Analysis of the Temperature Influence on Insulation Characteristics in High Voltage Motor Stator Windings  

Kong, Tae-Sik (Korea Electric Power Corporation (KEPCO) Research Institute)
Ju, Young-Ho (Korea Electric Power Corporation (KEPCO) Research Institute)
Kim, Hee-Dong (Korea Electric Power Corporation (KEPCO) Research Institute)
Park, Tae-Sung (Korea Electric Power Corporation (KEPCO) Research Institute)
Publication Information
Journal of the Korean Institute of Electrical and Electronic Material Engineers / v.25, no.10, 2012 , pp. 786-790 More about this Journal
Abstract
A variety of diagnostic tests are widely applied in the field in industry to evaluate the condition of high voltage (HV) motor stator insulation. In this paper, the influence of temperature on the stator insulation diagnostic tests such as the insulation resistance, AC current, dissipation factor, and partial discharge measurements are studied and reported. The tests are performed with the HV motor stator winding temperature set between $40^{\circ}C$ to $80^{\circ}C$ in $10^{\circ}C$ intervals. It is shown that the AC current, dissipation factor, and partial discharge magnitude steadily increase with temperature, which suggests that temperature must be taken into account in the interpretation of the test results.
Keywords
Diagnostic test; Motor; Insulation; Temperature; Dissipation factor; Partial discharge;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Motor Reliability Working Group, IEEE IAS Trans., A21, 863 (1985).
2 H. D. Kim, J. KIEEME, 15, 119 (2002).
3 IEEE Std. 95-1977, 13 (1977).
4 ANSI/IEEE Std 56-1997, 12 (1997).
5 H. D. Kim, T. S. Kong, Y. H. Ju, and B. H. Kim, J. Electri. Eng. & Tech., 6, 384 (2011).   DOI
6 IEEE Std 43-2000, 10 (2000).
7 EPRI Research Project 2814-35 Final Report, 4 (1992).