Dynamic Simulation of a Dedicated Outdoor Air-conditioning System

외기 전용 공조기의 동특성 시뮬레이션

  • 김정민 (서울산업대학교 주택환경대학원) ;
  • 김영일 (서울산업대학교 건축학부) ;
  • 정광섭 (서울산업대학교 건축학부) ;
  • 박승태 ((주)에이티이엔지)
  • Published : 2007.11.30

Abstract

Dedicated outdoor air-conditioning(DOA) system that utilizes pre-cooling and desiccant dehumidification can be superior to conventional cooling and reheating system with respect to energy consumption and indoor thermal comfort. In this work, simulation has been conducted to study various factors that affect the performance of DOA. Dynamic simulation shows the transient variation of temperature and humidity as the on/off control logic is imposed. Exit humidity of process air and flow rate are varied to study the effect on exit temperature of process air, dehumidification quantity, required regeneration temperature and exit humidity of regeneration air. For an outdoor air condition of $28.5^{\circ}C$ temperature, 16 g/kg humidity ratio and 2000 cmh flow rate, the dehumidification efficiency is increased by 4.6% as the flow rate is doubled.

Keywords