• 제목/요약/키워드: Double tube heat exchanger

검색결과 65건 처리시간 0.023초

헬리컬 코일관 내 초임계 $CO_2$의 압력강하 특성 (Pressure Drop Characteristics of Supercritical $CO_2$ in a Helically Coiled Tube)

  • 유태근;김대희;노건상;구학근;오후규
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2005년도 전기학술대회논문집
    • /
    • pp.216-221
    • /
    • 2005
  • The heat transfer coefficient and pressure drop during gas cooling process of carbon dioxide in a helically coiled tube were investigated experimentally. The experiments were conducted without oil in the refrigerant loop. The main components of the refrigerant loop are a receiver, a variable speed pump, a mass flowmeter, a pre-heater, a gas cooler(test section) and an isothermal tank. The test section is a double pipe type heat exchanger with refrigerant flowing in the inner tube and water flowing in the annulus. It was made of a copper tube with the inner diameter of 4.85 [mm], the outer diameter of 6.35 [mm] and length of 10000 [mm]. The refrigerant mass fluxes were 200${\sim}$600 [kg/$m^2$s] and the average pressure varied from 7.5 [MPa] to 10.0 [MPa]. The main results were summarized as follows: The heat transfer coefficient of supercritical $CO_2$ increases, as the cooling pressure of gas cooler decreases. And the heat transfer coefficient increases with the increase of the refrigerant mass flux. The pressure drop decreases in increase of the gas cooler pressure and increases with increase the refrigerant mass flux.

  • PDF

설비공학 분야의 최근 연구 동향 : 2012년 학회지 논문에 대한 종합적 고찰 (Recent Progress in Air-Conditioning and Refrigeration Research : A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2012)

  • 한화택;이대영;김사량;김현정;최종민;박준석;김수민
    • 설비공학논문집
    • /
    • 제25권6호
    • /
    • pp.346-361
    • /
    • 2013
  • This article reviews the papers published in the Korean Journal of Air-Conditioning and Refrigeration Engineering during 2012. It is intended to understand the status of current research in the areas of heating, cooling, ventilation, sanitation, and indoor environments of buildings and plant facilities. The conclusions are as follows : (1) The research works on thermal and fluid engineering have been reviewed as groups of fluid machinery, pipes and valves, fuel cells and power plants, ground-coupled heat pumps, and general heat and mass transfer systems. Research issues are mainly focused on new and renewable energy systems, such as fuel cells, ocean thermal energy conversion power plants, and ground-coupled heat pump systems. (2) Research works on the heat transfer area have been reviewed in the categories of heat transfer characteristics, pool boiling and condensing heat transfer, and industrial heat exchangers. Researches on heat transfer characteristics included the results for natural convection in a square enclosure with two hot circular cylinders, non-uniform grooved tube considering tube expansion, single-tube annular baffle system, broadcasting LED light with ion wind generator, mechanical property and microstructure of SA213 P92 boiler pipe steel, and flat plate using multiple tripping wires. In the area of pool boiling and condensing heat transfer, researches on the design of a micro-channel heat exchanger for a heat pump, numerical simulation of a heat pump evaporator considering the pressure drop in the distributor and capillary tubes, critical heat flux on a thermoexcel-E enhanced surface, and the performance of a fin-and-tube condenser with non-uniform air distribution and different tube types were actively carried out. In the area of industrial heat exchangers, researches on a plate heat exchanger type dehumidifier, fin-tube heat exchanger, an electric circuit transient analogy model in a vertical closed loop ground heat exchanger, heat transfer characteristics of a double skin window for plant factory, a regenerative heat exchanger depending on its porous structure, and various types of plate heat exchangers were performed. (3) In the field of refrigeration, various studies were executed to improve refrigeration system performance, and to evaluate the applicability of alternative refrigerants and new components. Various topics were presented in the area of refrigeration cycle. Research issues mainly focused on the enhancement of the system performance. In the alternative refrigerant area, studies on CO2, R32/R152a mixture, and R1234yf were performed. Studies on the design and performance analysis of various compressors and evaporator were executed. (4) In building mechanical system research fields, twenty-nine studies were conducted to achieve effective design of mechanical systems, and also to maximize the energy efficiency of buildings. The topics of the studies included heating and cooling, HVAC system, ventilation, renewable energy systems, and lighting systems in buildings. New designs and performance tests using numerical methods and experiments provide useful information and key data, which can improve the energy efficiency of buildings. (5) In the fields of the architectural environment, studies for various purposes, such as indoor environment, building energy, and renewable energy were performed. In particular, building energy-related researches and renewable energy systems have been mainly studied, reflecting interests in global climate change, and efforts to reduce building energy consumption by government and architectural specialists. In addition, many researches have been conducted regarding indoor environments.

12.7mm 내면핀관을 이용한 R-1270의 열전달 특성 (Heat Transfer Characteristics of R-1270 using 12.7mm Inner Fin Tube)

  • 윤정인;성광훈;심규진;진병주;백승문;문춘근
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제32권4호
    • /
    • pp.534-541
    • /
    • 2008
  • This paper deals with the heat transfer characteristics of R-290 (Propane), R-600a (Iso-butane) and R-1270 (Propylene) as an environment friendly refrigerant and R-22 as a HCFC's refrigerant for evaporating. The experimental apparatus has been set-up as conventional vapor compression type refrigeration and air-conditioning system. The test section is a horizontal double pipe heat exchanger. Evaporating heat transfer measurements were performed for smooth tube with the outer diameters of 12.70, 9.52 and 6.35 mm and micro-fin tube 12.70 mm, respectively. For the smooth and micro-fin tubes measured in this study, the evaporating heat transfer coefficient was enhanced according to the increase of the mass flux and decrease of the tube diameter. The local evaporating heat transfer coefficients of hydrocarbon refrigerants were superior to those of R-22 and the maximum increasing rate of heat transfer coefficient was found in R-1270. The average evaporating heat transfer coefficients in hydrocarbon refrigerants showed 20 to 28% higher values than those of R-22. Also, the evaporating heat transfer coefficients of R-22 in the tube diameter of the 12.70 mm smooth and micro-fin tube were compared. Generally, the local heat transfer coefficients for both types of tubes increased with an increase of the mass flux. The heat transfer enhancement factor (EF) between smooth and micro-fin tube varied from 1.9 to 2.7 in all experimental conditions.

수직이중관형 잠열축열장치의 성능분석 (Performance Analysis of a Vertical Double Pipe Heat Exchanger for Latent Heat Storage)

  • 김영복;송현갑
    • 태양에너지
    • /
    • 제10권1호
    • /
    • pp.38-46
    • /
    • 1990
  • 고밀도 잠열축열장치의 최적설계와 효율적인 작동을 위해서는 그 전열특성과 축열효율이 규명되어야 한다. 본 연에서는 수직이중관형 잠열축열장치의 방열과정에서의 전열특성을 이론 및 실험적으로 분석하였으며 두 결과는 잘 일치하였다. 그리고 컴퓨터 시뮬레이션을 통하여 방열효율에 대한 설계 및 작동피라미터의 영향을 분석하였다.

  • PDF

관경별 탄화수소계 냉매의 증발 열전달에 관한 특성평가 (Study on Evaporating Heat Transfer of HCs Refrigerants by Changing of Tube Diameter)

  • 이광배;이호생;문춘군;김재돌;윤정인
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2005년도 후기학술대회논문집
    • /
    • pp.41-42
    • /
    • 2005
  • The experimental apparatus has been set-up as a conventional vapor compression type heat pump system. The test section is a horizontal double pipe heat exchanger. A tube diameter of 12.70 mm, 9.52 mm, 6.35 mm with 1.78 mm,1.52 mm,1.4 mm wall thickness each is used for this investigation. The local evaporating heat transfer coefficients of hydrocarbon refrigerants were superior to that of R-22. and the maximum increasing rate of heat transfer coefficient was found in R-1270. The average evaporating heat transfer coefficient increased with the increase of the mass velocity and it showed the higher values in hydrocarbon refrigerants than R-22. The highest evaporating heat transfer coefficient of all refrigerants was shown in a tube diameter of 6.35 mm with same mass flux.

  • PDF

지열원 시스템 히트펌프의 냉방 성능 특성에 관한 실증 연구 (Verification experiment of a ground source multi-heat pump at cooling mode)

  • 임효재;강신형;최재호;최종민;문제명;권영석;권형진;김록희
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 동계학술발표대회 논문집
    • /
    • pp.21-26
    • /
    • 2008
  • Recently, small and medium-sized buildings have employed a multi-heat pump. The major benefits of the multi-heat pump over a conventional system are that it is easier system to maintain along with a diversification of facility use, and high comfortability. The performance of multi-heat pump systems can be enhanced by using geothermal energy instead of air source energy. This paper describes the multi-heat pumps applied in an ground source heat pump system for an actual building. The performance of a ground source multi-heat pump installed in the field was investigated in cooling mode. The maximum COP of the systems with single U-tube and double tube ground loop heat exchangers were 6.6 and 6.0, respectively. It is suggested that the new algorithms to control the flow rate of secondary fluid for ground loop heat exchanger have to be developed in order to enhance the performance of the system.

  • PDF

LNG 냉열활용을 위한 초저온 열교환시스템의 축소모형에서 증발 열전달 특성 (Characteristics of Evaporation Heat Transfer in a Small-Scale Cryogenic Heat Exchange System for the Utilization of LNG Cold Energy)

  • 남상철;이상천;이용원;손영순
    • 한국가스학회지
    • /
    • 제2권4호
    • /
    • pp.25-33
    • /
    • 1998
  • 본 연구는 LNG냉열활용을 위해 초저온 열교환시스템을 제작하고 액화질소와 에틸렌-글리콜 수용액을 작동유체로 사용하여 증발 열전달 특성실험을 수행하였다. 초저온 열교환기는 2중관식 열교환기이며, 내부관 지름이 8, 15 mm이며 길이는 6m이다. wire-coil inserts를 사용하여 열전달촉진 성능평가를 수행하였다. 액화질소와 에틸렌-글리콜 수용액의 출입구 온도, 벽면온도, 유량, 압력을 측정하였고, 이를 증발 열전달계수와 누셀트수를 계산하는데 사용하였다. 열전달상관식을 누셀트수, 프란틀수와 등가레이놀즈수의 멱법칙관계로 제안하였고, 그 결과 열전달촉진관이 평활관보다 2.5 ${\~}$ 5.5배정도 열전달이 증가되었다. 이 상관식을 이용하여 LNG냉열이용을 위한 초저온 2중관 열교환기를 설계하였고, 그 결과로 제시하였다.

  • PDF

아이스슬러리형 빙축열 시스템을 이용한 냉각 시스템의 성능에 관한 실험적 연구 (Characteristic Analysis of the Cooling System Using Ice Slurry Type Heat Storage System)

  • 이동원;김정배
    • 에너지공학
    • /
    • 제20권1호
    • /
    • pp.30-35
    • /
    • 2011
  • 2중관형과 판형 열교환기에 에틸렌 클리콜-물 수용액으로 만들어진 아이스슬러리를 적용하는 경우의 유동 및 열적 특성을 규명하기 위하여 실험을 수행하였다. 아이스슬러리의 질량유속과 얼음 분율은 각각 800에서 3500 kg/$m^2s$과 0에서 25%이었다. 실험을 통해, 압력강하와 열전달율은 질량유속과 얼음 분율에 따라 증가하였다. 그러나 얼음 분율의 효과는 높은 질량유속 영역에서는 크지 않은 것으로 나타났다. 낮은 질량유속에서는 압력강하와 열전달율의 급속한 증가가 질량 유속에 관계되는 것으로 나타났다.

태양에너지 해수담수화를 위한 3중 효용 증발식 담수기 개발 (Development of 3th Effects Evaporative desalination system for Solar Desalination System)

  • 황인선;주홍진;윤응상;곽희열
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 춘계학술대회 초록집
    • /
    • pp.201-201
    • /
    • 2010
  • The evaporative desalination system with solar energy would be the efficient and attractive method to get fresh water. This study was described the development of Multi Effect Distillation(MED) with solar energy desalination system. The system was designed and manufactured Multi effect distillation on the capacity of $3m^3$/day. The experimental apparatus consists mainly of ejector pump, Hot water pump, flow meter, demister, cooler, evaporator and condenser. Evaporator and condenser were made Shell&Tube Heat Exchanger type with corrugated tube. The experimental variables were chosen $75^{\circ}C$ for hot water inlet temperature, 40, 60 and $80{\ell}$/min for hot water inlet volume flow rate, 6.0 and $8.0{\ell}$/min for evaporator feed seawater flow rate, $18^{\circ}C$ for sea water inlet temperature to cover the average sea water temperature and the salinity of sea water is measured about 33,000 PPM (parts per million). for a year in Korea. This study was analyzed the results of thermal performance of Multi Effect Distillation. The results are as follows, The experimental Multi effect distillation is required about 40 kW heat source for production of $3m^3$/day fresh water. Various operating flow rate was confirm in the experiments to get the optimum design data and the results showed that the optimum total flow was $8.0{\ell}$/min. Comparison of Single Effect Distillation with Multi Effect Distillation showed MED is at least more than double of SED.

  • PDF

프로필렌 냉매의 응축열전달 특성에 관한 실험적 연구 (Condensing Heat Transfer Characteristics of Propylene Refrigerant)

  • 이호생;김재돌;윤정인
    • 설비공학논문집
    • /
    • 제16권7호
    • /
    • pp.639-644
    • /
    • 2004
  • This paper deals with the heat transfer characteristics of R-1270 (Propylene), R-600a (Iso-butane) and R-290 (Propane) as an environment friendly refrigerant and R-22 for condensing. The experimental apparatus has been set-up as a conventional vapor compression type heat pump system. The test section is a horizontal double pipe heat exchanger. A tube diameter of 12.70 mm with 1.32 mm wall thickness is used for this investigation. The test results showed that the local condensing heat transfer coefficients of hydrocarbon refrigerants were higher than that of R-22. The average condensing heat transfer coefficient was obtained with the maximum value in R-1270 and the minimum one in R-22. Comparing the heat transfer coefficient of experimental results with that of other correlations, the presented results had a good agreement with the Cavallini-Zecchin's correlation. It reveals that the natural refrigerants can be used as substitute for R-22.