• Title/Summary/Keyword: Facility Diagnosis

Search Result 201, Processing Time 0.036 seconds

A Study on the Breaking down of overhead line in the middle of span (가공전선 경간 중간 단선고장 에 관한 연구)

  • Park, Chul-Bae;Joung, Jong-Man;Kim, Dong-Myeong;Kim, Hanl-Hong
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.509-510
    • /
    • 2011
  • 한국전력공사 배전선로의 가공설비(특고압)는 2011.03 현재 약 615,089 km가 설치 운전 중에 있으며 해마다 가공전선 단선 고장이 일어나고 있어, 원인 규명 및 방지대책을 강구하고 있다. 본 연구에서는 가공전선 단선사고의 일반적인 사례 LP 애자 설치개소가 아닌 선로 중간에서 단선 고장난 사고사례에 관한 것으로써 전선피복(절연체)의 두께와 impulse voltage에 따른 Pinhole 형성 그리고 단선 메커니즘에 대해서 기술하였다.

  • PDF

Design of a Real-Time Facility Diagnosis & Complex Data Management System Using IT Convergence Technology (IT융합기술을 활용한 실시간 설비진단 및 복합정보 관리시스템 설계)

  • Kang, Moon-Sik
    • Journal of the Korea Society of Computer and Information
    • /
    • v.19 no.5
    • /
    • pp.53-60
    • /
    • 2014
  • With the rapid development of IT technology, recently, the development of IT convergence technology related to the facility diagnosis is prevalent, and the study for the efficient integrated management scheme is required to handle all relevant information, from the design to the maintenance, including the stage of repair. In this paper, an efficient scheme to process the complex data for the facility and its diagnosis is proposed based on IT convergence technique and the real-time complex data management is designed. In order to evaluate the performance of the proposed system, the real-time management system is designed for a particular facility, and the comparative results show the good performance of the proposed system.

On the Improvement of the Process by Analyzing Precision Diagnosis of Deteriorated Railroad Communication Facilities

  • Hwang, Sun Woo;Kim, Joo Uk;Park, Jeong Jun;Kim, Hyung Chul;Park, Jin Hyuk;Kim, Young Min;Lee, Gye Chool
    • International Journal of Internet, Broadcasting and Communication
    • /
    • v.13 no.2
    • /
    • pp.136-144
    • /
    • 2021
  • Railroad Systems, which are national infrastructure industries, cause unexpected property and human damage if they fail to function while operating. Accordingly, railroad facilities supporting the railroad system are areas where high reliability and safety are required. However, it is time for systematic and scientific maintenance to be taken away from the traditional maintenance methods, as the nation's railroad facilities are now aging seriously. The purpose of this study was to secure the safety and reliability of the aging railroad communication facilities and to improve their performance. The research subjects were selected as a precision diagnosis process for railroad communication facilities, and improvement points were derived through detailed precision diagnosis process analysis. It is deemed that this study can contribute based on securing stability, improving reliability, and continuous improvement of railroad communication facilities should be conducted in the operation of the entire railroad system.

A Study on Management Body Consciousness for Managing Facility Safety Inspection and Diagnosis (시설물 안전 점검 및 진단 실시에 대한 관리주체 의식에 관한 연구)

  • Kim, Hak-Eung;Jung, Soo-Il
    • Journal of the Korea Safety Management & Science
    • /
    • v.10 no.3
    • /
    • pp.19-27
    • /
    • 2008
  • Since 1995, the facility of class 1 and 2, classified by law had been subject to system of post maintenance management where periodic safety inspection and diagnosis to identify any problems and to take appropriate measures as a matter of urgency. Although the standards and systems had been revised many times for continuous improvement due to surrounding environmental factors, the technical factors and other factors for improvements, continuous researches and efforts are needed to ensure even higher effectiveness. Furthermore, the consciousness of the management body that executes and implements such improvements for facility management is most important. Therefore in this study, through such analysis, more realistic management consciousness review was performed. Also the direction for improvements is proposed, to carry out more effective facility safety management systems implementation.

The AHP Method to Quantitate Investigation Items of Cut Slope (계층분석과정을 통한 절토사면 조사항목의 정량화)

  • Lee, Jong-Young;Shin, Chang-Gun;Kim, Yong-Soo;An, Sang-Lo
    • Proceedings of the Korean Geotechical Society Conference
    • /
    • 2006.03a
    • /
    • pp.732-737
    • /
    • 2006
  • The facility diagnosis technique of past subjective judged the technical expert and interpreted stably mainly. The facility the periodical civil official becomes indispensability consequently with the law and the system and objectivity inspection which relates with a this and development of diagnosis technique were necessary. Currently the evaluation elements which relate with an inspection and diagnosis technique depended to the subjectivity of each facility quality, data statistics, diagnosis know-how, various circumstance and the technical expert and the evaluation item came to decide. But the evaluation score distribution of marks of each item depended plentifully in data analysis result and experience. The past method is weak in logically because the objection theoretical background and basis are insufficiency. Consequently in order to apply a data analysis result and an experience logically, it used AHP(Analytic Hierarchy Process) method from this research. It is visible with the fact that the application result reconfirmation and complement process will be necessary the technique which is suitable in the multi facility management. Also it is expected with the fact that the application characteristic from the next relation technique will be excellent.

  • PDF

Setup of standard PD calibrator and its uncertainties

  • Kim, Kwang-Hwa;Yi, Sang-Hwa;Lee, Heun-Jin;Kang, Dong-Sik
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.5
    • /
    • pp.677-683
    • /
    • 2011
  • The present paper describes the setup of standard partial discharge calibrator for measuring partial discharge and estimating uncertainties. The standard PD calibrator was designed and set up, consisting of a digital pulse generator, capacitor modules, and a digital oscilloscope controlled by software developed in the laboratory. Using this software, averages of charges and rising times and their standard deviations in the measured pulses can also be calculated. The standard PD calibrator generates five types of pulses: single, double, random, oscillating, and long-rising. The coefficient sensitivities to estimate the uncertainties of pulses were extracted in the model circuit of the standard PD calibrator. The uncertainties of charges and rising times in pulses of the standard PD calibrator were estimated with single pulses. These values were 0.3%-1.4% in charges and 1.9%-7.0% in rising time; however, these values are lower than the limit values in IEC 60270.

GISPD Measurement Using UHFPD Measurement System (UHFPD측정시스템을 이용한 GISPD측정)

  • Choi, Jae-Gu;Yi, Sang-Hwa;Kim, Kwang-Hwa
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1857-1859
    • /
    • 2004
  • It is widely known that the ultra high frequency (UHF) method that detects the electromagnetic wave of the PD pulses in the gas insulated space is one of the most competitive methods for its high sensitivity. From the above point of view, this paper describes the noise suppression methods and the PD measurement results of the in-service substation by the developed UHF PD measurement system which consists of the external UHF coupler, the UWB LNA and the digital storage oscilloscope. As results, it was found that the effect of the noise suppression methods were verified and that the developed external UHF coupler showed a better detection sensitivity than a conventional external coupler.

  • PDF

GISPD Analysis Using UHF Dual-Band Method (UHF이중대역법을 이용한 GISPD분석)

  • Kim, Kwang-Hwa;Yi, Sang-Hwa;Choi, Jae-Gu
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1860-1862
    • /
    • 2004
  • It is widely known that the ultra high frequency (UHF) method that detects the electromagnetic wave of the PD pulses in the gas insulated space is one of the most competitive methods for its high sensitivity. From the above point of view, this paper describes the characteristics of GIS PD signals measured with ultra wide band (UWB) GIS PD detecting system in which PD signals are detected into the dual UHF band. The UWB PD detection system consists of the UWB UHF coupler, the UWB low noise amplifier (LNA) and the oscilloscope. The dual bands for PD signals are 0.5-2GHz(full band) and 1-2GHz(high band). As results, it was found that the partial discharges of each defect have their own characteristic pattern and the ratio of High band to Full band increases with gas pressure.

  • PDF

GlSPD Analysis Using UHF Dual-Band Method (UHF 이중대역법을 이용한 GIS PD 분석)

  • Yi, Sang-Hwa;Choi, Jae-Gu;Kim, Kwang-Hwa
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.63-66
    • /
    • 2004
  • It is widely known that the ultra high frequency (UHF) method that detects the electromagnetic wave of the PD pulses in the gas insulated space is one of the most competitive methods for its high sensitivity. From the above point of view, this paper describes the characteristics of GIS PD signals measured with ultra wide band (UWB) GIS PD defecting system in which PD signals are defected into the dual UHF band. Thc UWB PD detection system consists of the UWB UHF coupler, the UWB low noise amplifier (LNA) and the oscilloscope. The dual bands for PD signals are 0.5-2GHz(full band) and 1-2GHz(high band). As results, it was found that the partial discharges of each defect have their own characteristic pattern and the ratio of High hand to Full band increases with gas pressure.

  • PDF