• Title/Summary/Keyword: DOA(dedicated outdoor air)

Search Result 5, Processing Time 0.017 seconds

The Performance Analysis and On-site Performance Test of a Dedicated Outdoor Air System (외기 전용 공조기의 성능 분석 및 현장 성능시험)

  • Kim, Young-Il;Kim, Jung-Min;Chung, Kwang-Seop;Park, Seung-Tae
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.346-351
    • /
    • 2007
  • Dedicated outdoor air(DOA) system which conditions the outdoor air separately is superior to conventional cooling+reheating system with respect to energy consumption and indoor comfort. Since the sensible and latent load characteristics of indoor and outdoor are different, it is more efficient to treat them separately. In this study, cycle analysis and on-site performance test of DOA system have been conducted. The study shows that DOA requires 48.8% less equivalent energy that conventional system. The on-site performance test of the prototype shows that the coefficient of performance(COP) of the DOA system is 37.4% higher than the conventional system.

  • PDF

Operation Cost Comparison of Dedicated Outdoor and Cooling + reheating Air-conditioning Systems by On-site Performance Test (현장성능시험에 의한 외기전용과 냉각식 + 재열 공조기의 운전비 비교)

  • Kim, Young-Il;Kim, Jung-Min;Chung, Kwang-Seop;Park, Seung-Tae
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.7 no.2
    • /
    • pp.37-42
    • /
    • 2011
  • Dedicated outdoor air(DOA) system which conditions the outdoor air separately is superior to conventional Cooling + reheating system with respect to energy consumption and indoor comfort. Since the sensible and latent load characteristics of indoor and outdoor are different, it is more efficient to treat them separately. In this study, cycle analysis and on-site performance test of DOA system have been conducted. The study shows that DOA requires 50% less equivalent energy than the conventional system. The on-site performance test of a prototype shows that the coefficient of performance(COP) of the DOA system is 37% higher than the conventional system.

Dynamic Simulation of a Dedicated Outdoor Air-conditioning System (외기 전용 공조기의 동특성 시뮬레이션)

  • Kim, Jung-Min;Kim, Young-Il;Chung, Kwang-Seop;Park, Seung-Tae
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.322-327
    • /
    • 2007
  • Dedicated outdoor air-conditioning(DOA) system that utilizes pre-cooling and desiccant dehumidification can be superior to conventional cooling and reheating system with respect to energy consumption and indoor thermal comfort. In this work, simulation has been conducted to study various factors that affect the performance of DOA. Dynamic simulation shows the transient variation of temperature and humidity as the on/off control logic is imposed. Exit humidity of process air and flow rate are varied to study the effect on exit temperature of process air, dehumidification quantity, required regeneration temperature and exit humidity of regeneration air. For an outdoor air condition of $28.5^{\circ}C$ temperature, 16 g/kg humidity ratio and 2000 cmh flow rate, the dehumidification efficiency is increased by 4.6% as the flow rate is doubled.

  • PDF

An Experimental Study on Four-season Dedicated Outdoor Air Handling Unit (사계절 외기 전용 공조기에 대한 실험적 연구)

  • Park, Seung-Tae;Kim, Jong-Cheon;Hong, Young-Ju;Kim, Youn-Gil
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.577-582
    • /
    • 2008
  • The present study has been conducted to study the performance of Dedicated outdoor air handling unit. Dedicated outdoor air handling unit consists of pre-cooler, dehumidification and after cooler. By combining dedicated outdoor air-conditioning and heat pump, a new four-season dedicated outdoor air handling unit has been developed. Amount of energy saved and condition when this new system is superior to conventional vapor-compression cooling system has been presented.

  • PDF

Evaluation on the Indoor Thermal Environment and Cooling Operation Characteristics of Thermally Activated Building System integrated with Dedicated Outdoor Air System during Cooling Operation in Hot and Humid Climate of Seoul (국내 여름철 기후조건에서 DOAS와 TABS 통합시스템 냉방운전시 실내온열환경 및 운전특성 평가)

  • Lee, YoonSun;Lee, Keo-Re;Chung, Woong June;Lim, Jae-Han
    • Journal of the Architectural Institute of Korea Planning & Design
    • /
    • v.34 no.11
    • /
    • pp.45-55
    • /
    • 2018
  • To reduce the energy consumption of HVAC system in buildings, thermally activated building system(TABS) has been applied to low energy building because of energy efficient performance and reduction of peak load. DOAS coupled with a parallel sensible cooling could be promising because TABS handles sensible heat load only. The purpose of this study was to evaluate the indoor thermal environment and cooling operation characteristic of TABS with dedicated outdoor air system(DOAS) in Korea climate. Indoor thermal environment and operation characteristic of TABS integrated with DOAS are investigated at different TABS operation schedules and climate conditions by simulation tests. The result shows that the DOAS is more suitable for hot and humid climates. And also it show that the potential of intermittent operation of TABS.