• Title/Summary/Keyword: Governor system

Search Result 230, Processing Time 0.026 seconds

Fault Detection of Governor Systems Using Discrete Wavelet Transform Analysis

  • Kim, Sung-Shin;Bae, Hyeon;Lee, Jae-Hyun
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.36 no.5
    • /
    • pp.662-673
    • /
    • 2012
  • This study introduces a condition diagnosis technique for a turbine governor system. The governor system is an important control system to handle turbine speed in a nuclear power plant. The turbine governor system includes turbine valves and stop valves which have their own functions in the system. Because a turbine governor system is operated by high oil pressure, it is very difficult to maintain under stable operating conditions. Turbine valves supply oil pressure to the governor system for proper operation. Using the pressure variation of turbine and governor valves, operating conditions of the turbine governor control system are detected and identified. To achieve automatic detection of valve status, time-based and frequency-based analysis is employed. In this study, a new approach, wavelet decomposition, was used to extract specific features from the pressure signals of the governor and stop valves. The extracted features, which represent the operating conditions of the turbine governor system, include important information to control and diagnose the valves. After extracting the specific features, decision rules were used to classify the valve conditions. The rules were generated by a decision tree algorithm (a typical simple method for data-based rule generation). The results given by the wavelet-based analysis were compared to detection results using time- and frequency-based approaches. Compared with the several related studies, the wavelet transform-based analysis, the proposed in this study has the advantage of easier application without auxiliary features.

A study on the Turbine-Generator Governor Dynamic Characteristic Testing System (터빈-발전기 조속기의 동특성 시험시스템 개발에 관한 연구)

  • Choi, Hyung-Joo;Lee, Heung-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.10
    • /
    • pp.1399-1411
    • /
    • 2012
  • The grid frequency is controlled cooperatively by the governor of the Turbine-Generator and the automatic generation controller(AGC) of the KPX(Korea Power Exchange). It is a basic requirement that the reliability of the governor is verified to enhance the power system stability but it is not easy to confirm the response characteristics of the governor because all generators are operated in the grid system that has the constant voltage and frequency. Therefore, it is necessary to study a new test method in order to examine the governor dynamic characteristic in the similar fault conditions. A study has shown that it is verified to simulate the turbine-generator power control system, the governor response characteristic under limited conditions and contribution of AGC with the gas turbine generator simulation model as well as demonstrate the dynamic response of the governor with the developed governor dynamic characteristic tester based on digital controller while the turbine-generator is connected to the grid system. This tester is constructed by the built-in functions of the turbine-generator main controller. In this treatise, the theoretical background, development method and the results of both simulations and demonstrations are described as another way to verify the turbine-generator governor dynamic characteristics.

The Speed Control of a Marine Diesel Engine with Electro Hydraulic Governor by using W Transformation Method (w 변환법에 의한 전기 - 유압식 조속기를 가진 박용디젤기관의 속도제어)

  • 강창남;박진길
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.21 no.2
    • /
    • pp.195-205
    • /
    • 1997
  • The propulsion marine diesel engine have been widely applied with a mechanical- hydraulic governor to control the ship speed for long time. But it was recently very difficult for the mechani¬cal - hydraulic governor to control the speed of engine under the condition of low speed and low load because of jiggling by rough fluctuation of rotating torque and hunting by dead time of Desiel engnie The performance improvement of mechanical - hydraulic governor is required to solve these problems of control system. The electro - hydraulic governor using PID algorithm is provided to compensate the faults of mechanical- hydraulic governor. In this paper, in order to analyze the ship speed control system, the transfer function was converted from the z tansformation to w transformation. The influence of dead time changing by engine speed which induces hunting phenomena was investigated by Nichols chart of w plane. As a method of performance improvement of mechanical hydraulic governor, a Eletro - hydraulic governor shows that fine control results can be obtained through optimal parameter tuning of PID

  • PDF

A Study on Reliability Improvement of a Fault Tolerant Digital Governor (내고장성 디지털 조속기의 신뢰성 향상에 관한 연구)

  • Sin, Myeong-Cheol;Jeon, Il-Yeong;Jo, Seong-Hun;Lee, Seong-Geun;Kim, Yun-Sik
    • The Transactions of the Korean Institute of Electrical Engineers D
    • /
    • v.51 no.5
    • /
    • pp.175-181
    • /
    • 2002
  • In this paper, fault tolerant digital governor is designed to realize ceaseless controlling and to improve the reliability of control system. Designed digital governor huts duplex I/O module and triplex CPU module and also 2 out of 3 voting algorithm and self diagnostic ability. The Processor module of the system(SIDG-3000) is developed based on 32 Bit industrial microprocessor, which guaranteed high quality of the module and SRAM for data also SRAM for command are separated. The process module also includes inter process communication function and power back up function (SRAM for back-up). System reliability is estimated by using the model of Markov process. It is shown that the reliability of triplex system in mission time can be dramatically improved compared with a single control system Designed digital governor system is applied after modelling of the steam turbine generator system of Buk-Cheju Thermal Power Plant. Simulation is carried out to prove the effectiveness of the designed digital governor system

A Study on Suppressed Hunting of Diesel Engine Truck Using Electronic Governor (전자식 가버너를 이용한 디젤 자동차의 헌팅억제 제어에 관한 연구)

  • Hong, S.I.;Kim, N.S.
    • Journal of Power System Engineering
    • /
    • v.2 no.3
    • /
    • pp.68-73
    • /
    • 1998
  • The propulsion diesel engine have been widely applied with a mechanical governor to control the truck speed for a long time. But it was recently very difficult for mechanical governor to control the speed of long stock and diesel engine of truck because of hunting by dead time between fuel injection and power output. This study is aimed to configure the modeling for performance simulation regarding to diesel truck operation which could be suppressed for hunting. The modeling have been made on the base of dynamic characteristic such as electronic governor, injection of fuel system and operating states of diesel engine truck. Real model system have been introduced for deciding reacting parameters and for the comparison of resulting performance in simulation. In results of simulation, we obtained items which diesel truck drives for suppressed hunting.

  • PDF

Application of FESS Controller for Load Frequency Control

  • Lee, Jeong-Phil;Kim, Han-Guen
    • Journal of international Conference on Electrical Machines and Systems
    • /
    • v.2 no.3
    • /
    • pp.361-366
    • /
    • 2013
  • This paper presents the effect on application of the flywheel energy storage system (FESS) for load frequency control (LFC) of an interconnected 2 area power system. To do this, the control characteristics with the FESS were compared with that of the conventional governor controller. The controller for the FESS control and the governor control used a PID type controller. Both the FESS PID controller and the governor PID controller using genetic algorithm (GA) were designed to optimize the PID parameters. The frequency and generation output characteristics with the only FESS controller and with the only conventional governor controller were compared. To verify robust performance of the FESS controller, the computer simulations were performed under various disturbances. The simulation results showed that the FESS controller provided better dynamic responses in comparison with the conventional governor controller.

Improvement of Load Following Operation by Governor Control Logic Modification of the Thermal Power Plant (1) (기력발전소 조속기의 제어개선에 의한 발전기 부하추종성의 향상 (1))

  • Lee, Jong-Ha;Kim, Tae-Woong
    • Proceedings of the KIPE Conference
    • /
    • 2005.07a
    • /
    • pp.501-503
    • /
    • 2005
  • The improvement of load following operation of the thermal power plant is influenced to the electrical quality. Analysis of boiler, turbine, and governor system, and the study of control algorithm are preceded. The thermal power plant is operated by various control systems. In the case of faulty governor system, it takes long days to solve the problem and impossible to repair the mechanism without outage. A non-planned out-age is taken into consideration because of economical power production. In this paper, to clear the continuous swings of an old turbine governor system(YEOSU #1), the trend, the control logic, and the hydraulic mechanism are analyzed, and then the control circuit with ADAPT function and the 1st order lag circuit are inserted and modified. After that, the power plant comes to automatic governor control operation.

  • PDF

Automation of Governor Performance Test System (조속기 시험 시스템의 자동화)

  • Lee, I.Y.;Kim, J.W.;Kang, M.G.
    • Journal of Power System Engineering
    • /
    • v.9 no.4
    • /
    • pp.155-161
    • /
    • 2005
  • Governors control the revolution speed of heat engines such as diesel engines, steam turbines and gas turbines. Precise and prompt tests for the control performances of governors are essential both in governors' manufacturing processes and in governors' maintenance processes. In the conventional governor test systems controlled by analog type electronic controllers, the incorporation of heat engine's dynamics to the test system have been considered very difficult to realize. This study suggests a new governor test system controlled by a digital controller using a personal computer. The application of the digital controller to the test system instead of the analog type electronic controller have brought about the following advancements; (1) heat engine's dynamics could be implemented easily in the test system, (2) automatic test data acquisition both in steady state and in transient state enables us to save test time and to enhance the reliability of the tests.

  • PDF

The Modernization of Automatic Control facilities of Hydro Power Plant (수력발전소 자동제어설비의 현대화)

  • Kwon, O-Geuk;Kwon, Young-June;Song, Young-Cheol
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.69-70
    • /
    • 2008
  • Automatic control systems(AVR, Governor, Synchronizer) installed $1970{\sim}1980$ in K-water were considered to be rehabilitated around 2000. Moreover, Korea Power Exchange market system was changed from PPA (Power Purchase Agreement) to a bidding system. Therefore, depending on the power quality, the power provider could achieve additional profits. It is the excitation system and governor that have the functions of enhancing power necessities. During the 20 to 30 years of generator operation, there were many major and minor problems. Examples are SCR burnout (Andong: Excitation system), hunting (Imha: governor), field circuit breaker failure (Chungju 1st: excitation system), the rise of leakage current (Chungju 2nd: excitation system), power supply burnout (Chungju 2nd: governor). These are the typical examples of malfunction which hindered the generator operation and, consequently, diminished the profit of power business. In order to satisfy the needs of the power market and prevent malfunctions mentioned above, the rehabilitation of AVRs and governors were executed. A new system was made to have the flexibility of ancillary service (GF, AGC, etc.), PSS function. With user friendly HMI software, it is more convenient for the operator to fulfill suitable maintenance. It was possible to connect SCADA system by opening protocol of AVR, governor for the efficiency of operation and maintenance.

  • PDF

A Study on the Development of Control System for Low-Speed Diesel Engines for Ships (선박용 저속 디젤 엔진을 위한 제어 시스템 개발에 관한 연구)

  • Kim, Tae-Hoon;Lee, Jun-Ho;Um, Duk-Hyung;Jeong, Dong-Chai
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.11-12
    • /
    • 2005
  • BMS & Governor System은 선박용 추진 기관으로 사용되는 저속 디젤 엔진의 원격 운전 및 제어를 담당하는 시스템으로 선박 추진과 엔진 제어에 필수적인 중요 구성 요소이며, 조선 기자재관련 고부가가치 산업의 한 부분이다. 그러나 조선관련 산업에 있어서 세계 최강국의 위상에 걸맞지 않게 국내에는 BMS & Governor System의 독자 모델이 없는 실정이고, 유럽이나 일본의 제품으로 전량 수입에 의존하고 있는 상황이다. 이에 선박 추진용 저속 디젤 엔진을 위한 제어 시스템의 관련 기술을 연구하여, SEA-CAPS를 개발하였다. 본 연구에서는 BMS & Governor System에 대한 개요와 SEA-CAPS의 개발 내용, 그리고 환경 및 성능 시험에 관한 내용을 언급하고자 한다.

  • PDF