Development of Deterioration Detecting System for Aged ACSR-OC Conductors in HV Overhead Distribution Lines

고압 가공배전선의 노화된 ACSR-OC 도체에 대한 열화검출시스템 설계

  • Kim, Sung-Duck (Department of Electronic Engineering, Taejon National University of Technology) ;
  • Lee, Seung-Ho (Department of Electronic Engineering, Taejon National University of Technology)
  • 김성덕 (대전산업대학교, 전자공학과) ;
  • 이승호 (대전산업대학교, 전자공학과)
  • Published : 2000.11.25

Abstract

Design and experiments of a nondestructive system to inspect deterioration of ACSR-OC (ACSR Outdoor Cross-linked Polyethylene Insulated Wire usually used in HV overhead distribution lines presented in this paper. ACSR-OC conductor built to pollutants air for a long period would be easily progress to corrode so that it may lead to the reduction of the effective cross section area of conductors. A fault diagnosis system consisting of a solenoid sensor, a constant current source with RF frequency signal processing unit and a motor driver/controller designed and implemented. This instrument can dot the sensor output variation due to deterioration corrosion, continuously. As a result, it was shown such corrosion detector can readily be utilized estimating the diameter change due to deterioration overhead distribution lines and in giving an warning or inform before severe aged conductor lead to fail.