• Title/Summary/Keyword: FDS code

Search Result 43, Processing Time 0.031 seconds

ANALYSIS OF SMOKE SPREAD EFFECT DUE TO THE FIRE STRENGTH IN UNDERGROUND SUBWAY-STATION (대심도 역사의 화재강도에 따른 연기확산 영향 분석)

  • Jang, Yong-Jun;Koo, In-Hyuk;Kim, Hag-Beom;Kim, Jin-Ho
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2011.05a
    • /
    • pp.373-378
    • /
    • 2011
  • As the number of deeply-underground subway station(DUSS) increases, the safety measures for DUSS have been requested. In this research, Shingumho station (The line # 5, Depth: 46m) has been selected as case-study for the analysis of smoke-spread speed with the different fire strength. Field test data measured for actual fan in DUSS was applied as a condition of a simulation. The whole station was covered in this analysis and total of 4 million grids were generated for this simulation. The fire driven flow was analyzed case by case to compare the smoke-spread effect according to the fire strength. in order to enhance the efficiency of calculation, parallel processing by MPI was employed and large eddy simulation method in FDS code was adopted.

  • PDF

Analysis of Smoke Spread Effect Due to The Ventilation Capability in Underground Subway-Station (대심도 역사의 제연팬 용량에 따른 연기확산 영향 분석)

  • Koo, In-Hyuk;Jang, Yong-Jun
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2012.04a
    • /
    • pp.424-427
    • /
    • 2012
  • 본 연구에서는 최근 증가하고 있는 대심도역사의 제연팬 용량에 따른 연기확산영향에 대하여 분석하였다. 시뮬레이션모델은 신금호 역사(5호선, 깊이 46m)를 대상으로 하였으며, 제연팬 용량에 따른 연기확산 영향을 분석 하였다. 현장조사 및 실측을 통하여 계측된 실제 역사의 제연팬에 관한 데이터를 화재시뮬레이션 조건으로 적용하였다. 역사전체를 해석 대상으로 하여 총 400만개의 격자를 사용하였으며, 제연팬 용량에 따른 연기확산 영향 비교를 위하여 화재 시나리오를 작성하여 Case별로 화재해석을 수행하였다. 계산 효율을 높이기 위하여 MPI병렬처리기법을 사용하였으며 해석코드는 LES(large eddy simulation) 기법을 주로 사용하는 FDS5 code를 사용하였다.

  • PDF

A Numerical Study of Fire Development Characteristics on a Ro/Ro Ferry Vehicle Deck. (Ro/Ro 여객선 차량갑판의 화재 특성에 관한 수치 해석 연구)

  • Kim, Sung-Chan;Ryou, Hong-Sun
    • Journal of the Society of Naval Architects of Korea
    • /
    • v.41 no.5
    • /
    • pp.48-54
    • /
    • 2004
  • The present study investigates the fire development characteristics on a Ro-Ro ferry vehicle using the modified FDS code considering droplet break-up. Numerical simulations are compared with model-scale tests for validation of field model. The predicted results such as smoke layer temperature and oxygen concentration are in good agreement with model-scale tests. Also, it is shown that water spray systems are very effective to control the fire development on a vehicle deck. These numerical simulations using a field model may be helpful in accomplishing the fire safety for marine vehicle.

A Numerical Study of the Effect off Fire Growth Model on Fire Characteristics in a Carriage (화재 성장 모델이 객차내 화재 특성에 미치는 영향에 관한 수치해석적 연구)

  • 김성찬;유홍선;최영기;김동현
    • Journal of the Korean Society for Railway
    • /
    • v.7 no.3
    • /
    • pp.180-185
    • /
    • 2004
  • The present study investigates the effect of fire growth model on fire development characteristics in a carriage. The parallel processing version of FDS code is used to simulate the fire driven flow in a carriage and two types of fire growth model which are flame spread model and t$^2$ model are examined for the same geometrical condition. The heat release rates(HRR) of both model are similar each other until 30 s after ignition, but the flame spread model predicts 5 times higher than those of the t$^2$ fire model during the quasi-steady fire period. Maximum heat release rate in the case of flame spread model reaches about to 12 MW at 100 s after fire ignition. Also, various database of fire properties for combustible materials and more elaborate combustion model considering the flame spreading phenomena are required for better predictions of fire development characteristics using numerical simulation.

ANALYSIS OF VORTEX SHEDDING PHENOMENA AROUND PANTOGRAPH PANHEAD FOR TRAIN USING LARGE EDDY SIMULATION (LES를 이용한 판토그라프 팬헤드의 와 흘림 현상 해석)

  • Jang, Yong-Jun
    • Journal of computational fluids engineering
    • /
    • v.16 no.2
    • /
    • pp.17-23
    • /
    • 2011
  • The turbulent flow and vortex shedding phenomena around pantograph panhead of high speed train were investigated and compared with available experimental data and other simulations. The pantograph head was simplified to be a square-cross-section pillar and assumed to be no interference with other bodies. The Reynolds number (Re) was 22,000. The LES(large eddy simulation) of FDS code was applied to solve the momentum equations and the Wener-Wengle wall model was employed to solve the near wall turbulent flow. Smagorinsky model($C_s$=0.2) was used as SGS(subgrid scale) model. The total grid numbers were about 9 millions and the analyzed domain was divided into 12 multi blocks which were communicated with each other by MPI. The time-averaged mainstream flows were calculated and well compared with experimental data. The phased-averaged quantities had also a good agreement with experimental data. The near-wall turbulence should be carefully treated by wall function or direct resolution to get successful application of LES methods.

The Analysis of the effects of the platform screen door on the fire driven flow in The Deeply Underground Subway Station (대심도 지하역사에서의 화재시 플랫폼 스크린 도어에 의한 열, 연기 거동 영향 분석)

  • Jang, Y.J.;Kim, H.B.;Lee, C.H.;Jung, W.S.
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.1984-1989
    • /
    • 2008
  • In this study, fire simulations were performed to analyze the characteristics of the fire driven flow and the effects of the platform screen door on the smoke flow in the station, when the fire occurred in the center of the platform. Soongsil Univ. station (line number 7, 47m in depth underground) was chosen which was the one of the deepest underground subway stations in the Seoul metro, SMRT. The parallel computational method was employed to compute the heat and mass transfer eqn's with 6 CPUs of the linux clustering machine. The fire driven flow was simulated with using FDS code in which LES method was applied. The Heat release rate was 10MW and The Ultrafast model was applied for the growing model of the fire source. The 10,000,000 structured grids were used.

  • PDF

A Numerical Study on the Fire Suppression Characteristics of a Water Mist with Natural Wind in a Road Tunnel (도로터널에서 자연풍에 의한 미세물분무의 화재제어 특성에 관한 수치해석 연구)

  • Hwang, Cheol-Hong;Kim, Han-Su;Lee, Chang-Eon;Jang, Young-Nam;Shin, Hyun-Joon
    • Fire Science and Engineering
    • /
    • v.22 no.3
    • /
    • pp.221-227
    • /
    • 2008
  • In this study, the fire suppression characteristics of a water mist with natural wind in a road tunnel were calculated using the FDS(Fire Dynamic Simulation) code. In addition, the cooling and the chemical kinetic effects of water vapor on fire extinction ere investigated in a counterflow non-premixed flame using a detailed chemistry. As a result, the behavior of fire plume and the spray characteristics of water mist are modified remarkably with the increasing of wind velocity. In the case which is not the external natural wind, small droplets are more efficient in fire suppression than large droplets. However, the large droplets show better results on the fire suppression than the small droplets with the increasing of wind velocity. It can be estimated that the natural wind disturb the penetration of water droplets into the flame region and decrease the effect of oxygen dilution. Finally, it can be identified that the fire into the natural wind can be suppressed with smaller amount of $H_2O$ by flame stretching effect in the flame region than one in an enclosure, and the chemical kinetic effects of $H_2O$ on fire extinction are not affected significantly the velocity of natural wind.

Effects of Fire Curtain and Forced Smoke Ventilation on Smoke Spread to Auditorium in Stage Fire of Theater (공연장 무대 화재 시 방화막과 강제 배연구가 객석으로의 연기 확산에 미치는 영향)

  • Kim, Jae Han;Kim, Duncan;Lee, Chi Young
    • Fire Science and Engineering
    • /
    • v.31 no.5
    • /
    • pp.28-36
    • /
    • 2017
  • In this work, the effects of fire curtain and forced smoke ventilation on smoke spread to auditorium in the stage fire of theater were investigated using the Fire Dynamics Simulator (FDS). For the stage of 31 m (Width)${\times}$34 m (Depth)${\times}$32 m (Height) in dimension, the fast growth fire condition with 10 MW of heat release rate was applied. The forced smoke ventilation was set based on the National Fire Safety Code (NFSC) and previous research. The gap distances between the fire curtain and proscenium wall was established to be 0 m and 0.5 m. When the fire curtain was attached completely to the proscenium wall without any gap, no smoke spread from the stage to the auditorium occurred, independent of forced smoke ventilation. When the gap distance between the fire curtain and proscenium wall was 0.5 m, the smoke layer in the stage descended to the lower height from the bottom than the case without the fire curtain, which was because the smoke spread to auditorium was impeded by the fire curtain. Under the same fire curtain condition, the case with the forced smoke ventilation led to decreasing the mass flow rate of outflow through the gap between the fire curtain and proscenium wall, as compared to the case without the forced smoke ventilation. Based on this study, it was confirmed that the fire curtain and forced smoke ventilation were the effective tools to hold down the smoke spread to the auditorium in the stage fire of theater.

Axisymmetric Simulation of Nonpremixed Counterflow Flames - Effects of Fuel Concentration on Flame Structure - (비예혼합 대향류 화염의 축대칭 모사 - 연료농도가 화염구조에 미치는 영향 -)

  • Park Woe-Chul
    • Journal of the Korean Institute of Gas
    • /
    • v.7 no.3 s.20
    • /
    • pp.44-50
    • /
    • 2003
  • The axisymmetric methane-air counterflow flame was simulated to investigate changes in the flame structure due to the fuel concentration and to evaluate the numerical method. The global strain rates $a_g=20,\;60,\;90\;s^{-1}$ and the mole fractions of methane $x_m=20,\;50,\;80\%$ in the fuel stream were taken to be numerical parameters. The axisymmetric simulation was conducted by using the Fire Dynamics Simulator (FDS) which employed a mixture fraction combustion model, and the results were compared with those of OPPDIF, which is an one-dimensional flamelet code and includes detail chemical reactions. In all the cases tested, there was good agreement in the temperature and axial velocity profiles between the axisymmetric and one-dimensional simulations. It was shown that the flame thickness and peak flame temperature increase and the flame radius decreases as the fuel concentration increases.

  • PDF

COMPUTATIONAL SIMULATION OF FIRE SUPPRESSION SYSTEM FOR CABINS OF SHIPBOARD ENCLOSURE (선박 거주구역용 소화시스템의 전산 시뮬레이션)

  • Jung, I.S.;Chung, H.T.;Han, Y.S.
    • Journal of computational fluids engineering
    • /
    • v.21 no.4
    • /
    • pp.40-45
    • /
    • 2016
  • The numerical simulation has been performed to predict the performance of the fire suppression system for cabin of shipboard enclosure. The present study aims ultimately at finding the optimal parametric conditions of the mist-injecting nozzles using the CFD methods. The open numerical code was used for the present simulation named as FDS (Fire Dynamics Simulator). Application has been done to predict the interaction between water mist and fire plume. In this study, the passenger cabin was chosen as simulation space. The computational domains for simulation in the passenger cabin were determined following the fire scenario of IMO rules. The full scale of the flow field is $W{\times}L{\times}H=4{\times}3{\times}2.4m^3$ with a dead zone of $W{\times}L{\times}H=1.22{\times}1.1{\times}2.4m^3$. The water mist nozzle is installed in ceiling center of 2.3 m height from the floor, and there are six mattresses and four cushions in the simulation space. The combination patterns of orifices to the main nozzle and the position to install nozzles were chosen as the simulation parameters for design applications. From the present numerical results, the centered-located nozzles having evenly combined orifices were shown as the best performance of fire suppression.