Browse > Article
http://dx.doi.org/10.11142/jicems.2013.2.3.361

Application of FESS Controller for Load Frequency Control  

Lee, Jeong-Phil (Dept. of New & Renewable Electric Energy, Kyungnam College of Information & Technology)
Kim, Han-Guen (Dept. of New & Renewable Electric Energy, Kyungnam College of Information & Technology)
Publication Information
Journal of international Conference on Electrical Machines and Systems / v.2, no.3, 2013 , pp. 361-366 More about this Journal
Abstract
This paper presents the effect on application of the flywheel energy storage system (FESS) for load frequency control (LFC) of an interconnected 2 area power system. To do this, the control characteristics with the FESS were compared with that of the conventional governor controller. The controller for the FESS control and the governor control used a PID type controller. Both the FESS PID controller and the governor PID controller using genetic algorithm (GA) were designed to optimize the PID parameters. The frequency and generation output characteristics with the only FESS controller and with the only conventional governor controller were compared. To verify robust performance of the FESS controller, the computer simulations were performed under various disturbances. The simulation results showed that the FESS controller provided better dynamic responses in comparison with the conventional governor controller.
Keywords
Flywheel energy storage system; Genetic algorithm; Load frequency control; Power system;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Z. Michalewicz, "Genetic algorithm + data structures = evolution program", second edition, Springer-Verlag, 1992
2 C. E Fosha and O. I. Elgerd, "The megawatt-frequency control problem : A new approach via optimal control problem control theory", IEEE Tran. on Power App. And Syst., vol. PAS-80, no. 4, pp. 553-577, 1970
3 Y. Mizutani, "Suboptimal control for load frequency control of P-I type using area-decomposition and aggregation method", IEE J. vol. 100, no. 1, pp. 9-16, 1980
4 C. T. Pan and C. M. Liaw, "An adaptive controller for power system load-frequency control", IEEE Trans. on Power Syst., Vol. 4, No. 1,, pp. 122-128, 1989
5 F. Beaufays. Y. A-M and B. Widrow, "Application of neural networks to load-frequency control in power systems", Neural Networks, vol. 7, no. 1, pp. 183-193, 1994   DOI   ScienceOn
6 C. S. Chang and W. Fu, "Area load frequency control using fuzzy gain scheduling of PI controller", Electric Power Systems Research, Vol. 42, Issue 2, pp. 145-152, 1997   DOI   ScienceOn
7 S. C. Tripathy, "Improved load-frequency control with capacitive energy storage", Energy Conversion and Management, Vol. 38, No. 6, pp. 551-562, 1997   DOI   ScienceOn
8 R. J. Abraham, D. Das, A. Patra, "Automatic generation control of an interconnectec hydrothermal power system considering superconducting magnetic energy storage", Electric Power and Energy System, Vol. 29, pp. 571-579, 2007   DOI   ScienceOn
9 S. C. Tripathy, R. Balasubramanian, P. S. Chandramohanan Nair, "Effect of superconducting magnetic energy storage on automatic generation control considering governor deadband and boiler dynamics", IEEE Trans. on Power Syst., vol. 7, no. 3, pp. 1266-1273, 1992   DOI   ScienceOn
10 I. Ngamroo, "An optimization technique of robust load frequency stabilizer for superconducting magnetic energy storage", Energy conversion and management, vol. 46, pp. 3060-3090, 2005,   DOI   ScienceOn