This research estimates the material characteristic after efficient and functional surface treatment using HPDL, which is more efficient than the existing CW Nd:YAG laser heat source. To estimate this, microstructural changes and hardness characteristics of three parts (the surface treatment part, heat affect zone, and parental material) are observed with the change of laser beam speed and surface temperature. Moreover, the depth of the hardened area is observed with the change of the laser beam speed and temperature. From the results of the experiments, it has been shown that the maximum hardness is approximately 788Hv when the heat treatment temperature and the travel speed are $1150^{\circ}$ and 2 mm/sec, respectively.