• 제목/요약/키워드: Breakdown cause

검색결과 203건 처리시간 0.033초

절연파괴 사례분석을 통한 진공함침 방식 발전기 고정자권선의 절연특성 연구 (A Study on Insulation Property of VPI Type Generator Stator Winding Through the Case Analysis of Insulation Breakdown)

  • 공태식
    • 전기학회논문지P
    • /
    • 제59권3호
    • /
    • pp.311-316
    • /
    • 2010
  • According to increase of combined cycle power generation, the manufacturing market of gas turbine generator has become more competitive, so there is high pressure on the manufacturer to reduce generator price. Global VPI(vacuum pressure impregnation) method is effective to save the production cost and time for manufacturing stator windings, but it has an abrasion problem by vibration between stator windings and slots. This paper presents the insulation breakdown case, which is for VPI type generator during high voltage insulation tests, and also shows the cause analysis, repair works as well as reliability test. the purpose of this paper is to understand the insulation properties of VPI type generator and to know prevention of insulation weakness.

인버터구동 고압전동기 열화특성 분석 및 필터 설계기법 확립 (Insulation System and Filter Design for Inverter-Fed Motor)

  • 최영찬;이상동;김익모;정명길
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 B
    • /
    • pp.711-713
    • /
    • 2000
  • Recently, the insulation breakdown accident happened at 6.6kV inverter driving motor brings out the reliability decrease to the motor driving system. We need to find the solution with system engineering level. The objectives of this study are developing the appropriate filter for the drive to protect the motor and the insulation system of motor which is driven by inverter. The circuit parameters of cable are calculated by EMTP(Electromagnetic Transient Program) to simulate the system. And we use MATLAB to find the appropriate filter parameter. The simulation and the test results are compared to verify the suitability of the filter parameter. We clarify the cause of the deterioration of the inverter driving motor through the analysis of insulation breakdown accidents. The endurance test scheme and the configuration method of insulation system are established.

  • PDF

수력발전기 고정자권선의 단말부 절연파괴와 절연특성시험과의 관련성 분석 (Analysis of Correlation Endwinding Breakdown and Insulation Test for Stator winding of Hydro-Generator)

  • 이동근;이광호;최교남;김현일;오봉근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 전기설비
    • /
    • pp.103-105
    • /
    • 2005
  • The test were performed to analyze the cause of endwinding breakdown of hydro-generator which had been in service after being constructed 1971. we conducted insulation diagnostic tests and checked visual inspection and operating condition of protective relays. On the basis of these test results, this paper tried to present the importance of service environment for the generator stator winding.

  • PDF

Validation of Some Protection Guidelines for Neighboring Pipelines against Fault Currents from Power Transmission Tower

  • Lee, Seong-Min;Song, Hong-Seok;Kim, Young Geun
    • Corrosion Science and Technology
    • /
    • 제6권2호
    • /
    • pp.77-81
    • /
    • 2007
  • Fault current can be discharged from power transmission tower due to lightning or inadvertent contact of crane, etc. Pipelines in proximity to either the source of the ground fault or the substation grounding grid may provide convenient conductive path for the fault current to travel. Inappropriate measures to the neighboring pipelines against the fault current may cause severe damages to the pipes such as coating breakdown, arc burn, puncture, loss in wall thickness, or brittle heat-affected zone. Like inductive and conductive AC coupling, steadily induced fault current right after the coating breakdown can lead to corrosion of the pipeline. In this work, some protection guidelines against fault currents used in the field have been validated through the simulation and analytical method.

전경 물체 추출 기법을 이용한 전기트리 영상에서 열화 측정 (Degradation Measurement from Electrical Tree Image Using Foreground Object Extracting Skill)

  • 김형균;정기봉;고석만;오무송;김태성
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 추계학술대회 논문집
    • /
    • pp.270-273
    • /
    • 2001
  • Electrical tree is studied widely by manufacture state of insulating material fare and blazing fire diagnosis system of use in phenomenon of part discharge that happen for main cause of dielectric breakdown of equipment for electric power. Use process that draw tree pattern here measuring above zero to study special quality of this electricity tree, real-time processing by image processing is proposed because reproduction of tree blazing fire process drops and pattern of tree is difficult correct quantification of tree growth by existent visual observation by involution. This research presents general process that need in image processing of tree blazing fire, and that remove various noises that happen in above zero by measuring electrical tree dividing background and complete view in measured above zero taking advantage of specially proposed complete view object abstraction techniques effectively and quantification of tree becomes easy naturally, can apply to dielectric breakdown estimate because can chase growth process of tree.

  • PDF

인버터 구동에 따른 고압전동기 사고사례와 대책 (Failure Case-Study and Countermeasures of High-Voltage Motor with Inverter Drive System)

  • 최영찬;우명호
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2002년도 추계학술대회 논문집
    • /
    • pp.163-166
    • /
    • 2002
  • Recently, the insulation breakdown accident has been experienced at 6.6kV inverter driving motor. That brought about the reliability degradation of motor driving system.. We need to find the solution with system engineering level. The objectives of this study are developing the appropriate filter for the drive to protect the motor and the Insulation system of motor which Is driven by inverter. We clarify the cause of the deterioration of the inverter driving motor through the analysis of Insulation breakdown accidents.

  • PDF

Fixture를 이용한 토양 절연파괴 실험 (Soil Breakdown Test using Fixture)

  • 이현구;하태현;정동학;하윤철;김대경;배정효
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.384-385
    • /
    • 2007
  • The fault current through the earth originated from a power line ground fault might cause arcing through the soil to an adjacent pipeline, which might bring about not only a catastrophic accident such as gas explosion and oil leakage but also a hazard to the safety of workers responsible for the maintenance and repair of the pipeline. In this paper we experimented on the soil breakdown test using the fixture and outlined the standards for the separation distance of a buried pipeline adjacent to the power line tower.

  • PDF

가속된 열적 스트레스에 의한 PAI / Nano Silica 하이브리드 코일의 절연수명 추정 (Estimation of Insulation Life of PAI/Nano Silica Hybrid Coil by Accelerated Thermal Stress)

  • 박재준
    • 전기학회논문지
    • /
    • 제68권1호
    • /
    • pp.52-60
    • /
    • 2019
  • In this paper, four types of insulation coils were fabricated by adding various kinds of glycols to improve the flexibility and adhesion of insulating coils in varnish dispersed with PAI / Nano Silica_15wt%. The applied voltage and frequency were 1.5 kV / 20 kHz for accelerated life evaluation. Through the 6th temperature stress level, the cause of the insulation breakdown of the coil was ignored and only the breakdown time was measured. The Arrhenius model was chosen based on the theoretical relationship between chemical reaction rate and temperature for estimating the insulation life of the coil due to accelerated thermal stress. Three types of distributions (Weibull, Lognormal, Exponential) were selected as the relationship between thermal stress model and distribution. The average insulation lifetime was estimated under the temperature stress of four types of insulation coils through the relationship between one kind of model and three kinds of distributions.

희귀분석을 이용한 복합 시스템의 열화진단 (Degradation Diagnosis of Complex System Using Regression Analysis)

  • 김성홍;송재주
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 기술교육위원회 창립총회 및 학술대회 의료기기전시회
    • /
    • pp.60-66
    • /
    • 2001
  • 절연체 내부의 보이드로 인하여 부분방전이 발생하면 국부파괴와 완전절연파괴의 원인이 된다. 부분방전으로 생기는 트리잉은 절연재료를 열화 시키고 절연 수명을 단축시키는 중요한 원인이 되므로 절연파괴를 미연에 하여 절연재료 수명을 예측할 수 있는 방법에 대한 연구는 매우 중요하다. 이러한 관점에서 본 연구는 부분방전 및 음향방출 시스템을 이용한 컴퓨터 시스템을 개발하여 각 시스템의 장점을 이용함으로써 열화진단을 실시하였다. 부분방전 시스템의 장점은 음향에 비하여 검출 신호가 양호하고, 고전압 절연 장치의 신뢰성을 평가하기에 적합하다. 또한 음향방출 시스템의 장점은 전자기의 영향을 받지 않고, 열화 과정을 실시간으로 관찰할 수 있다는 것이다. 이 두 가지의 장점을 복합적으로 이용하면 절연재료 내부에서 발생하는 트리의 위치와 부분방전을 효과적으로 할 수 있다. 열화분석 방법으로 먼저 부분방전 펄스와 음향방출 펄스를 희귀분석하여 T검정에 의한 상관계수와 결정계수를 구하여 비교해본 결과 부분방전과 음향방출 펄스는 대체적으로 비슷한 형태를 보였다. 이것은 Yoshimura와 Fujita의 연구 결과와 일치하였다.

  • PDF

복합 감지 시스템을 이용한 부분방전의 절연열화 수명추정 (A Life Prediction of Insulation Degradation Using Complex Sensing System)

  • 김성홍;김재환;박재준;최재관;윤헌주;이영상
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 추계학술대회 논문집 학회본부
    • /
    • pp.348-350
    • /
    • 1997
  • Because of internal voids ininsulators give rise to partial discharge(PD), which cause local breakdown and even entire insulation breakdown. Treeing due to PD is one of the main causes of breakdown of the insulating materials and reduction of the insulation life. Therefore the necessity for establishing a method to diagnose the aging of insulation materials and to predict the breakdown of insulation has become important. From this viewpoint, our studies diagnose insulation degradation using the method of computer sensing system, which has the advantages of PD and acoustic emission(AE) sensing system. To use advantages of these two methods can be used effectively to search for treeing location and PD in some materials. In analysis method of degradation. We analyzed the PD pulse and AE pulses by regression analysis, compared to these obtained the correlation coefficient and determination coefficient by T-distribution and saw that PD and AE pulses show a similar pattern on the whole. Finally using statically operator such as the center of gravity(G), the gradient of the discharge distribution(C), we have analyzed for the prediction of life which we can be obtained the time, occurred of many pulse of small discharge amplitude.

  • PDF