AC Breakdown Voltage Characteristics for 22.9kV Power Cable Before and After Cyclic Aging for 14days

14주기 열화에 따른 22.9kV 전력케이블의 교류파괴전압 특성분석

  • 김위영 (한국전기연구원 시험평가본부) ;
  • 허종철 (한국전기연구원 시험평가본부) ;
  • 박태곤 (창원대학교 전기공학과)
  • Published : 2005.07.18

Abstract

The cyclic aging for 14days is performed in order to remove the large amount of the volatiles contained in freshly manufactured cable. And the accelerated water treeing test(AWTT) is performed to accelerate the occurance of the water tree in the dielectric of XLPE. In this paper, we examined the AC breakdown voltage characteristics of the 22.9kV power cable before and after the cyclic aging for 14days and the AWTT. As the result, the AC breakdown voltage of the TR CNCV-W power cable is higher than that of CNCV-W and FR CNCO-W power cable.

Keywords