• Title/Summary/Keyword: Busbar distribution system

Search Result 9, Processing Time 0.03 seconds

Applicability Comparison of Transmission Line Parameter Extraction Methods for Busbar Distribution Systems

  • Hasirci, Zeynep;Cavdar, Ismail Hakki;Ozturk, Mehmet
    • Journal of Electrical Engineering and Technology
    • /
    • v.12 no.2
    • /
    • pp.586-593
    • /
    • 2017
  • Modeling busbar distribution system as a transmission line is an important subject of power line communication in the smart grid concept. This requires extraction of busbar RLGC parameters, accurately. In this study, a comparison is made between conventional and modified method for the aspect of optimum RLGC parameters extraction in the 1 MHz to 50 MHz frequency band. The usefulness of these methods is shown both in time and frequency-domain analysis. The frequency-domain analyzes show that the inherent power of modified method can eliminate the errors especially due to the discontinuities arise in conventional method. This makes the modeling approach of modified method more advantageous for the busbars due to its robustness against disturbances in the S-parameters measurements which cannot be eliminated with the calibration procedure. On the other hand, time-domain simulations show that the transmission line representation of the modified method is closer to physical reality by handling causality issues.

Comparison of the Operational Speed of Hard-wired and IEC 61850 Standard-based Implementations of a Reverse Blocking Protection Scheme

  • Mnguni, Mkhululi Elvis Siyanda;Tzoneva, Raynitchka
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.740-754
    • /
    • 2015
  • This paper focuses on the reverse blocking busbar protection scheme with aim to improve the speed of its operation and at the same time to increase operational reliability, flexibility and stability of the protection during external and internal faults by implementation of the extended functionality provided by the IEC61850 standard-based protective Intelligent Electronic Devices (IEDs). The practical implementation of the scheme by the use of IEC 61850 standard communication protocol is investigated. The proposed scheme is designed for a radial type of a distribution network and is modeled and simulated in the DigSILENT software environment for various faults on the busbar and its outgoing feeders. A laboratory test bench is built using three ABB IEDs 670 series that are compliant with the IEC 61850 standard, CMC 356 Omicron test injection device, PC, MOXA switch, and a DC power supplier. Two types of the reverse blocking signals between the IEDs in the test bench are considered: hard wired and Ethernet communication by using IEC 61850 standard GOOSE messages. Comparative experimental study of the operational trip response speeds of the two implementations for various traffic conditions of the communication network shows that the performance of the protection scheme for the case of Ethernet IEC 61850 standard-based communication is better.

A Design and Implementation of Busbar Joint and Temperature Measurement System (부스바 접촉 상태 및 온도 감지 시스템 설계 및 구현)

  • Lee, Young-dong;Jeong, Sung-Hak
    • Journal of the Korea Institute of Information and Communication Engineering
    • /
    • v.21 no.2
    • /
    • pp.379-385
    • /
    • 2017
  • In general, distribution board, panel board and motor control center can be installed over a wide area such as residence of group, building, schools, factories, ports, airports, water service and sewerage, substation and heavy industries that are used to supply converts the voltages extra high voltage into optimal voltage. There are electrical accidents due to rise of contact temperature, loose contact between busbar, deterioration of the contact resistance, over temperature of the busbars. In this paper, we designed and implemented the busbar joint and temperature measurement system, which can measure the joint resistance of busbar and loose connection between busbar using potentiometer and non-contact infrared sensor. The experimental results show that tightening the bolt and nut is fully engaged, resistance was decreased and maximum error range was 0.1mm. Also, the experimental result showed that the temperature at the contact area is increased from $27.3^{\circ}C$ to $69.3^{\circ}C$by the contact resistance.

Design of Busbar Joint Condition Monitoring System (부스바 접촉부 체결상태 모니터링 시스템 설계)

  • Jeong, Sung-Hak;Lee, Young-Dong
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2016.10a
    • /
    • pp.823-824
    • /
    • 2016
  • In general, distribution board, panel board and motor control center can be installed over a wide area such as residence of group, building, schools, factories, ports, airports, water service and sewerage, substation and heavy industries that are used to supply converts the voltages extra high voltage into optimal voltage. There are electrical accidents due to rise of contact temperature, loose contact of bus bar, deterioration of the contact resistance, overtemperatue of the bus bars. In this paper, we propose bus bar joints monitoring system with loose connection of bus bar, measuring the joint resistance of busbars and monitoring internal and external heat. The proposed system can be reduced the electrical accidents by maintenance of busbar joints and the temperature of the conductive contact surface of busbars.

  • PDF

Bus Reconfiguration Strategy Based on Local Minimum Tree Search for the Event Processing of Automated Distribution Substations

  • Ko Yun-Seok
    • KIEE International Transactions on Power Engineering
    • /
    • v.5A no.2
    • /
    • pp.177-185
    • /
    • 2005
  • This paper proposes an expert system that can enhance the accuracy of real-time bus reconfiguration strategy by adopting the local minimum tree search method and that can minimize the spreading effect of the fault by considering the operating condition when a main transformer fault occurs in an automated substation. The local minimum tree search method is used to expand the best-first search method. This method has the advantage that it can improve the solution performance within the limits of the real-time condition. The inference strategy proposed expert system consists of two stages. The first stage determines the switching candidate set by searching possible switching candidates starting from the main transformer or busbar related to the event. The second stage determines the rational real-time bus reconfiguration strategy based on heuristic rules from the obtained switching candidate set. Also, this paper proposes generalized distribution substation modeling using graph theory, and a substation database based on the study results is designed.

Bus Reconfiguration Strategy Based on Local Minimum Tree Search for the Event Processing of Automated Distribution Substation (자동화된 변전소의 이벤트 발생시 준최적 탐색법에 기반한 모선 재구성 전략의 개발)

  • Ko Yun-Seok
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.10
    • /
    • pp.565-572
    • /
    • 2004
  • This paper proposes an expert system which can enhance the accuracy of real-time bus reconfiguration strategy by adopting local minimum tree search method and minimize the spreading effect of the fault by considering totally the operating condition when a main transformer fault occurs in the automated substation. The local minimum tree search method to expand the best-first search method. This method has an advantage which can improve the performance of solution within the limits of the real-time condition. The inference strategy proposed expert system consists of two stages. The first stage determines the switching candidate set by searching possible switching candidates starting from the main transformer or busbar related to the event. And, second stage determines the rational real-time bus reconfiguration strategy based on heuristic rules for the obtained switching candidate set. Also, this paper studies the generalized distribution substation modelling using graph theory and a substation database is designed based on the study result. The inference engine of the expert system and the substation database is implemented in MFC function of Visual C++. Finally, the performance and effectiveness of the proposed expert system is verified by comparing the best-first search solution and local minimum tree search solution based on diversity event simulations for typical distribution substation.

The Alleviation Countermeasures of Line Overloads Due To a Contingency Occured in Power System (전력계통(電力系統)의 상정(想定)사고(事故)에 따른 선로(線路)의 과부하(過負荷) 해소(解消) 대책(對策))

  • Chung, Jai-Kil;Noh, Sin-Hong;Park, Kyu-Hong
    • Proceedings of the KIEE Conference
    • /
    • 1991.07a
    • /
    • pp.432-436
    • /
    • 1991
  • This paper presents a new algorithm for the countermeasure to alleviate without shedding system loads the line overloads due to contingency in power system. This method for relieving by line switching is based on obtaining the line outage distribution factors - the linear sensitivity factors, which give the amount of change in the power flow of each line due to the removal of same other line in the power system. These factors are made up of the elements of Bus Reactance Matrix and branch reactances. In this paper a fast algorithm and program is presented for obtaining only the required Bus Reactance elements which corresponds to a non - zero elements of Bus Admittance Matrix and elements of columns which correspond to two terminal Buses of the overloaded(monitored) line. The proposed algorithm has been validated in tests on the 6 busbar test system

  • PDF

The Design of Operation and Control Solution with Intelligent Inference Capability for IED based Digital Switchgear Panel (IED를 기반으로 하는 디지털 수배전반의 지적추론기반 운전제어 솔루션 설계)

  • Ko, Yun-Seok
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.9
    • /
    • pp.351-358
    • /
    • 2006
  • In this paper, DSPOCS(Digital Switchgear-Panel Operation and Control Solution) is designed, which is the intelligent inference based operation and control solution to obtain the safety and reliability of electric power supply in substation based on IED. DSPOCS is designed as a scheduled monitoring and control task and a real-time alarm inference task, and is interlinked with BRES(Bus Reconfiguration Expert System) in the required case. The intelligent alarm inference task consists of the alarm knowledge generation part and the real-time pattern matching part. The alarm knowledge generation part generates automatically alarm knowledge from DB saves it in alarm knowledge base. On the other hand, the pattern matching part inferences the real-time event by comparing the real-time event information furnished from IEDs of substation with the patterns of the saved alarm knowledge base.; Especially, alarm knowledge base includes the knowledge patterns related with fault alarm, the overload alarm and the diagnosis alarm. In order to design the database independently in substation structure, busbar is represented as a connectivity node which makes the more generalized graph theory possible. Finally, DSPOCS is implemented in MS Visual $C^{++}$, MFC, the effectiveness and accuracy of the design is verified by simulation study to the typical distribution substation.

Development of An Expert system with Knowledge Learning Capability for Service Restoration of Automated Distribution Substation (고도화된 자동화 변전소의 사고복구 지원을 위한 지식학습능력을 가지는 전문가 시스템의 개발)

  • Ko Yun-Seok;Kang Tae-Gue
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.12
    • /
    • pp.637-644
    • /
    • 2004
  • This paper proposes an expert system with the knowledge learning capability which can enhance the safety and effectiveness of substation operation in the automated substation as well as existing substation by inferring multiple events such as main transformer fault, busbar fault and main transformer work schedule under multiple inference mode and multiple objective mode and by considering totally the switch status and the main transformer operating constraints. Especially inference mode includes the local minimum tree search method and pattern recognition method to enhance the performance of real-time bus reconfiguration strategy. The inference engine of the expert system consists of intuitive inferencing part and logical inferencing part. The intuitive inferencing part offers the control strategy corresponding to the event which is most similar to the real event by searching based on a minimum distance classification method of pattern recognition methods. On the other hand, logical inferencing part makes real-time control strategy using real-time mode(best-first search method) when the intuitive inferencing is failed. Also, it builds up a knowledge base or appends a new knowledge to the knowledge base using pattern learning function. The expert system has main transformer fault, main transformer maintenance work and bus fault processing function. It is implemented as computer language, Visual C++ which has a dynamic programming function for implementing of inference engine and a MFC function for implementing of MMI. Finally, it's accuracy and effectiveness is proved by several event simulation works for a typical substation.