• 제목/요약/키워드: Cable Aging

검색결과 126건 처리시간 0.032초

XLPE 케이블 절연체에서의 가지형 전기트리 성장에 따른 부분방전 위상 특성 연구 (A Study on the Partial Discharge Phase Properties with Branch Type Eleotrical Tree Growth in XLPE Cable Insulation)

  • 강동식;선종호;김위영;이홍식;박정후
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제51권5호
    • /
    • pp.213-221
    • /
    • 2002
  • In order to improve the reliability of XLPE cables, it is necessary to find the useful diagnostic parameter according to long term aging. This paper described the change of partial discharge(PD) phase Properties of XLPE cable insulation with branch type electrical tree degradation. for long term aging. To understand the PD Properties with $\phi$ -q-n distributed shape of XLPE insulation, specimens were prepared by 22.9㎸ distribution cable and made in a type of block(16${\times}$16${\times}$3[mm]). Ogura needles having tip radius of l0${\mu}{\textrm}{m}$ were inserted into each block pieces. The measuring system was consisted of PD detector, digitizer for digital conversion, VXI system for signal processing. The PD properties of the specimens were measured from initiation of tree to breakdown and their characteristics were analyzed. We analyzed the relationship between electrical properties(PD Quantity, PD initiation angle, PD extinction angle, PD occurrence angle : (PD extinction angle - PD initiation angle)) and the normalized aging rate. We found PD parameter, PD initiation angle and occurrence angle, which are a useful diagnostic parameter in estimating the branch type electrical tree for XLPE insulation condition.

지중송전계통에서 OF 및 XLPE 케이블 혼용 연계 운용의 효용성 평가 (Effectiveness Evaluation on Combined Connection Operation of OF and XLPE Cable)

  • 채직병;이종범
    • 전기학회논문지
    • /
    • 제64권6호
    • /
    • pp.857-863
    • /
    • 2015
  • OF cable with excellent reliability and economic efficiency, has been used as the main cable of underground transmission in Korea. However, as XLPE cable is excellent in view points such as reduction of loss, convenience on the construction/operation, and manufacturing technology, it has been replaced as instead of OF cable. Also, when the aging occurs in some sections of OF cable, the section is replaced as XLPE cable without changing of whole cable line. However, there are some differences like electrical constants between both types of cables. Therefore if underground transmission system will be operated as combined connection composited of both cables, it should be proved that overvoltage is stable in steady and transient state. This paper describes the effectiveness of connection operation in combined OF and XLPE cable. For the evaluation of effectiveness, some important analysis such as sheath component voltage, lightning and switching overvoltage, single line-to-ground fault are carried out in steady and transient state. EMTP/ATPDraw is used for modeling and analysis of system.

초고압 전력 케이블 절연층의 Flow Pattern 방향각에 따른 전기 트리 개시 특성 비교 (Comparison of Electrical Tree Initiation According to Flow Pattern in EHV Power Cable Insulation)

  • 이승엽;김영호;조대희;이인호;박완기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 D
    • /
    • pp.1532-1534
    • /
    • 1999
  • Electrical treeing phenomenon, regarded as pre-breakdown which accelerates aging process leading an insulation to the complete breakdown, is with no doubt extremely fatal to the performance of the insulation. Investigated in this paper is electrical treeing representing local dielectric failure according to flow pattern, the flow history of liquid polyethylene formed during the extrusion process. Experiments of electrical tree initiation by means of ramp tests were conducted using newly developed electrode system with point-to-point structure. Constant voltage tests were also carried out with the electrode system to estimate the life time of the insulation. Results were analyzed using statistical method such as Weibull distribution.

  • PDF

자동차용 모바일 폰 충전 케이블의 발화 안전성에 관한 연구 (A Study on safety against a fire of charging cable for mobile phone for vehicle)

  • 권진욱;최규식;황명환
    • 대한안전경영과학회지
    • /
    • 제20권3호
    • /
    • pp.21-26
    • /
    • 2018
  • This paper describes result of a study on safety against a fire of charging cable for mobile phone for vehicle. Combustion on the USB cable in the car was happened while driving. Gas coming from the burning USB cable could be a reason which can make a secondary car accident since the driver also can be embarrassed while driving. In order to prevent a secondary car accident connected on the road, to research a reason why USB cable can emit gas and be burned in charging. We did simulation test with abnormal fault condition for the electronic component on the board in the USB cable. So we get the result from abnormal fault condition simulation test, for instance, shorted test for output terminal of 8 pin switch, shorted test for chip resistor after thermal aging in the condition $25^{\circ}C$, 93 % RH during 48 hours. To analysis the result of all test, Combustion on the USB cable was not the 8 pin but other electrical component such as a chip resistor. Therefore we guess that the reason for USB cable combustion in charging in a car was not 8 pin and a LED but another defective component.

파괴 및 비파괴진단 비교분석을 통한 케이블 열화특성평가 (Insulation Aging Characteristic Assessment on the Power cables with the Comparative Analysis Between Destructive and Nondestructive Diagnosis)

  • 이동영
    • 조명전기설비학회논문지
    • /
    • 제23권6호
    • /
    • pp.104-108
    • /
    • 2009
  • 본 논문에서는 지중전력케이블을 대상으로 케이블의 절연열화특성 분석시험을 통해 케이블의 절연열화와 절연 진단결과 및 파괴강도와의 상관관계에 대한 실증연구를 수행하였다. 시험대상 선로의 제조결함 여부를 확인하기 위해 가교도분석, 핫오일테스트 등을 실시한 결과 제조결함은 없는 것으로 확인되었다. 진단대상 선로는 3상 모두 장기간 사용에 의해 열화가 많이 진전되었고, 특히 B상이 수트리 길이 및 화학구조결함 농도 면에서 가장 열화된 케이블인 것으로 판단되며, C상, A상의 순으로 열화정도가 다소 감소함을 확인하였다. 상기 결과는 진단시험 및 파괴 강도시험 결과와 일치하며, 따라서 열화시정수법을 이용한 진단장치가 열화상태가 심각한 케이블의 선별에 효과적인 진단법임을 확인하였다.