• 제목/요약/키워드: HV motor

검색결과 16건 처리시간 0.023초

세척과 절연보강에 따른 고압전동기 고정자 권선의 절연상태 분석 (Analysis of Insulation Condition in High Voltage Motor Stator Windings Following Cleaning and Insulation Reinforcement)

  • 김희동
    • 한국전기전자재료학회논문지
    • /
    • 제25권6호
    • /
    • pp.474-480
    • /
    • 2012
  • Diagnostic tests were performed on two high voltage(HV) motor stator windings. These tests included the measurement of insulation resistance, polarization index, AC current, dissipation factor($tan{\delta}$) and partial discharge(PD) magnitude. Surface contamination of HV motor stator windings has an effect on the AC current and $tan{\delta}$. When the stator windings were finished cleaning and insulation reinforcement, the increase rate of AC current(${\Delta}I$) and dissipation factor(${\Delta}tan{\delta}$) were very small compared to those before cleaning. However, the PD magnitude remained the same. These tests show that cleaning and insulation reinforcement of HV motor stator windings can reduce the insulation failure.

6.6 kV 전동기 고정자 권선의 절연진단과 절연내력 평가 (Estimation of Insulation Diagnosis and Dielectric Strength in 6.6 kV Motor Stator Windings)

  • 김희동;공태식
    • 전기학회논문지
    • /
    • 제63권6호
    • /
    • pp.780-785
    • /
    • 2014
  • To assess the deterioration condition of stator insulation, diagnostic and AC dielectric strength tests were performed on five high voltage (HV) motors (2,000 HP, 6.6 kV) for boiler feed-water pump (BFP). Two HV motors for BFP were installed per unit. Following the long term rewinding program, the diagnostic test was performed on five 6.6 kV motors during the planning maintenance period. After completing diagnostic test, AC dielectric strength test was done on the stator windings of HV motors. The AC dielectric strength test was conducted at 15 kV for one minute. Dielectric strength test and diagnostics test results confirmed that the stator insulation was judged to be in serviceable condition in the five 6.6 kV motors.

Analysis of Off-Line and On-Line Partial Discharge in High Voltage Motor Stator Windings

  • Kim, Hee-Dong;Kong, Tae-Sik;Lee, Sang-Kil;Kim, Beom-Soo;Kim, Doo-Young
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권3호
    • /
    • pp.1086-1092
    • /
    • 2015
  • The off-line and on-line partial discharge (PD) in the stator winding of three high-voltage (HV) motors (1,400 HP, 6.6 kV) is measured and analyzed in this paper. The off-line PD is measured at high values between 24,300 ~ 36,100 pC after 18 years of motor operation. Spare replacement motors were not available for testing the degree of deterioration of the stator windings in standstill status. Therefore, on-line periodic analysis was conducted to monitor the trend of PD after installing a ceramic sensor (110 pF, 6.6 kV) in the terminal box for each phase of each motor. In the stator winding of the No.1 and No.2 HV motors, which showed high magnitudes of off-line PD and low magnitudes of on-line PD, defects are expected to appear in the neutral end of the winding. On the contrary, in the stator windings of the No.3 HV motor, which exhibits high off-line and on-line PD magnitude, defects are expected to appear in the terminal end of the winding where a voltage close to the phase voltage is applied.

A Novel Seamless Direct Torque Control for Electric Drive Vehicles

  • Ghaderi, Ahmad;Umeno, Takaji;Amano, Yasushi;Masaru, Sugai
    • Journal of Power Electronics
    • /
    • 제11권4호
    • /
    • pp.449-455
    • /
    • 2011
  • Electric drive vehicles (EDV) have received much attention recently because of their environmental and energy benefits. In an EDV, the motor drive system directly influences the performance of the propulsion system. However, the available DC voltage is limited, which limits the maximum speed of the motors. At high speeds, the inverter voltage increases if the square wave (SW) voltage (six-step operation) is used. Although conventional direct torque control (DTC) has several advantages, it cannot work in the six-step mode required in high-speed applications. In this paper, a single-mode seamless DTC for AC motors is proposed. In this scheme, the trajectory of the reference flux changes continuously between circular and hexagonal paths. Therefore, the armature voltage changes smoothly from a high-frequency switching pattern to a square wave pattern without torque discontinuity. In addition, because multi-mode controllers are not used, implementation is more straightforward. Simulation results show the voltage pattern changes smoothly when the motor speed changes, and consequently, torque control without torque discontinuity is possible in the field weakening area even with a six-step voltage pattern.

고압 유도전동기 고정자권선의 결함에 따른 부분방전발생양상의 특징분석 (Characteristic Analysis of PD Occurrence Aspects for Defect of Stator Coil in HV Induction motor)

  • 이강원;김명룡;백광선;장동욱;임기조
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2226-2228
    • /
    • 2005
  • High voltage induction motor is the important equipment for ensuring the driving performance of the electric train. PD(partial discharge) is a good indicator for showing the insulation performance of stator coil in HV induction motor. This paper has investigated the characteristics of PD occurrence aspects for both the sound and defective stator coil which consist of maximum PD amplitude(V), total occurrence number, average PD amplitude(V) and PD amplitude(v) - PD occurrence number(n). They were compared with each other depending on applied voltages and reconstructed to $60{\times}60$ matrices of PD amplitude(v)-occurrence phase (${\phi}$)-occurrence number(n) which is the good way to estimate the PD sources in stator coil.

  • PDF

순환수 펌프용 고압전동기 고정자 권선의 절연내력 평가 (Estimation of Dielectric Strength in High Voltage Motor Stator Windings for Circulating Water Pump)

  • 김희동;공태식;박태성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.1191-1192
    • /
    • 2015
  • To assess the deterioration condition of stator insulation, diagnostic and overpotential tests were performed on two high voltage(HV) motors for circulating water pump (CWP). Following the long term rewinding program, the diagnostic test was performed on two motors during the planning maintenance period. After completing the diagnostic test, overpotential test was done on the stator windings of HV motors. During the overpotential test, the No. 1 and No. 2 of HV motors failed at 8.8 kV and 7.9 kV, respectively. Stator windings of two HV motors had deteriorated significantly.

  • PDF

고압전동기 고정자 권선의 온도변화에 따른 절연특성 분석 (Analysis of the Temperature Influence on Insulation Characteristics in High Voltage Motor Stator Windings)

  • 공태식;주영호;김희동;박태성
    • 한국전기전자재료학회논문지
    • /
    • 제25권10호
    • /
    • pp.786-790
    • /
    • 2012
  • A variety of diagnostic tests are widely applied in the field in industry to evaluate the condition of high voltage (HV) motor stator insulation. In this paper, the influence of temperature on the stator insulation diagnostic tests such as the insulation resistance, AC current, dissipation factor, and partial discharge measurements are studied and reported. The tests are performed with the HV motor stator winding temperature set between $40^{\circ}C$ to $80^{\circ}C$ in $10^{\circ}C$ intervals. It is shown that the AC current, dissipation factor, and partial discharge magnitude steadily increase with temperature, which suggests that temperature must be taken into account in the interpretation of the test results.

The New Smart Power Modules for up to 1kW Motor Drive Application

  • Kwon, Tae-Sung;Yong, Sung-Il
    • Journal of Power Electronics
    • /
    • 제9권3호
    • /
    • pp.464-471
    • /
    • 2009
  • This paper introduces a new Motion-$SPM^{TM}$ (Smart Power Modules) module in Single In-line Package (SIP), which is a fully optimized intelligent integrated IGBT inverter module for up to 1kW low power motor drive applications. This module offers a sophisticated, integrated solution and tremendous design flexibility. It also takes advantage of pliability for the arrangement of heat-sink due to two types of lead forms. It comes to be realized by employing non-punch-through (NPT) IGBT with a fast recovery diode and highly integrated building block, which features built-in HVICs and a gate driver that offers more simplicity and compactness leading to reduced costs and high reliability of the entire system. This module also provides technical advantages such as the optimized cost effective thermal performances through IMS (Insulated Metal Substrate), the high latch immunity. This paper provides an overall description of the Motion-$SPM^{TM}$ in SIP as well as actual application issues such as electrical characteristics, thermal performance, circuit configurations and power ratings.

전기화학 임피던스 분석을 통한 자동차용 코일스프링 강의 부식 평가 (Study on Corrosion of Automotive Coil Spring Steel by Electrochemical Impedance Spectroscopy)

  • 이규혁;박중현;안승호;서지원;장희진
    • Corrosion Science and Technology
    • /
    • 제16권6호
    • /
    • pp.298-304
    • /
    • 2017
  • Coil spring steels from the automobile suspension part after field exposure for 10 years and those after anti-corrosion validation test in proving ground of 5,000 ~ 10,000 km were examined for corrosion damages. Partial loss of paint, accumulation of corrosion product, and cracking of paint and superficial material were observed. The surface and subsurface region of spring steels had compressive residual stress and high hardness by shot peening. The surface hardness values of the specimens were 620 ~ 670 Hv. They were 60 ~ 80 Hv higher than those of the samples taken from the middle part of the spring. The maximum compressive stress was -916 ~ -1208 MPa measured at depth of about $100{\mu}m$. Electrochemical impedance spectroscopy showed that the resistances of charge transfer and the paint layer of the spring steels ranged from several tens to millions ${\Omega}{\cdot}cm^2$. The resistance of the field samples was much higher than that of the proving ground samples used in this study, implying that the proving ground test condition would be more corrosive than the field environment.