• Title/Summary/Keyword: Electric Heater

Search Result 261, Processing Time 0.028 seconds

Fault Prediction Based on Unbalanced Current Detection of Three Phase Heater and Selection of the Protective Device (3상 히터의 불평형전류 검출에 의한 결함예측 및 보호장치의 선정)

  • Lee, Mun Hyung;Jung, Jae Hee
    • Journal of the Korean Society of Safety
    • /
    • v.30 no.1
    • /
    • pp.28-33
    • /
    • 2015
  • Three phase heaters in 7 buildings of 2 sites were examined for precise diagnosis. The sample size was 626. Precise examinations of current and the heater wiring status revealed contact failures and arcs in equipments that had CUF larger than 10%. Contact failures and arcs may cause electrical fire. Therefore, the correlation between the CUF and the imperfections in heater equipment and its wiring was analyzed for three phase heaters. In addition, the protection devices used for detection of heater imperfections were found to be unsuitable for the purpose. Current status of the protection devices was analyzed, and suggestions for improvements were made for new standards of the protection device selection.

Development of Heater Using Eddy Current (와전류를 이용한 발열기의 개발)

  • Yun, Dong-Won;Park, Hee-Chang;Hong, Yong-Ju;Lee, Sung-Hee;Kim, Byung-In;Ham, Sang-Yong
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.33 no.8
    • /
    • pp.565-572
    • /
    • 2009
  • In this research, a heater using eddy current for generator is designed and some analysis is performed to validate the system. FEM (finite element method) is used for analysing eddy current phenomena at the various speed of rotor with permanent magnet. A real heater system is fabricated. Some experiment is also performed to validate the analysis result. Through the experiment, the FE analysis is validated and we found that the efficiency of developed heater is over 94%.

Studies on Performance of CO2 Water Heater by Numerical Modeling (수치적 모델링을 통한 이산화탄소 급탕기의 특성 연구)

  • Park, Han Vit;Yun, Rin
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.1
    • /
    • pp.20-27
    • /
    • 2013
  • Numerical modeling of $CO_2$ water heater was conducted prior to optimal design of medium and large sized $CO_2$ water heater, and the experimental test with small sized $CO_2$ water heater having heat capacity of 4 kW was completed to verify the present numerical model. The present model estimated the experimental data of COP(coefficient of performance), heating capacity, and the hot water outlet temperature within the range of 3% to 8% of mean deviation. As increase of EEV(electric expansion valve) opening area, decreasing of heating capacity and the hot water outlet temperature, and increasing of COP were found in both experimental and numerical investigation.

Design Alterations of a Leak Machine Structure for the Improved Leak Quality of Coolant Heater (Coolant Heater의 기밀성 품질 향상을 위한 Leak Test Machine 구조 개선)

  • Han, Dae Seong;Nam, Kyu Dong
    • Journal of the Semiconductor & Display Technology
    • /
    • v.20 no.2
    • /
    • pp.14-18
    • /
    • 2021
  • Electric Vehicle industry requires high technologies to stabilize apparatuses for the Coolant heater manufacturing. Vibrations of Leak Machine are one of the most critical factors for causing delivered of the defective product or poor inspection, which are the main reasons of the defects. In this study, the structure of the Leak Machine was analyzed through the experiment and the computer simulation to investigate the main reasons of the vibrations, and further to alter the design for the improved stability. And that design alterations were applied to the machine to identify the effects of those alterations. The result of the study shows that design alterations of the Leak Machine can effectively suppress about 97.8% of the vibrations, and further can improving the Inspection precision of the Coolant heater.

Study on Thermal Performance of the Electric Boiler according to Screw Rotation Speed in Heating Tank (가열탱크 내부 스크류 회전속도에 따른 전기보일러의 열성능에 관한 연구)

  • Kum, Jong-Soo;Kim, Dong-Gyu;Park, Jong-Il
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.11 no.3
    • /
    • pp.13-19
    • /
    • 2015
  • This study was aimed at the heating tank with a screw-rotation device for improving the thermal efficiency of electric boiler. In the proposed system, analysis items were the heater rod surface temperature variation, reaching time for set temperature and thermal efficiency. The following conclusions are obtained from this experimental study. (1) When screw speed increases, the time reaching for set temperature tended to be shorter. (2) When the rotation speed becomes 300 rpm, the surface temperature difference between the right and left heater rod decreases by 49%, from $19.7^{\circ}C$ to $9.7^{\circ}C$ in average. (3) When the rotation speed is over 250 rpm, proposed heating tank structure appeared to be effective in terms of thermal efficiency. Thermal efficiency with the rotation speed 300 rpm is improved by 3.8% compared to the case of rotation speed 0 rpm.

Development of Heat Pump System for High Efficiency Engine Vehicle (고효율엔진 차량 히트펌프 시스템 개발)

  • Park, Byung-Duck;Won, Jong-Phil;Lee, Won-Suk
    • Journal of the Korean Society of Industry Convergence
    • /
    • v.10 no.1
    • /
    • pp.21-26
    • /
    • 2007
  • As DDI or GDI engine discharges very low heat due to its high thermal efficiency, the heat source is not enough for heating the passenger compartment in cold climate condition. To remedy the heating problem, the conventional HFC-134a automotive air-conditioning system has been attempted to run as a heat pump mode. Futhermore, an auxiliary electric heater of new type was equipped to the heat pump air-conditioning loop as a new approach. Hence, a proto-type heat pump air conditioner has been made and tested to investigate the feasibility of the HFC-134a automobile air-conditioning system that could be worked as a heat pump. The experiment results showed that the sufficient heating capacity could be obtained by adding a heat pump with an new electric type auxiliary heater into the conventional heat core in low temperature condition.

  • PDF

Precision Control of Water Bath Temperature using Air Cooled Variable Refrigerant Flow Chiller (공랭식 변유량 냉매 냉동기를 적용한 수조 온도의 정밀 제어)

  • Jeong, Kwang-Ju;Kim, Young Il
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.14 no.4
    • /
    • pp.27-34
    • /
    • 2018
  • This study compared constant water bath performances of conventional water-cooled refrigerator and electric heater with an air-cooled VRF chiller and electric heater equipped with optimal control algorithm. In heating mode, the air cooled VRF chiller and electric heater combination reduced the set temperature arrival time by an average of 42 minutes, and energy was also reduced by 18%. In cooling mode, the two systems took 70 minutes to reach the set temperature and showed no difference. Energy was reduced by 33.5% with the new system. For constant temperature maintaining experiment, after reaching the set temperature of $15^{\circ}C$, $20^{\circ}C$ and $22^{\circ}C$, temperature deviations were all in the range of $-0.2^{\circ}C$ to $+0.1^{\circ}C$. Energy was reduced by an average of 84.9%. Through this study, possibility of precise temperature control by an air cooled VRF chiller system was confirmed.

Cause Analysis Ignited at a Far Infrared Radiation Heater (원적외선 히터에서 출화된 화재의 원인분석)

  • Kim, Dong-Ook;Choi, Chung-Seog
    • Fire Science and Engineering
    • /
    • v.22 no.2
    • /
    • pp.91-96
    • /
    • 2008
  • This research studied about the cause analysis of fire that was occurred in far infrared rays heater to base on the fire examples. Fire of electric heater was apt to commit error that handled an over-heating accident by judged molten mark in heat ray. Molten mark which was attached in heat ray was appeared to the form of layer short circuit by other metal material, but other metal material was not found beside the ingredient of heat wire which was mixed to an alloy of Fe-Cr-Al according to result of ingredient distribution by SEM/EDX. Also, the result of overheating experiment by layer short circuit and overvoltage showed higher febrility than normal, but there was no possibility of fire occurrence. This paper will be contributed to science for cause analysis of electric fire through analyzing physical, chemical and flame features of burnout heater on the basis of diagnosis of fire that was happened in infrared rays heater.

Selection of Heater Location in Linear Source for OLED Vapor Deposition (OLED 증착을 위한 선형증발원 히터 위치선정)

  • Joo, Young-Cheol;Han, Choong-Hwan;Um, Tai-Joon;Lee, Sang-Wook;Kim, Kug-Weon;Kwon, Kye-Si
    • Journal of Institute of Control, Robotics and Systems
    • /
    • v.14 no.6
    • /
    • pp.515-518
    • /
    • 2008
  • Organic light emitting diode(OLED) is one of the most promising type of future flat panel display. A linear source is used to deposite organic vapor to a large size OLED substrate. An electric heater which is attached on the side of linear source heats the organic powder for the sublimation. The nozzle of heater, which is attached at the top of the linear source has an optimal temperature. An numerical analysis has been performed to find optimal heater position for the optimal nozzle temperature. A commercial CFD program, FLUENT, is used on the analysis. Two-dimensional and three-dimensional analysis have been performed. The analysis showed that the heater should be attached at the outer side of crucible wall rather than inner side of housing, which was original design. Eighteen milimeter from the top of the linear source was suggested as the optimal position of heater. Improving thermal performance of linear source not only helps the uniformity of organic vapor deposition on the substrate but also increase productibity of vapor deposition process.

Design and Verification of Ceramic Heating Element-based Tankless Instant Electric Water Heater (세라믹 발열체기반 비저장식 순간 전기 온수기 개발 및 검증)

  • Ahn, Sung-Su;Kim, Woo-Hyun
    • Journal of the Institute of Electronics and Information Engineers
    • /
    • v.53 no.11
    • /
    • pp.151-159
    • /
    • 2016
  • This paper proposes a ceramic heating element-based tankless instant electric water heater for hand/face washing that does not require a lot of hot water. The heating module, which heats the input water and outputs hot water, operates the ceramic heating element detecting input water using a flow sensor. Inside of the heating module is designed to form one flow path in order to get almost $15^{\circ}C$ increased heated water compared to the input water temperature within 2 second after 1.5 liter per minute water supply. The design validity is verified using a heat flow analysis of the water flow and temperature variations inside of the heating module also. Based on the design data, the heating module is constructed including a single rod-type ceramic heating element. After that, a prototype system having temperature setting function by three steps were constructed. The prototype system is connected to a 1.5 liter per minute water supply line, and the water output temperature and time measurement experiments confirmed that the proposed system output the heated water increased by $18.3^{\circ}C$ in case of third step setting within 2 second after water supply. And standby power is under 1 W and peak power does not exceed the permissible range for the general house usage. Several performance results verify that the proposed tankless instant electric water heater is applicable for the washstand of the house, highway rest area and factory so on as winter-time hand/face washing.