• Title/Summary/Keyword: EDG System

Search Result 23, Processing Time 0.019 seconds

Operating Vibration Reduction Effect Evaluation of EDG at the NPP Site (원자력발전소 비상디젤발전기의 가동중 진동저감 효과)

  • Kim, Min-Kyu;Choun, Young-Sun
    • Proceedings of the Korean Society for Noise and Vibration Engineering Conference
    • /
    • 2006.11a
    • /
    • pp.111-118
    • /
    • 2006
  • The Emergency Diesel Generator(EDG) is a very important piece of equipment for the safety of a Nuclear Power Plant(NPP). In this study, the operating vibration or three kinds or EDG system was measured. The target EDG systems art Yonggwang 5 unit, Ulchin 2 unit and Ulchin 3 unit. The Yonggwang 5 and Ulchin 3 unit EDG system is the same type but the foundation systems are different. One is an anchor bolt type and the other is a spring and viscous-damper type. The purpose of this measurement is for a verification of the vibration isolation effect according to the foundation system. As a result. it can he said that the spring and viscous damper system of the EDG performed well for the vibration isolation.

  • PDF

Seismic Risk Evaluation of Isolated Emergency Diesel Generator System (면진된 비상디젤발전기의 지진위험도 평가)

  • Kim, Min-Kyu;Ohtori, Yasuki;Choun, Young-Sun
    • Proceedings of the Computational Structural Engineering Institute Conference
    • /
    • 2007.04a
    • /
    • pp.217-222
    • /
    • 2007
  • An Emergency Diesel Generator (EDG) is one of the safety related equipments of a Nuclear Power Plant. The seismic capacity of an EDG in nuclear power plants influences the seismic safety of the plants significantly. A recent study showed that the increase of the seismic capacity of the EDG could reduce the core damage frequency (CDF) remarkably. It is known that the major failure mode of the EDG is a concrete coning failure due to a pulling out of the anchor bolts. The use of base isolators instead of anchor bolts can increase the seismic capacity of the EDG without any major problems. This study introduces a seismic risk analysis method and presents sample results about the seismically isolated and conventional EDG system.

  • PDF

Analysis of Seismic Fragility Improvement Effect of an Isolated Rotational Equipment (면진장치를 설치한 회전기기의 지진취약도 개선효과 분석)

  • Kim, Min-Kyu;Ohtori, Yasuki;Choun, Young-Sun;Choi, In-Kil
    • Journal of the Earthquake Engineering Society of Korea
    • /
    • v.11 no.6
    • /
    • pp.69-78
    • /
    • 2007
  • In this study, for the evaluation of seismic safety of the isolated Emergency Diesel Generator (EDG) System more quantitatively, the seismic fragility analysis method were proposed. Using the proposed method, seismic fragility analysis performed and a seismic risk of EDG system was present. The fragility analysis performed not for an existing EDG system but also for an isolated EDG system which increases the seismic capacity. At first, numerical models for existing and isolated EDG system were constructed and seismic response analysis performed according to input seismic waves and peak ground accelerations. An uncertainty factors and failure modes of both fixed and isolated EDG system were assumed for fragility analysis. The HCLPF values were evaluated for the compare the improvement effect using the isolation system. As a result, the isolation system can make better the seismic fragility of EDG system, but the failure of isolation system was govern the behavior of whole system.

The Shaking Table Test of Isolated Model EDG System (면진된 모형디젤발전기의 지진응답실험)

  • Kim, Min-Kyu;Choun, Young-Sun
    • Proceedings of the Earthquake Engineering Society of Korea Conference
    • /
    • 2006.03a
    • /
    • pp.479-486
    • /
    • 2006
  • This paper presents tile results of experimental studies of the isolated Model EDG Systems. For the experimental work, the scaled model of EDG system and the isolation systems were developed. The target EDG model is 16PC2-5V400 which was manufactured by the SEMT Pielstick corporation. The Coil Spring and Viscous Damper Systems were selected for the isolation system. The Coil Spring and Viscous Damper systems can reduce not only seismic forces but also the operating vibration. For the input seismic motions, the scenario earthquake and the artificial earthquakes which were developed as NRC design spectrum and Uniform hazard Spectrum(UHS) were selected. As a result, at least 20% of seismic forces were decreased as the isolation system.

  • PDF

A PERFORMANCE ASSESSMENT OF A BASE ISOLATION SYSTEM FOR AN EMERGENCY DIESEL GENERATOR IN A NUCLEAR POWER PLANT

  • Choun, Young-Sun;Kim, Min-Kyu
    • Nuclear Engineering and Technology
    • /
    • v.40 no.4
    • /
    • pp.285-298
    • /
    • 2008
  • This study evaluates the performance of a coil spring-viscous damper system for the vibration and seismic isolation of an Emergency Diesel Generator (EDG) by measuring its operational vibration and seismic responses. The vibration performance of a coil spring-viscous damper system was evaluated by the vibration measurements for an identical EDG set with different base systems - one with an anchor bolt system and the other with a coil spring-viscous damper system. The seismic performance of the coil spring-viscous damper system was evaluated by seismic tests with a scaled model of a base-isolated EDG on a shaking table. The effects of EDG base isolation on the fragility curve and core damage frequency in a nuclear power plant were also investigated through a case study.

Evaluation of Vibration Characteristics of Operating Rotational Machines Depending of Types of Foundation (기초형식에 따른 회전기기의 가동중 진동특성 분석)

  • Kim, Min-Kyu;Choun, Young-Sun
    • Journal of the Earthquake Engineering Society of Korea
    • /
    • v.11 no.3 s.55
    • /
    • pp.63-72
    • /
    • 2007
  • The Emergency Diesel Generator (EDG) is a very important equipment for the safety of a Nuclear Power Plant (NPP). In this study, the operating vibration of three kinds of EDG systems was measured. The target EDG systems are Yonggwang 5 unit and Ulchin 2 and 3 units. The Yonggwang 5 and Ulchin 3 unit EDG systems are the same type but the foundation systems are different. One is an anchor bolt type and the other is a spring and viscous-damper type. The purpose of these measurements is for a verification of the vibration isolation effect depending on the foundation system. As a result, It can be said that the spring and viscous damper system of the EDG performed better for the vibration isolation than that of anchor bolt type.

Mechanical Characteristics Analysis of Coil Spring & Viscous Damper System (Coil Spring & Viscose Damper System의 동적거동특성분석)

  • Kim, Min-Kyu;Choun, Young-Sun
    • Proceedings of the Earthquake Engineering Society of Korea Conference
    • /
    • 2006.03a
    • /
    • pp.471-478
    • /
    • 2006
  • This paper presents the results of experimental studies of the mechanical characteristics of the Coil Spring and Viscous Damper system. The Coil Spring and Viscous Damper systems were selected for the isolation of Emergency Diesel Generator (EDG) which is located in Nuclear Power Plant (NPP). The Coil Spring and Viscous Damper systems were developed for, the operating vibration isolation and seismic isolation for scaled Model EDG System. The damping properties of the viscous damper changes as the variation of velocity. As a results, nonlinear damping characteristics of viscous damper system were evaluated.

  • PDF

A Study of Analytical Integrity Estimations for the Structure and Rotor System of an Emergency Diesel Generator (비상디젤발전기의 회전체 및 구조물 해석적 건전성 평가에 관한 연구)

  • Kim, Chae-Sil;Choi, Heon-Oh;Jung, Hoon-Hyung
    • Transactions of the Korean Society for Noise and Vibration Engineering
    • /
    • v.24 no.2
    • /
    • pp.79-86
    • /
    • 2014
  • This paper describes an integrity evaluation method for emergency diesel generator(EDG) and rotor part of EDG. EDG is a very important equipment in the nuclear power plant(NPP). EDG supplies electricity to the safety-related equipments for the safety shut down of NPP in an emergency situation of earthquake. The safety of the rotor part of EDG is also important during seismic impact from earthquake. The finite element modelling of the EDG including rotor part was constructed. The modal analysis of EDG was firstly performed. The first natural frequency was calculated and revealed higher than the cutoff frequency of seismic spectrum. Then the stress analysis was done to compare with the allowable stress. The safety of the rotor part was investigated by the finite element analysis of the rotor and journal bearing interaction to find film thickness and critical speed. The seismic load was applied to rotor part in a manner that the load was a weighted static load. Analysis results showed that the maximum stress was within the range of allowable stress and the film thickness is larger than the permissible minimum thickness, and the critical speed was out of the operating speed. Hence, the structural and dynamic integrity of EDG could be confirmed by the numerical analysis method used in this paper. However, dynamic analysis of a rotating rotor and supporting bearing with the seismic impact needs to be investigated in a more rigorous method since the seismic load to the rotating part complicates the behavior of rotating system.

A Study on the Development of EDG Engine Condition Diagnosis Program in Power Plant (발전용 비상디젤발전기 엔진 상태진단 프로그램 개발 연구)

  • Lee, Sang-Guk;Kim, Dae-Woong
    • Journal of Power System Engineering
    • /
    • v.19 no.5
    • /
    • pp.67-72
    • /
    • 2015
  • The reliable operation of onsite emergency diesel generator(EDG) should be ensured by a conditioning monitoring system designed to maintain, monitor and forecast the reliability level of diesel generator. The purpose of this paper is to develop condition diagnosis algorithm(logic) and analysis program of engine for the accurate diagnosis in actual condition of emergency diesel generator engine. As a result of this study, we confirmed that developed engine condition diagnosis algorithm and analysis program could be efficiently applied for actual EDG engine in nuclear power plant.

Development of the Monitoring and Diagnosis Technique on Emergency Diesel Generator System (비상디젤발전기계통 상태감시 및 고장진단기술 개발)

  • Cho, Kwon-Hae;Rhyu, Keel-Soo;So, Myung-Ok;Park, Jong-Il;Son, Min-Su;Ahn, Jong-Kap;Lee, Yun-Hyung;Jang, Tae-Lin
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2005.06a
    • /
    • pp.777-782
    • /
    • 2005
  • The importance of emergency diesel generator(EDG) has confirmed in the safety evaluation of PSA and the study on aging of EDG has been progressed actively as a part of the project of nuclear plant aging research in the U.S.A. As the result, the concept of performance evaluation is being transferred from statistical analysis of test results to performance monitoring and trending analysis for monitoring of aging and reliability. Recently, the study related aging characteristic and reliability for EDGS has begun in Korea. Consequently, the efficient performance monitoring based systematic and integrated monitoring and failure diagnostic technology is necessary. In the research, the knowledge basis of monitoring parameters for EDGS is constructed, and the prototype monitoring and diagnosis system applicable to Pielstick EDG is developed.

  • PDF