• Title/Summary/Keyword: Discharges

Search Result 1,134, Processing Time 0.035 seconds

Characteristics of the plume formed by the buoyant discharges from the river

  • Kim, Ki-Cheol;Kim, Sung-Bo
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.38 no.8
    • /
    • pp.981-994
    • /
    • 2014
  • Density currents formed by buoyancy discharges from rivers are numerically studied using non-dimensional two layer model including Coriolis acceleration, bottom stress, interfacial friction. Some typical numbers such as Froude number, densimetric Froude number and Kelvin number are obtained and some characteristic scales are defined as a result of non-dimensionalization of the governing equations. Besides the Coriolis effect, the configurations of bottom topography, bottom friction coefficient and interfacial friction are found to significantly affect the propagation of the warm water plume. Frontal position can fastly propagate in the case of large density difference between the two layers and small interfacial friction. Left side boundary current is easily formed under the small interfacial friction. With large Kelvin number, both right and left side boundary currents are formed. Wave-like disturbances and eddies are easily formed under the high Froude number.

A Study on the measurement and Method of Partial Discharge in High Voltage CV Cable (고압 CV 케이블에서의 부분방전 측정과 위치검출 방법에 관한 연구)

  • Song Jae-Yong;Seo Hwang-Dong;Park Dae-Won;Kil Gyung-Suk;Han Moon-Sup;Jang Dong-Wook
    • Proceedings of the KSR Conference
    • /
    • 2005.05a
    • /
    • pp.867-872
    • /
    • 2005
  • This paper describes the measurement and location method of partial discharges in high voltage CV cables. Coupling capacitors were used to detect partial discharge signal. Impedance characteristic of the coupling circuit and an amplifier with a high Common Mode Rejection Ratio(CMRR) were studied to improve sensitivity of the circuit. From the calibration experiment, the sensitivity of the partial discharge detection circuit was about 100pC. Also, we confirmed that the location of partial discharges in cables can be estimated by calculation of time difference between the first pulse and the second one reflected from the other end of the cable.

Diagnostic Technique of a Switchboard by Frequency Analysis of Radiated Electromagnetic Wave (방사전자파의 주파수분석에 의한 배전반 진단기술)

  • Park, Dae-Won;Kim, Sun-Jae;Jung, Kwang-Seok;Kil, Gyung-Suk;Jo, Eun-Je
    • Proceedings of the KSR Conference
    • /
    • 2010.06a
    • /
    • pp.41-45
    • /
    • 2010
  • In this paper, we analyzed the frequency spectrum of radiated electromagnetic waves generated by series arc- and corona- discharges as a basic study to develop an online diagnostic technique for power facilities installed inside switchboards. To simulate corona and series arc discharges, an arc generator specified in UL1699 and a corona generator were fabricated. The experiment was carried out in an electromagnetic shielding room, and the measurement system consists of an Ultra Log Antenna and an EMI Test Receiver. The frequency spectrum exists in ranges from 30 to 500 [MHz] for series arc discharge and 30 [MHz] to 2 [GHz] depending on defects for corona discharge. The peak frequency of series arc discharge and corona were 40 [MHz], 80 [MHz] and 35 [MHz]~160 [MHz], respectively.

  • PDF

Ultrasonic detection properties for partial discharge at the premolded joint of a 23kV cable (23kV급 조립형 케이블 접속재에서 부분방전 신호의 초음파 검출특성)

  • Lee, Woo-Young;Ryoo, Hee-Suk;Sun, Jong-Ho;Kim, Sang-Jun;Song, Il-Gun;Kim, Joo-Yong
    • Proceedings of the KIEE Conference
    • /
    • 1996.07c
    • /
    • pp.1907-1909
    • /
    • 1996
  • In this paper, ultrsonic detection properties at a premolde joint utilized in a 23kV cables are studied. In a experiment a artificial defect within a joint and a measuring system are builded for generating discharges, gathering data about a detection properties, respectively. The experiment results show that one point detection is not allowed for monitoring a global status of a joint discharges and a detection sensitivity is less than 100pC. And also the attenuation and wave speed at the material of joint insulator are obtained.

  • PDF

A Study on the Minimnum Ignition Limit for LPG-Air Mixtures by Switching Sparks in Radio-frequency Circuits (고주파 전기회로의 개폐불꽃에 의한 LPG-공기 혼합가스의 점화한계에 관한 연구)

  • Jee, S.W.;Song, H.J.;Lee, C.H.;Park, W.Z.;Lee, K.S.;Lee, D.I.
    • Proceedings of the KIEE Conference
    • /
    • 1996.07c
    • /
    • pp.1854-1856
    • /
    • 1996
  • This study describes the minimum ignition limit for LPG-Ai-r mixtures by switching sparks in radio-frequency limits using RF power supply and IEC type ignition spark apparatus. As a result, the minimum ignition limit voltage is increased in proportional to the rate of increasing of frequency in LPG-Air mixed gas. Especially, increment between 10[kHz] and 30[kHz] is typical. It is considered that ignition is caused by one discharge until 10 [kHz] and, beyond 10[kHz] ignition is caused by more than two discharges. The reason is analysed that energy loss is caused by existing pause interval between discharges.

  • PDF

The Analysis of Partial Discharges Pattern using Discrete Wavelet Transform (이산 웨이브렛변환에 의한 부분방전패턴 분석)

  • 이현동;김충년;지승욱;박광서;이광식;이동인
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.183-187
    • /
    • 2000
  • This paper deals with multiresolution analysis of wavelet transform for partial discharge(PD), both corona and surface discharge. Multiresolution analysis was used for performing discrete wavelet transform. PD signals was decomposed into "approximation" and "detail" components until 4 levels by using discrete wavelet analysis. In this paper, daubechies family is adopted for the research of the characteristics of PD signals. The results show that in corona discharge the segment 7, 8, 9, 10, 11 values of defined variable is increased with discharge process, so phase distribution is characterized by 210~330 ranges. In case surface discharge in expoxy insulator inserted, defined variable values is fairly symmetric discharge pattern because coupled both corona and dielectric bounded discharges. We can confirmly discriminate the type PD source. the type PD source.

  • PDF

Frequency Spectra of AC Signal Generated from the Operation of Cast-Resin Power Transformer (운전중인 몰드형 전력변압기의 음향방출신호에 대한 주파수 스펙트럼 특성)

  • 구경철;이상우;이동인;이광식;김인식;김이국;신용철
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.246-250
    • /
    • 2000
  • In this paper, Frequency spectra of AE(acoustic emission) signals generated from the magnetizing and the load currents in the actual operating cast-resin power transformer of 500[kVA] under distribution system of22.9[kV] were also analysed to distinguish the AE signals due to void discharges from the magnetic circuit noises in the core of cast-resin power transformer. As the experimental results, we could distinguish the AE signals whether those signals were caused due to the void discharges or due to the magnetic circuit noises by analyzing the frequency spectrum of AE signals. Frequency spectra of AE signals generated from the cast-resin power transformer in operation due to both the magnetizing and the load currents appeared in the range of 40-120[khz].

  • PDF

Internal PD Pulses Analysis Accompanying with Bush-type Tree in Solid Dielectrics (고체유전체에서 발생한 부시형 전기트리에 수반된 내부 부분방전 펄스 해석)

  • 강성화;홍현문;류부형
    • Journal of the Korean Society of Safety
    • /
    • v.15 no.1
    • /
    • pp.100-105
    • /
    • 2000
  • Correlation between propagation of bush-type electrical tree and internal partial discharges(PD) was discussed. We used specimens with needle-plane electrode system made of LDPE(Low Density Polyethylene), observed inception and propagation of electrical tree by optical microscope interfaced with computer and investigated characteristics of phase resolved PD pulses accompanying with propagation of electrical tree. Electrical tree generally growed bush-type tree. PD data detected and analyzed were average discharge current and statistical operator of q-n, $\psi$- $q_{avg}$, $\psi$-n, ${\psi}-q_{max}$ distribution. Parameters used were skewness, kurtosis, average discharge phase, cross-correlation factor, asymmetry and etc. In generally, average discharge current had good linear relationship with propagation of bush type electrical tree on this experiment. Peak discharge magnitude and repetition rate were increased, but they had not good linear relationship.p.

  • PDF

Damage and Failure Characteristics of Semiconductor Devices by ESD (ESD에 의한 반도체소자의 손상특성)

  • 김두현;김상렬
    • Journal of the Korean Society of Safety
    • /
    • v.15 no.4
    • /
    • pp.62-68
    • /
    • 2000
  • Static electricity in electronics manufacturing plants causes the economic loss, yet it is one of the least understood and least recognized effects haunting the industry today. Today's challenge in semiconductor devices is to achieve greater functional density pattern and to miniaturize electronic systems of being more fragile by electrostatic discharges(ESD) phenomena. As the use of automatic handling equipment for static-sensitive semiconductor components is rapidly increased, most manufacturers need to be more alert to the problem of ESD. One of the most common causes of electrostatic damage is the direct transfer of electrostatic charge from the human body or a charged material to the static-sensitive devices. To evaluate the ESD hazards by charged human body and devices, in this paper, characteristics of electrostatic attenuation in domestic semiconductor devices is investigated and the voltage to cause electronic component failures is investigated by field-induced charged device model(FCDM) tester. The FCDM simulator provides a fast and inexpensive test that faithfully represents ESD hazards in plants. Also the results obtained in this paper can be used for the prevention of semiconductor failure from ESD hazards.

  • PDF

Location and Frequency Domain Detection of Corona Discharge Point in Oil Using AE Sensor (AE센서를 이용한 유중 코로나방전점 위치 및 주파수 영역 검출)

  • 이상우;김성훈;김인식;김기채;박원주;이광식;이동인
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 1999.11a
    • /
    • pp.127-131
    • /
    • 1999
  • In this paper, using a wide-band AE sensor with the frequency range from 100[kHz], the frequency spectra of AE signals generated from the corona discharges of the needle-plane electrode was analyzed to determine the proper ultrasonic sensor. We also examined the relationship between the magnitude of corona discharge and the magnitude of AE signals in peak-to-peak value under the application of 60[Hz] AC high-voltage in oil. From these results, the main frequency spectra of AE signals emitted from the corona discharges of the needle-plane gap were found to be 130[kHz] by the fast fourier transform. The magnitude of AE signals was proportional to the magnitude of corona discharge and discharge current pulse with increasing the applied voltages. Also the detection of corona discharge point location by AE signals was found to be possible by using two sensors.

  • PDF