Studies on Performance of CO2 Water Heater by Numerical Modeling  

Park, Han Vit (Department of Mechanical Engineering, Hanbat National University)
Yun, Rin (Department of Mechanical Engineering, Hanbat National University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.25, no.1, 2013 , pp. 20-27 More about this Journal
Abstract
Numerical modeling of $CO_2$ water heater was conducted prior to optimal design of medium and large sized $CO_2$ water heater, and the experimental test with small sized $CO_2$ water heater having heat capacity of 4 kW was completed to verify the present numerical model. The present model estimated the experimental data of COP(coefficient of performance), heating capacity, and the hot water outlet temperature within the range of 3% to 8% of mean deviation. As increase of EEV(electric expansion valve) opening area, decreasing of heating capacity and the hot water outlet temperature, and increasing of COP were found in both experimental and numerical investigation.
Keywords
$CO_2$ water heater; Numerical modeling; Gas cooler; IHX; EEV;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Sanchez, D., Torrella, E., Cabello, R., and Llopis, R., 2010, Influence of the superheat associated to a semihermetic compressor of a transcritical $CO_2$ refrigeration plant, Applied Thermal Engineering Vol. 30, pp. 302-309.   DOI   ScienceOn
2 Kim, S. G. and Kim, M. S., 2003, Experimental studies on the performance of a transcritical cycle for hot water heating using carbon dioxide, Korea Journal of Air-conditioning and Refrigeration, Vol, 15, pp. 461-470.   과학기술학회마을
3 Beak, C., Lee, E., Kang, H., Kim, Y., Cho, H., and Cho, S. 2008, Experimental study on the heating performance of a $CO_2$ heat pump water heater, Korea Journal of Air-conditioning and Refrigeration, Vol, winter, pp. 310-315.
4 Lee, H. S., Kim, J.-D., Woo, J.-T., and Chang, K. S., 2009, A Study on the performance characteristics of heat pump system using carbon dioxide as refrigerant, Korea Journal of Airconditioning and Refrigeration, Vol, winter, pp. 645-650.
5 Park, H. V., Quoc, N., Yun, R., Kim, Y., Lee, S. J., and Choi, S., 2011, Developing the $CO_2$ water heater adapting high efficient gas cooler, Korea Journal of Air-conditioning and Refrigeration, Vol. winter, pp. 29-32.
6 Laioradit, P., Tiansuwa, J., Kiatsiriroat, T., and Aye, L., 2008, Theoretical performance analysis of heat pump water heater using carbon dioxide as refrigerant, Int. J. Energy Res, Vol. 32, pp. 356-366.   DOI   ScienceOn
7 Cho, H., Lee, M.-Y., and Kim, Y., 2009, Numerical evaluation on the performance of advanced $CO_2$ cycles in the cooling mode operation, Applied Thermal Engineering Vol. 29, pp. 1485-1492.   DOI   ScienceOn