Pressure Drop Characteristics of Supercritical $CO_2$ in a Helically Coiled Tube

헬리컬 코일관 내 초임계 $CO_2$의 압력강하 특성

  • 유태근 (부경대학교 냉동공조공학과) ;
  • 김대희 (부경대학교 냉동공조공학과) ;
  • 노건상 (동명대학교 가스냉동과) ;
  • 구학근 (동명대학교 가스냉동과) ;
  • 오후규 (부경대학교 냉동공조공학과)
  • Published : 2005.06.26

Abstract

The heat transfer coefficient and pressure drop during gas cooling process of carbon dioxide in a helically coiled tube were investigated experimentally. The experiments were conducted without oil in the refrigerant loop. The main components of the refrigerant loop are a receiver, a variable speed pump, a mass flowmeter, a pre-heater, a gas cooler(test section) and an isothermal tank. The test section is a double pipe type heat exchanger with refrigerant flowing in the inner tube and water flowing in the annulus. It was made of a copper tube with the inner diameter of 4.85 [mm], the outer diameter of 6.35 [mm] and length of 10000 [mm]. The refrigerant mass fluxes were 200${\sim}$600 [kg/$m^2$s] and the average pressure varied from 7.5 [MPa] to 10.0 [MPa]. The main results were summarized as follows: The heat transfer coefficient of supercritical $CO_2$ increases, as the cooling pressure of gas cooler decreases. And the heat transfer coefficient increases with the increase of the refrigerant mass flux. The pressure drop decreases in increase of the gas cooler pressure and increases with increase the refrigerant mass flux.

Keywords