Browse > Article
http://dx.doi.org/10.5855/ENERGY.2011.20.1.030

Characteristic Analysis of the Cooling System Using Ice Slurry Type Heat Storage System  

Lee, Dong-Won (Korea Institute of Energy Research)
Kim, Jeong-Bae (Department of Energy System Engineering, ChungJu National University)
Publication Information
Abstract
To clarify the hydraulic and thermal characteristics of ice slurry which made from 6.5% ethylene glycol-water solution flow in the double tube and plate type heat exchanger, experimental studies were performed. The mass flux and ice fraction of ice slurry were varied from 800 to 3500 kg/$m^2s$(or 7 to 17 kg/min) and from 0 to 25%, respectively. Through the experiment, it was found that the measured pressure drop and heat transfer rate increase with the mass flux and ice fraction; however the effect of ice fraction appears not to be significant at high mass flux region. At the region of low mass flux, a sharp increase in the pressure drop and heat transfer rate were observed depends on mass flux.
Keywords
Ice slurry; Direct transportation; Heat exchanger; Heat transfer rate; Pressure drop;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Lee, D. W. at al., 2002, Experimental study on heat transfer characteristics of ice slurry direct transportation loop, Proceedings of the SAREK 2002 Summer Annual Conference, pp. 358-363.
2 V. Ayel at al., 2003, Rheology, flow behaviour and heat transfer of ice slurries: a review of the state of the art, Int. J. of Refrigeration, Vol. 26, pp. 95-107.   DOI
3 Lee, D. W., 2002, The application technology of ice slurry, 2002 Seminar of Cold Energy Storage Technology, Vol. 2.
4 Lee, D. W., Jang, H. W., Im, H. M. and Yun, D. W, 2002, Proceedings of the SAREK, pp. 359-363.