수조모델 실험에 의한 접지저항 추정 (presumption of Earth Resistance by Water Tank Model)

  • 고희석;최종규;김주찬;이충식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2002년도 학술대회논문집
    • /
    • pp.125-131
    • /
    • 2002
  • It is very important to assume potential distribution to be generated in electrode environs and grounding resistance by current beforehand, when incoming at grounding electrode to plan efficient grounding facilities In this paper, we analyzed grounding resistance through a simulation experiment by a water tank scaled model electrode of the rectangular earth plate, a theoretical Calculation result of the rectangular earth plate and measurement of grounding resistance buried rectangular earth plate analysing earth surface potential.

  • PDF

철탑접지저항 측정에 관한 연구 (A Study on Measurement for Earth Resistance of Steel Structure)

  • 박석탁;김시영
    • 전기의세계
    • /
    • 제22권6호
    • /
    • pp.33-51
    • /
    • 1973
  • To lower the earth resistance shall be one of the most effective method for the prevention of lightening damage on power transmission line. In this report, in order to investigate various characteristic necessary to lowering the earth resistance, the following experiments have been made at 154KV U1San-PoHang T/L, 154KV YoSu-SoonChun T/L and so on. 1. Measurement of Earth specific resistance, 2. Efficiency of Earthing of concrete foundation for steel structure., 3. Efficiency of Earthing with counter poise., 4. Compound impulse test with foundation of steel structure and counter poise. With the above investigate a guidance have been prepared for the effective work-performance of steel structure.

  • PDF

심타접지와 천타병렬접지에 관한 이론적해석 (Theoretical Analysis of Earth Deep-Driven Rod and Earth Slight-Driven Parallel Rods in the Earth)

  • 김주찬;최종규;이충식;고희석
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 춘계학술대회 논문집
    • /
    • pp.358-360
    • /
    • 2004
  • To reduce the earth resistance, earth electrode are installed horizontally or vertically in the earth. There are two kinds of vertical earth electrode methods, one is a deep-driven rod and another is slight-driven parallel rods. Bibliography have so far analyzed the earth resistance calcalation of a rod type electrode and parallel rods type for the multi-layered earth. Befor long, We are going to study earth resistance of deep-driven rod and slight-driven parallel rods in the multi-layered earth with reference to bibliography.

  • PDF

수직 접지전극의 접지임피던스 측정에서 도전유도에 의한 오차 평가 (Evaluation of Errors Due to Earth Mutual Resistance in Measuring Ground Impedance of Vertically-driven Ground Electrode)

  • 최종혁;최영철;이복희
    • 전기학회논문지
    • /
    • 제58권9호
    • /
    • pp.1778-1783
    • /
    • 2009
  • Ground impedance for the large grounding system is measured according to the IEEE Standard 81.2 which is based on the revised fall-of-potential method of installing auxiliary electrode at a right angle. When the auxiliary electrodes are located at an angle of $90^{\circ}$, the ground impedance inevitably includes the error due to earth mutual resistance. In this paper, in order to accurately measure the ground impedance of vertically-driven ground electrodes, error rates due to earth mutual resistance are evaluated by ground resistance and ground impedance measuring devices and compared with calculated values. As a result, the measured results are in good agreement with the computed results considering soil layer with different resistivity. The error rates due to earth mutual resistance decrease with increasing the length of ground electrode in the case that the ratio of the distance between the ground rod to be measured and the auxiliary electrodes to the length of ground electrode(D/L) is same. The ground impedance should be measured at the minimum distance between the auxiliary electrodes that will have an estimated measurement accuracy due to earth mutual resistance.

공동 접지망에서의 접지 저항값 시뮬레이션 및 측정 (Simulation and Measurement of Earth resistance Values in Common Earth Network)

  • 김용규;김종기;양도철;박현준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 B
    • /
    • pp.1073-1074
    • /
    • 2006
  • In this paper, we perform a simulation to verify the earth resistance values in Common Earth Network. The simulation is performed on the assumption that certain shorts are occurred in common earth network. Furthermore, from the result, we confirmed that very small earth resistance values in common earth network are given, by carrying out practical measurements in railway sections where common earth network is composed. From the effect, we could discover that the construction of common earth network is in a disadvantageous position on the financial aspect, while it is the most desirable way of construction for the purpose of Earth.

  • PDF

현장실증시험에 의한 대지저항률별 접지저항 보정계수의 결정 (The Determination of Corrective Coefficient for Ground Resistance about Variation of Soil Resistivity by Field Test)

  • 심건보;김경철;이형수;박재덕;박상만
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2006년도 춘계학술대회 논문집
    • /
    • pp.288-292
    • /
    • 2006
  • Usually, equations that calculate ground resistance of earth electrode was already informed well by form of earth electrode. But, when apply on the spot because general expressions are very insufficient at point that calculate exact ground resistance value by variation of earth electrode, and constant value that corrective coefficient for ground resistance calculation is fixed regardless of change of the earth resistivity specially is presented, it is actuality that difficulty is. Therefore, in this study, about these problem, proposed corrective coefficient for calculation of ground resistance according to change of the earth resistivity.

  • PDF

FORM 신뢰성 기반 항타강관말뚝 저항계수 산정 (FORM Reliability-based Resistance Factors for Driven Steel Pipe Piles)

  • 박재현;허정원;이주형;정문경;곽기석
    • 한국지반공학회:학술대회논문집
    • /
    • 한국지반공학회 2008년도 추계 학술발표회
    • /
    • pp.779-783
    • /
    • 2008
  • LRFD Resistance factors for static bearing capacity of driven steel pipe piles were calibrated in the freamework of reliability theory. Reliability analysis was performed by the First Order Reliability Method (FORM) using resistance bias factor statistics.The target reliability indices are selected as 2.0 and 2.33 for group pile case and 2.5 for single pile case, based on the reliability level of the current design practice and considering redundancy of pile group, acceptable risk level, construction quality control, and significance of individual structure.

  • PDF

토양환경 변화와 접지저항의 상관관계 분석을 통한 접지 저항값 예측 연구 (Estimation of Grounding Resistance by Correlation Analysing Change Factors of Soil Resistivity and Grounding Resistance)

  • 최선규;이규영;문영호;심건보
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제6권1호
    • /
    • pp.35-40
    • /
    • 2020
  • The purpose of this paper is to improve the grounding point measurement method for the maintenance of the earth resistance of the distribution line. This study defines the correlation among humidity of the soil, the earth resistivity and the grounding resistance. Based on the results of the study, the grounding resistance value measurement should be limited to the location where the earth resistivity change is large, and the measurement time and cost can be greatly reduced.

Development of the ANN for the Estimation of Earth Parameter and Equivalent Resistivity

  • Ji Pyeong-Shik;Lee Jong-Pil;Shin Kwan-Woo;Lim Jae-Yoon;Kim Sung-Soo
    • KIEE International Transactions on Power Engineering
    • /
    • 제5A권4호
    • /
    • pp.350-356
    • /
    • 2005
  • Earth equipments are essential to protect humans and other types of equipment from abnormal conditions. Earth resistance and potential must be restricted within a low value. An estimation algorithm of earth parameters and equivalent resistivity is introduced to calculate reliable earth resistance in this research. The proposed algorithm is based on the relationship between apparent resistances and earth parameters. The proposed algorithm, which approximates the non-linear characteristics of earth by using the Artificial Neural Network (ANN), estimates the earth parameters and equivalent resistivity. The effectiveness of the proposed method is verified with case studies.