345kV 및 154kV 송전철탑의 뇌사고율 예측계산 (The Calculation of Lightning Flashover rate of 345kV/154kV Transmission Tower)

  • 심응보;우정욱;곽주식;민병욱;황정일
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 A
    • /
    • pp.452-454
    • /
    • 2001
  • This paper described the calculation results of lightning flashover rate on the 345kV and 154kV transmission system of KEPCO. The back-flashover rate and shielding failure rate was calculated by FLASH(lightning flashover rate calculation program from IEEE) and KEPRI's own program which is based on the EGM(Electro Geometrical Model) method. The estimated lightning flashover late of 345kV transmission system of double circuit was 1.0 flash per 100km-year, and the lightning flashover rate of 154kV transmission line was 2.0 flash Per 100km-year approximately.

  • PDF

New Simulation Method of Flashover Rate by Connection of EMTP and MATLAB

  • Seo, Hun-Chul;Han, Joon;Choi, Sun-Kyu;Lee, Byung-Sung;Kim, Chul-Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • 제11권3호
    • /
    • pp.602-608
    • /
    • 2016
  • Because of the random characteristics of lightning, the Monte Carlo method is applied to estimate the flashover rate due to lightning, however, the simulations using previous methods are difficult to both beginner and expert in power corporations. Therefore, this paper proposes the new and easy method to simulate the flashover rate by connection of electromagnetic transients program (EMTP) and MATLAB. The magnitude of a lightning strike is based on a curve measured in the field, while the classification of direct and indirect lightning depends on the striking distance. In a Korean distribution system, the flashover rate induced by lightning is simulated using proposed method. Simulations of the footing resistance according to the existence of an overhead ground wire (OHGW) are performed and the simulation results are discussed. The simulation results are compared with findings obtained with the IEEE Flash 2.0 program.

건물화재의 플래시오버 도달 시간에 영향을 미치는 인자들에 관한 연구 (Parameter Effects on the Time to Reach Flashover Conditions in Single Room Fires)

  • 김형진;데이비드 릴리;백병준;박복춘
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2003년도 춘계학술대회
    • /
    • pp.1384-1388
    • /
    • 2003
  • In structural fires, flashover is characterized by the rapid transition in fire behavior from localized burning of fuel to the involvement of all combustibles in the enclosure. An investigation of parameter effects on the time to reach flashover conditions in a typical single room fire is undertaken using a zone method (FAST) and Thomas method. Major parameters affecting the time to reach flashover are found to be fire growth rate, ventilation opening area and internal room surface. The results of the FAST and the Thomas Method give very similar results of the time to reach flashover..

  • PDF

건축구조물에 있어서 플래시오버와 연기발생량의 상관관계 분석에 관한 연구 (A Study on the Correlation of Analysis between Flashover and Smoke Production Rate in Building Structure)

  • 서동구;김동은;권영진
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2013년도 추계 학술논문 발표대회
    • /
    • pp.236-237
    • /
    • 2013
  • The fire safety design of performance is fire behavior inside buildings must be scientifically described and systemized as a theory, thereby allowing application to fire safety design of buildings. In this study, experiment of fire behavior according to disposition of combustibles were performed for correlation analysis between flashover and smoke production rate in building structure. As a result, smoke production rates is happened more than 80 m2/s in compartment(ISO 9705). Also, even if the fire load for flashover to if occur smoke did not, which confirmed that the delay time of occurrence.

  • PDF

국내 배전계통의 가공지선 접지조건에 따른 뇌서지 영향 분석 (Analysis of Effect on Lightning Surge according to the Grounding Condition of Overhead Ground Wire in Distribution System)

  • 한준;김철환;서훈철;최선규;이병성
    • 전기학회논문지
    • /
    • 제63권3호
    • /
    • pp.331-337
    • /
    • 2014
  • The Korean distribution system consists of overhead ground wire (OHGW), phase conductors and neutral wire. Especially, OHGW is installed over the phase conductors to protect distribution system from the lightning surge. The flashover rate and the magnitude of lightning overvoltage on distribution system can be affected by grounding condition of OHGW such as grounding resistance and grounding interval. In this paper, we conduct an analysis of lightning overvoltage and flashover rate according to the grounding condition of OHGW. The distribution system and lightning surge are modeled by using ElectroMagnetic Transient Program (EMTP). Also, the Monte Carlo method is applied to consider random characteristics of lightning, and the flashover rate is calculated based on IEEE std. 1410. The simulations are performed by changing the grounding resistance and interval of OHGW and the simulation results are analyzed.

CRIEPI 방식을 이용한 국내 가공 배전선로에서의 뇌 섬락률 산정 (Analysis of Flashover Rate by Lightning in Korea Distribution Line using CRIEPI Method)

  • 최선규;서훈철;한준;김철환;이병성
    • 전기학회논문지
    • /
    • 제62권1호
    • /
    • pp.1-7
    • /
    • 2013
  • This paper analyzes the flashover rate by lightning in Korea distribution system. Because of random characteristics of lightning, the Monte Carlo method is applied to estimate the lightning performance. The magnitude of lightning stroke is based on the curve measured in field. The classification of direct and indirect lightning depends on the striking distance. The striking distance and flashover rate are calculated by using the method based on Central Research Institute of Electric Power Industry(CRIEPI). The distribution system and lightning is modeled by using EMTP and MATLAB, and the accuracy of modeling is discussed. The simulations for the various spacing between two adjacent surge arresters and the various grounding resistance of GW according to the existence of GW are performed and the simulation results are analyzed.

건축 내장재의 Flashover시간 및 열방출량 예측에 관한 연구 (A Study on the Prediction of Flashover Time and Heat Release Rate(HRR) for Building Interior Materials)

  • 하동명
    • 한국화재소방학회논문지
    • /
    • 제18권3호
    • /
    • pp.30-38
    • /
    • 2004
  • 화재성장기 동안의 중요한 특징은 국부연소에서 전실연소로 전이되는 플래시오버 현상이다. 본 연구의 목적은 건축내장재의 플래시오버 시간 및 발화시간 그리고 열방출량을 예측에 있다. Response Surface Methodology(RSM) 방법과 문헌자료를 사용하여 플래시오버 시간 및 발화시간 그리고 열방출량을 예측하는 식을 제시하였다. 예측식에 의해 계산된 플래시오버 시간과 문헌값의 A.A.P.E.는 38.74초, A.A.D.는 51.42초 그리고 상관계수는 0.975이다. 발화시간의 예측값과 문헌값의 A.A.P.E.는 10.96초, A.A.D.는 1.97초 그리고 상관계수는 0.962이다. 또한 시간에 의한 플래시오버 열방출량의 예측값과 문헌값의 A.A.P.E.는 29.92, A.A.D.는 514 그리고 상관계수는 0.830이다. 제시한 예측식에 의한 계산값은 문헌값과 일치하였다. 따라서 본 연구에서 제시된 식이 다른 건축내장재 연구에도 이용되기를 기대한다.

누설 전류 모니터링에 의한 오손된 고분자 애자에서의 섬락 예지 방법 (A Flashover Prediction Method by the Leakage Current Monitoring in the Contaminated Polymer Insulator)

  • 박재준;송영철
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권7호
    • /
    • pp.364-369
    • /
    • 2004
  • In this Paper, a flashover prediction method using the leakage current in the contaminated EPDM distribution polymer insulator is proposed. The leakage currents on the insulator were measured simultaneously with the different salt fog application such as 25g, 50g, and 75g per liter of deionized water. Then, the measured leakage currents were enveloped and transformed as the CDFS using the Hilbert transform and the level crossing rate, respectively. The obtained CDFS having different gradients(angles) were used as a important factor for the flashover prediction of the contaminated polymer insulator. Thus, the average angle change with an identical salt fog concentration was within a range of 20 degrees, and the average angle change among the different salt fog concentrations was 5 degrees. However, it is hard to be distinguished each other because the gradient differences among the CDFS were very small. So, the new weighting value was defined and used to solve this problem. Through simulation, it Is verified that the proposed method has the capability of the flashover prediction.

실대규모 화재시험시 플래시오버와 연기발생율간의 상관성 연구 (Study on Correlation between flashover and smoke production rate in real scale reaction-to-fire test)

  • 박계원;임홍순;정재군;김운형
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2010년도 춘계학술논문발표회 논문집
    • /
    • pp.289-296
    • /
    • 2010
  • This study is aiming at analyzing correlation between flashover's time and maximum smoke production rate's time on sandwich panel specimens. For this analysis, KS F ISO 137481-1 has been performed for 23 kinds of sandwich panels which mainly consist of EPS, PIR, PUR, Glass wool and so on. KS F ISO 13784-1 represents real scale reaction-to-fire test and focuses on measuring flashover phenomenon rather than other tests as like ISO 5660-1 and SBI.

  • PDF

콘칼로리미터를 이용한 내장판용 복합재료의 화재특성 (Fire Characteristics of Composites for Interior Panels Using Cone calorimeter)

  • 이철규;정우성;이덕희
    • 한국철도학회논문집
    • /
    • 제7권1호
    • /
    • pp.55-59
    • /
    • 2004
  • Composite materials were used widely due to merit of light weight, low maintenance cost and easy installation. But it is the cause of enormous casualties to men and properties because of weak about the fire. Particularly, it is more serious in case of subway train installed composite materials. For this reason, experimental comparison has been done fur measuring heat release rate(H.R.R) and smoke production rate(S.P.R) of interior panels of electric motor car using cone calorimeter. A high radiative heat flux of 50kW/㎡ was used to bum out all materials and to simulate the condition of fully developed fire case in the tests. It was observed that Heat Release Rate and Smoke Production Rate curves were dependent on the kinds of the interior materials. From the heat release rate curves, the sustained ignition time, peak heat release rate and total heat release rate were deduced, These data are useful in classifying the materials by calculating two parameters describing the possibility to flashover.