Operation Cost Comparison of Dedicated Outdoor and Cooling + reheating Air-conditioning Systems by On-site Performance Test  

Kim, Young-Il (School of Architecture, Seoul National University of Science and Technology)
Kim, Jung-Min (Graduate School of Housing, Seoul National University of Science and Technology)
Chung, Kwang-Seop (School of Architecture, Seoul National University of Science and Technology)
Park, Seung-Tae (Air-Tech Engineering Co. Ltd.)
Publication Information
Journal of the Korean Society for Geothermal and Hydrothermal Energy / v.7, no.2, 2011 , pp. 37-42 More about this Journal
Abstract
Dedicated outdoor air(DOA) system which conditions the outdoor air separately is superior to conventional Cooling + reheating system with respect to energy consumption and indoor comfort. Since the sensible and latent load characteristics of indoor and outdoor are different, it is more efficient to treat them separately. In this study, cycle analysis and on-site performance test of DOA system have been conducted. The study shows that DOA requires 50% less equivalent energy than the conventional system. The on-site performance test of a prototype shows that the coefficient of performance(COP) of the DOA system is 37% higher than the conventional system.
Keywords
DOA(dedicated outdoor air); Performance analysis; On-site performance test; COP(Coefficient of performance); Cooling; Ventilation;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Krakow, K I., Lin, S., Zeng, Z. -S., 1995, Temperature and Humidity Control during Cooling and Dehumidifying by Compressor and Evaporator Fan Speed Variation, ASHRAE Trans. Part 1, pp. 292-304.
2 Morris, W., 2003, The ABCs of Dedicated Outdoor Air Systems, ASHRAE Journal, May, pp. 24-29.
3 Mumma, S. A, 2001, Designing Dedicated Outdoor Air Systems, ASHRAE Journal, May, pp. 28-31.
4 Murphy, J. 2006, Smart Dedicated Outdoor Air Systems, ASHRAE Journal,July,pp. 30-37.