A Study on the Corrosion and Degradation of Boiler Tubes Steel in Fossil Power Plant

  • Baik, Young Min;Jeong, Hee Don;Kweon, Young Gak
    • Corrosion Science and Technology
    • /
    • v.5 no.4
    • /
    • pp.123-128
    • /
    • 2006
  • It was analyzed the causes of boiler tube rupture due to a degradation and corrosion on the boiler tubes in fossil power plant. The experiments were carried out among samples taken from the operating facilities. The result were analyzed based on experimental results from mechanical strength, microstructure observation, and hardness measurement in order to determine the cause of local rupture on boiler tubes. In general, 2.25Cr-1Mo steel generates carbides, it is coarsened, its ductility and strength abruptly decreased as degradation is in progress, In order to confirm this phenomenon, we observed changes of the mount of Cr and Mo of carbide by carrying out EDX chemical composition analysis. The amount of Cr and Mo in the degraded material or service exposed material gradually increased the amount of Mo but initially they were almost maintained at the same amount. Furthermore, we observed that the carbide become coarsened both in the grain and at the grain boundary. Tensile test was carried out to measure a material hardness and to recognize a drop-off of hardness. Overall result for tensile strength and hardness turned out to be lower than new material and mechanical strength and hardness was degraded as the material degradation was in progress.

Development of Mobile Robot Systems for Automatic Diagnosis of Boiler Tubes in Fossil Power Plants and Large Size Pipelines (화력발전소 보일러 튜브 및 대형 유체수송관 자동 진단을 위한 이동로봇 시스템 개발)

  • Park, Sang-Deok;Jeong, Hee-Don;Lim, Zhong-Soo
    • Journal of the Korean Society for Nondestructive Testing
    • /
    • v.22 no.3
    • /
    • pp.254-260
    • /
    • 2002
  • In this study, two types of mobile robotic systems using NDT (Non-destructive testing) method are developed for automatic diagnosis of the boiler tubes and large size pipelines. The developed mobile robots crawl the outer surface of the tubes or pipelines and detect in-pipe defects such as pinholes, cracks and thickness reduction by corrosion and/or erosion using EMAT (Electro-magnetic Acoustic Transducer). Automation of fault detection by means of mobile robotic systems for these large-scale structures helps to prevent significant troubles without danger of human beings under harmful environment.

A Two-Phase Flow Accelerated Corrosion Study on Water Wall Tube of Coal-Fired Boiler According to Flexible Operation (유연운전에 따른 석탄화력보일러 수계통 튜브에서의 이상 유동가속부식(Two-Phase Flow Accelerated Corrosion) 고찰)

  • Sang-Ho Kim;Seung-Min Lee;Jae-Hong Lee
    • Corrosion Science and Technology
    • /
    • v.23 no.3
    • /
    • pp.246-254
    • /
    • 2024
  • Recently, coal-fired power plants are experiencing many problems that they have never experienced before due to an increase in flexible operation. In particular, a two-phase flow accelerated corrosion on water wall tubes in a boiler has not been detected overseas or domestically. There is no response plan to deal with such corrosion problem either. However, oxide film damage and tube material corrosion due to a two-phase flow accelerated corrosion are being discovered on water wall boiler tubes of domestic coal-fired power plants recently. If this situation is severe, it can cause enormous damage such as tube rupture. Therefore, in this paper, in order to prepare a response plan for a two-phase flow accelerated corrosion on water wall tubes in the future, differences between a two-phase flow accelerated corrosion and a single-phase flow accelerated corrosion were investigated and an example of discovery of a two-phase flow accelerated corrosion on water wall tubes was presented.

Heat Transfer Characteristics of 0.5 t/h Class Non-Furnace Boiler with a Metal Fiber Burner (금속섬유 버너를 채택한 0.5 t/h 급 무연소실 보일러의 열전달 특성)

  • Ahn, Joon;Kim, Jong-Jin
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.35 no.2
    • /
    • pp.215-220
    • /
    • 2011
  • A 0.5 t/h class non-furnace boiler has been developed with the aim of achieving a high efficiency and compactness. A metal fiber burner has been adopted so that a stable flame can be obtained. The tube banks are installed downstream of the burner. Bare tubes are used upstream, while finned tubes are installed downstream. The heat-transfer characteristics of the non-furnace boiler have been studies on the basis of the results of the numerical simulation as well as those of the experiment. Important design parameters such as the bulk temperature along the streamwise direction and the temperature of the fin tips have been evaluated using the CFD results and compared with the experimental data and the empirical correlations typically used for the design of the boiler.

High-temperature Mechanical Properties Measurement and Life Assessment of Boiler Equipment by Instrumented Indentation Technique (계장화 압입시험법을 이용한 보일러 설비의 고온 기계적 물성 측정과 수명 평가)

  • Ro, Dong-Seong;Hong, Jeong-Wha;Kim, Kwang-Ho;Lee, Jung-Jun
    • Journal of the Korean Society of Safety
    • /
    • v.24 no.3
    • /
    • pp.1-6
    • /
    • 2009
  • Recently power plants and oil refineries are focusing on capacity enlargement for better efficiency through higher temperature and higher pressure. Thickness of boiler tubes becomes lessened due to oxidation and erasion caused by high temperature bums gas flowing over tubes outside. Accordingly, mechanical stress of tubes is increasing and that is a critical factor to make a crack and fracture. To prevent those sorts of accidents, aging assessment for proper periodic repair and replacement should be conducted reliably and reasonably. We performed IIT test on Cr-Mo steel, one of the most heat-resistant materials for facilities in power plants, and we report the test result and the considerable effectiveness of IIT test.

Experimental Study on Thermal Characteristics of Heat Exchanger Modules for Multi Burner Boiler (멀티버너 보일러용 열교환기 모듈 특성 시험 - 모듈 순서에 따른 특성결과 -)

  • Kang, Sae-Byul;Kim, Jong-Jin;Ahn, Joon
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.3053-3058
    • /
    • 2008
  • We develop a heat exchanger modules for a multi-burner boiler. The heat exchanger module is kind of a heat recovery steam generator (HRSG). This heat recovery system has 4 heat exchanger modules. The 1st module consists of 27 bare tubes due to high temperature exhaust gas and the others consist of 27 finned tubes. The maximum steam pressure of each module is 1 MPa and tested steam pressure is 0.7 MPa. In order to test these heat exchanger modules, we make a 0.5t/h flue tube boiler (LNG, $40\;Nm^3/h$). We tested the heat exchanger module with changing the position of each heat exchanger module. We measured the inlet and outlet temperature of each heat exchanger module and calculated the heat exchange rate. The results show that if module C is placed at second stage (the 1st stage is always module O, bare tube module), there is no need to attach an additional heat exchanger module. In this case the exit temperature of module C is low enough to enter an economizer which is more effective in heat recovery than a heat exchanger module.

  • PDF

Study on the Microstructural Degradation of the Boiler Tubes for Coal-Fired Power Plants

  • Yoo, Keun-Bong;He, Yinsheng;Lee, Han-Sang;Bae, Si-Yeon;Kim, Doo-Soo
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.4 no.1
    • /
    • pp.25-31
    • /
    • 2018
  • A boiler system transforms water to pressured supercritical steam which drives the running of the turbine to rotate in the generator to produce electricity in power plants. Materials for building the tube system face challenges from high temperature creep damage, thermal fatigue/expansion, fireside and steam corrosion, etc. A database on the creep resistance strength and steam oxidation of the materials is important to the long-term reliable operation of the boiler system. Generally, the ferritic steels, i.e., grade 1, grade 2, grade 9, and X20, are extensively used as the superheater (SH) and reheater (RH) in supercritical (SC) and ultra supercritcal (USC) power plants. Currently, advanced austenitic steel, such as TP347H (FG), Super304H and HR3C, are beginning to replace the traditional ferritic steels as they allow an increase in steam temperature to meet the demands for increased plant efficiency. The purpose of this paper is to provide the state-of-the-art knowledge on boiler tube materials, including the strengthening, metallurgy, property/microstructural degradation, oxidation, and oxidation property improvement and then describe the modern microstructural characterization methods to assess and control the properties of these alloys. The paper covers the limited experience and experiment results with the alloys and presents important information on microstructural strengthening, degradation, and oxidation mechanisms.

Flaw Discrimination for Welding Points in Boiler Tubes by Phased Array Ultrasonic Testing (위상배열초음파탐상검사에 의한 보일러관 용접부의 결함 판별)

  • Cho, Kuk-Hyung;Yoo, Ho-Seon
    • Plant Journal
    • /
    • v.14 no.2
    • /
    • pp.45-50
    • /
    • 2018
  • Nuclear safety law's amendment caused many problems to use radiography testing(RT). Phased array ultrasonic testing(PAUT) was adapted instead of RT for NDE of welding points in boiler tubes these days. Unfortunately, PAUT doesn't give us the discrimination characteristics about flaws distinction and flaws size clearly. In this thesis, the distinction characteristics of flaw types and the detection characteristics of flaw size using PAUT of welding points in boiler tubes were analyzed. It was concluded that PAUT can distinguish between planar flaws and rounded flaws, but it is hard to tell apart the types of flaw respectively. We paid attention to the discrimination of flaws size because PAUT tends to underestimate the flaw size of porosity and underestimate or overestimate the flaw size of porosity.

  • PDF

The design of heat exchanger of small size steam boiler using the concentric annuli tube with pin fin (동심원관-pin fin 열교환기를 이용한 소형 증기보일러 대류실 설계)

  • Kim, Sungil;Choi, Sangmin
    • 한국연소학회:학술대회논문집
    • /
    • 2012.11a
    • /
    • pp.115-118
    • /
    • 2012
  • The configurations of the heat exchanger of the boiler can be determined from the trade-off between the heat transfer area which is related to the capital cost and the pressure drop which is related to operating cost. In this study, 3.5 ton/hr small size marine boiler having concentric annuli tubes is the design boiler. To determine the optimizing point, according to diameter, number, length of tube, heat transfer, pressure drop, operating cost and capital cost have been calculated. Also, when the fin tube is replaced by the bare tube design parameters changed have been calculated.

  • PDF