• Title/Summary/Keyword: Cable Aging

Search Result 126, Processing Time 0.026 seconds

Lightning Impulse Characteristics for 22.9 kV CV Power Cable Before and After Cyclic Aging for 14days (22.9 kV CV 전력케이블의 14주기 고온 열화에 대한 Lightning-Impulse 특성)

  • Kim, We-Young;Yun, Dae-Hyuk;Park, Tae-Gone
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1549-1551
    • /
    • 2001
  • Cyclic aging for 14 days is performed to remove a large amount of the volatiles found in freshly manufactured cable. In this paper, we examined lightning impulse characteristics of 22.9 kV CV power cable before and after cyclic aging for 14days. As the result, the breakdown voltage after aging under normal temperature was lower than that before aging, and the breakdown voltage after aging under hot temperature was lower than that before aging. We found that the dispersion of lightning impulse breakdown voltage before 14 cyclic aging test were reduced rather than those after 14 cyclic aging test.

  • PDF

The Analysis of Weibull Distribution after an Accelerated Aging Test of MV Cable (차수형 케이블의 수트리 가속실험후 와이블분포 해석)

  • Kim, Jin-Gook;Lim, Jang-Seob;Song, Il-Keun;Lee, Jae-Bong
    • Proceedings of the KIEE Conference
    • /
    • 2003.10a
    • /
    • pp.178-181
    • /
    • 2003
  • For many years, testing laboratories, research institutes and manufactures try to find a reliable water tree accelerated ageing test that is able to show whether a polymer Medium Voltage cable os susceptible to water treeing or not. Test on laboratory samples, model cable designs, and fell size cable are presented Apart form aging, another important aspect of any accelerated aging test is the right choice of th preconditioning method. This paper is the analysis of weibull distribution method after an accelerated aging test of MV(Medium Voltage) cable.

  • PDF

Insulation Diagnostics and Maintenance of Submarine Medium Voltage Power Cable Systems (해저 케이블 시스템의 열화진단 및 유지보수)

  • 이동영
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.3
    • /
    • pp.80-86
    • /
    • 2003
  • A study on the insulation aging assessment and maintenance for submarine medium voltage power cable systems has been performed The purpose of this work is the economic discrimination and maintenance of bad cables which is likely to cause cable system failure. 1 have found that aging status of submarine cable systems are very poor and in progress. Therefore, we have the replacement of cable terminations and repeat the diagnostic measurement Insulation status were improved with the replacement of cable terminations. I have confirmed, with the electrical md structural analysis of terminations, that the poor aging status of cables are mainly caused not by the cable insulations but by the aging of cable terminations. From the above results, I have also confirmed that the domestic diagnostic system is successful and convenient for the discrimination and maintenance of the damaged cables economically.

Combustion Characteristics Analysis of a Non-class 1E Cable for Nuclear Power Plants according to Aging Period (경년열화 기간에 따른 원자력발전소용 비안전등급 케이블의 연소특성 분석)

  • Kim, Min Ho;Lee, Seok Hui;Lee, Min Chul;Lee, Sang Kyu;Lee, Ju Eun
    • Journal of the Korean Society of Safety
    • /
    • v.35 no.5
    • /
    • pp.22-29
    • /
    • 2020
  • In this study, combustion and smoke release characteristics of a non-class 1E cable for nuclear power plants were investigated according to aging period. The aging was reproduced through an accelerated aging method for interval of 10 years :10, 20, 30 and 40 year, which was applied the Arrhenius equation. The cable was subjected to accelerated aging. In order to understand combustion and smoke release characteristics, the cone calorimeter test was performed according to the standard code of KS F ISO 5660-1. Heat release rate, mass loss rate, average rate of heat emission and smoke production rate were examined through cone calorimeter test. Fire performance index, fire growth index and smoke factor were derived from test results for the comparison of quantitative fire risk. When comparing the fire performance index and the fire growth index, the early fire risk tends to decrease as aging progresses, which might be attributed from the fact that the volatile substances of cables were evaporated. However, when comparing the heat release rate, average rate of heat emission and mass loss rate, which represent the mid and late periods of the fire risk, the values of accelerated aging cables were much higher than those of non-aged cable, which signifies the unstable formation of the char layer resulted in the change in the performance of flame retardants. In addition, the results from the smoke characteristics show that the accelerated aging cables were lager than the non-aged cables in terms of overall fire risk. These results can be used as baseline data when assessing fire risk of cables and establishing fire safety code for nuclear power plants.

AC Breakdown Voltage Characteristics for 22.9kV Power Cable Before and After Cyclic Aging for 14days (14주기 열화에 따른 22.9kV 전력케이블의 교류파괴전압 특성분석)

  • Kim, We-Young;Heo, Jong-Cheol;Park, Tae-Gone
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2271-2273
    • /
    • 2005
  • The cyclic aging for 14days is performed in order to remove the large amount of the volatiles contained in freshly manufactured cable. And the accelerated water treeing test(AWTT) is performed to accelerate the occurance of the water tree in the dielectric of XLPE. In this paper, we examined the AC breakdown voltage characteristics of the 22.9kV power cable before and after the cyclic aging for 14days and the AWTT. As the result, the AC breakdown voltage of the TR CNCV-W power cable is higher than that of CNCV-W and FR CNCO-W power cable.

  • PDF

Analysis of Influence for High Frequency voltage Accelerated Aging of XLPE Cable (고주파 전압이 XLPE cable의 가속열화에 미치는 영향 분석)

  • Kim, We-Young;Hu, Jong-Chul;Yun, Dae-Hyuk;Park, Tae-Gone
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1670-1672
    • /
    • 2004
  • XLPE compound have used for insulation of 22.9kV power cable. XLPE insulation is aged for use long time in distribution line. The cause of aging is water tree is happening and growth. Accelerated water tree test method are Accelerated volatge aging method and high frequency aging method. In this paper, high frequency accelerated water tree was performed. And the result was analysed AC breakdown voltage and size and number of water trees.

  • PDF

Characteristic Analysis on the Distribution Pattern of Discharge Signals Generated in the Power Cable (전력 케이블에서 발생되는 방전 신호의 분포패턴에 관한 특성 분석)

  • So, Soon-Youl;Hong, Kyung-Jin;Jung, Woo-Seong;Lim, Jang-Seob;Lee, Jin;Lee, Joon-Ung;Kim, Tae-Sung
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.11 no.11
    • /
    • pp.1035-1042
    • /
    • 1998
  • After the 1990's, a computer-aided partial discharge(PD) measurement system was referred in part of aging diagnosis using digital signal processing as the new technology has been studied. The PD patterns and relevant information for pattern recognition are discussed in PD research area, because discharge quantity(q), the number of discharge pulse(n) and the applied boltage phase($\varphi$) was combined with the system information of the aging state. This paper investigates the discharge phase and quantity, as well as the number of discharge(n) with regard to discharge signals generated in power cable. therefore, according to characteristic analysis on the distribution of $\varphi$, q and n, it is able to apply in the aging analysis of power cable which visual observation is impossible and distribution change of discharge signals offers much information for risk degree on aging progress of insulation materials.

  • PDF

A Studies on Aging Properties for Transmission Line Polymer Insulators which are Installed in service (실계통에 포설된 송전용 고분자 애자의 AGING 특성 연구)

  • Kim, So-Yeon;Lee, Sang-Jin;Ha, Young-Kil;Kim, Dong-Wook
    • Proceedings of the KIEE Conference
    • /
    • 2001.11a
    • /
    • pp.152-154
    • /
    • 2001
  • Recently the extensive use of composite insulators for transmission lines can ultimately be justified only on long-term qualification tests. Especially, it is possible for the Polymer insulator to be aged in according to the environment in which it is used this may bring about the decrease of the duration of voltage application. So, this paper deals with aging property of the polymer insulator installed at real transmission line in the industry area. The contact angle, arc test, tracking test were measured for acquiring the degradation characteristics of silicone rubber and the SEM, XRF, FT-IR tests were measured for analyzing the crack and components. Also the surface leakage current of the polymer insulator was compared with that of the porcelain insulator. Finally, we knew that the aging property was not appeared during seven months at real transmission line in the industry area.

  • PDF

Aging Characteristics of Cable Terminations for Distribution Power System (배전용 케이블 종단접속재의 경년특성)

  • Han, Jae-Hong;Lee, Byeong-Seong;Kim, Sang-Jun;Lee, Cheol-Ho;Kim, Sang-Uk;Kim, Yong-Ae
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.8
    • /
    • pp.580-586
    • /
    • 1999
  • Aging characteristics of 13 years service-aged distribution cable terminations which dismounted from 3 regions were investigated by material characterization and electrical test. All dismounted terminations have propagating micro-cracks on the surface of weathershed and chalking fillers from bulk. Elemental analysis of these terminations showed that the carbon was decreased and the oxygen was increased on the surface of weathershed due to a little oxidation reaction. Contact angle of terminations was abnormally increased with time. In the analysis of anti-oxidation ability and chemical structure, there were no differences between new and dismounted terminations. All terminations showed satisfactory results in electrical test. Therefore, itcan be considered that aging is only propagating on the surface of dismounted terminations. Also, it was confirmed that environmental factors such as UV, pollution and salt have an effect on the aging through the observation of polymer composition change.

  • PDF

A Study on the Ultraviolet Aging characteristics of Outdoor Polymeric Insulating Materials (옥외용 고분자 절연재료의 자외선 열화특성 연구)

  • Kim, Y.S.;Lee, S.J.;Park, W.K.;Jeong, S.W.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07d
    • /
    • pp.1404-1406
    • /
    • 1998
  • The outdoor polymeric insulating materials such as silicone rubber, ethylene propylene diene monomer(EPDM), ethylene vinyl acetate(EVA) and epoxy are aged by various natural environment with the long-term performance in outdoor. In this paper, the effects of UV-ray on surface of silicone rubber were investigated by using the weather-Ometer. The accelerated aging stresses were simulated by UV radiation. high temperature and humidity as well as water spray. These the aging characteristics were examined through contact angle measurements, tracking resistance test, FT-IR and SEM/EDS analysis. the experimental results showed that tracking resistance decreases with increase in the UV-ray irradiation period. But the surface of silicone rubber kept hydrophobicity. It is found that the inorganic filler such as $Al(OH)_3$ improves tracking resistance and the $TiO_2$ is very effective in preventing degradation of silicone rubber surface from UV-ray.

  • PDF