The Performance Analysis and On-site Performance Test of a Dedicated Outdoor Air System

외기 전용 공조기의 성능 분석 및 현장 성능시험

  • Kim, Young-Il (School of Architecture, Seoul National University of Technology) ;
  • Kim, Jung-Min (Graduate School of Housing, Seoul National University of Technology) ;
  • Chung, Kwang-Seop (School of Architecture, Seoul National University of Technology) ;
  • Park, Seung-Tae (Air-Tech Engineering Co. Ltd.)
  • Published : 2007.11.30

Abstract

Dedicated outdoor air(DOA) system which conditions the outdoor air separately is superior to conventional cooling+reheating system with respect to energy consumption and indoor comfort. Since the sensible and latent load characteristics of indoor and outdoor are different, it is more efficient to treat them separately. In this study, cycle analysis and on-site performance test of DOA system have been conducted. The study shows that DOA requires 48.8% less equivalent energy that conventional system. The on-site performance test of the prototype shows that the coefficient of performance(COP) of the DOA system is 37.4% higher than the conventional system.

Keywords