• Title/Summary/Keyword: AIT(autoignition temperatures)

Search Result 38, Processing Time 0.03 seconds

The Evaluation of Hazard by Measurement of Combustible Characteristics of n-Tetradecane (노말테트라데칸의 연소특성치 측정에 의한 위험성 평가)

  • Ha, Dong-Myeong
    • Journal of the Korean Society of Safety
    • /
    • v.27 no.5
    • /
    • pp.70-76
    • /
    • 2012
  • For the safe handling of n-tetradecane, the lower flash points and the upper flash point, fire point, AITs (auto-ignition temperatures) by ignition delay time were experimented. Also lower and upper explosion limits by using measured the lower and upper flash points for n-tetradecane were calculated. The lower flash points of n-tetradecane by using closed-cup tester were measured $104^{\circ}C$ and $112^{\circ}C$. The lower flash points and fire point of n-tetradecane by using open cup tester were measured $113^{\circ}C$ and $115^{\circ}C$, respectively. This study measured relationship between the AITs and the ignition delay times by using ASTM E659 apparatus for n-tetradecane. The experimental AIT of n-tridecane was $207^{\circ}C$. The calculated lower and upper explosion limit by using measured lower $104^{\circ}C$ and upper flash point $140^{\circ}C$ for n-tetradecane were 0.63 Vol.% and 3.18 Vol%.

The Measurement of Combustible Properties of Cyclopentanol (사이클로펜탄올의 연소특성치의 측정)

  • Ha, Dong-Myeong
    • Journal of the Korean Institute of Gas
    • /
    • v.18 no.2
    • /
    • pp.35-40
    • /
    • 2014
  • For the safe handling of cyclopentanol, this study was investigated the explosion limits of cyclopentanol in the reference data. The flash points and AITs(auto-ignition temperatures) by ignition delay time were experimented. The lower flash point of cyclopentanol by using closed-cup cyclopentanol was experimented at $49^{\circ}C$. The lower flash points of cyclopentanol by using open cup tester was experimented at $59^{\circ}C$. This study measured relationship between the AITs and the ignition delay times by using ASTM E659 tester for cyclopentanol. The experimental AIT of cyclopentanol was at $363 ^{\circ}C$.

The Measurement of Fire and Explosion Properties of n-Pentadecane (노말펜타데칸의 화재 및 폭발 특성치의 측정)

  • Ha, Dong-Myeong
    • Journal of the Korean Society of Safety
    • /
    • v.28 no.4
    • /
    • pp.53-57
    • /
    • 2013
  • For the safe handling of n-pentadecane, the lower flash points and the upper flash point, fire point, AITs(auto-ignition temperatures) by ignition delay time were experimented. Also lower and upper explosion limits by using measured the lower and upper flash points for n-pentadecane were calculated. The lower flash points of n-pentadecane by using closed-cup tester were measured $118^{\circ}C$ and $122^{\circ}C$. The lower flash points and fire point of n-pentadecane by using open cup tester were measured $126^{\circ}C$ and $127^{\circ}C$, respectively. This study measured relationship between the AITs and the ignition delay times by using ASTM E659 apparatus for n-pentadecane. The experimental AIT of n-pentadecane was $195^{\circ}C$. The calculated lower and upper explosion limit by using measured lower $118^{\circ}C$ and upper flash point $174^{\circ}C$ for n-pentadecane were 0.54 Vol.% and 6.40 Vol.%.

The Measurement and Investigation of Fire and Explosion Characteristics of Cyclohexanone (사이클로헥사논의 화재 및 폭발 특성치의 측정 및 고찰)

  • Ha, Dong-Myeong
    • Fire Science and Engineering
    • /
    • v.25 no.4
    • /
    • pp.28-34
    • /
    • 2011
  • For the safe handling of cyclohexanone, the explosion limits at $25^{\circ}C$ were investigated. The lower flash points and AITs (auto-ignition temperatures) by ignition time delay for cyclohexanone were experimented. By using the literatures data, the lower and upper explosion limits of cyclohexanone recommended 1.1 Vol.% ($100^{\circ}C$) and 9.4 Vol.%, respectively. The lower flash points of cyclohexanone were experimented $42{\sim}43^{\circ}C$ by using closed-cup tester and $49{\sim}51^{\circ}C$ by using open cup tester. This study measured relationship between the AITs and the ignition delay times by using ASTM E659-78 apparatus for cyclohexanone and the experimental AIT of cyclohexanone was $415^{\circ}C$.

Appropriateness of MSDS by Means of the Measurement of Combustible Properties of Anisole (아니솔의 연소특성치의 측정에 의한 MSDS의 적정성)

  • Ha, Dong-Myeong
    • Fire Science and Engineering
    • /
    • v.29 no.2
    • /
    • pp.20-24
    • /
    • 2015
  • For the safe handling of anisole, this study was investigated the explosion limits of anisole in the reference data. The flash points and auto-ignition temperatures (AITs) by ignition delay time were experimented. The lower flash points of Anisole by using closed-cup tester were experimented in $39^{\circ}C$ and $42^{\circ}C$. The lower flash points of Anisole by using open cup tester were experimented in $50^{\circ}C$ and $54^{\circ}C$. This study measured relationship between the AITs and the ignition delay times by using ASTM E659 tester for Anisole. The AIT of Anisole was experimented as $390^{\circ}C$. The lower explosion limit (LEL) by the measured the lower flash point for Anisole were calculated as 1.07 Vol%.

The Measurement of Combustible Properties of Cyclohexanol (사이클로헥산올의 연소특성치의 측정)

  • Ha, Dong-Myeong
    • Fire Science and Engineering
    • /
    • v.28 no.2
    • /
    • pp.64-68
    • /
    • 2014
  • For the safe handling of cyclohexanol, this study was investigated the explosion limits of cyclohexanol in the reference data. The flash points and auto-ignition temperatures (AITs) by ignition delay time were experimented. The lower flash points of cyclohexanol by using closed-cup tester were experimented in$60^{\circ}C{\sim}64^{\circ}C$. The lower flash points of cyclohexanol by using open cup tester were experimented in $66^{\circ}C{\sim}68^{\circ}C$. This study measured relationship between the AITs and the ignition delay times by using ASTM E659 tester for cyclohexanol. The AIT of cyclohexanol was experimented as $297^{\circ}C$. The lower explosion limit (LEL) and the upper explosion limit UEL) by the measured the lower flash point and the upper flash point of cyclohexanol were calculated as 0.95 Vol% and 10.7 Vol%, respectively.

The Measurement of Fire and Explosion Properties of n-Hexadecane (노말헥사데칸의 화재 및 폭발 특성치의 측정)

  • Ha, Dong-Myeong
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.3
    • /
    • pp.39-45
    • /
    • 2014
  • For the safe handling of n-hexadecane, the lower flash points and the upper flash point, fire point, AITs(auto-ignition temperatures) by ignition delay time were experimented. Also lower and upper explosion limits by using measured the lower and upper flash points for n-hexadecane were calculated. The lower flash points of n-hexadecane by using the Setaflash and the Pensky-Martens closed testers were measured $128^{\circ}C$ and $126^{\circ}C$, respectively. The lower flash points of the Tag and the Cleveland open cup testers were measured $136^{\circ}C$ and $132^{\circ}C$, respectively. The fire points of the Tag and the Cleveland open cup testers were measured $144^{\circ}C$. respectively. This study measured relationship between the AITs and the ignition delay times by using ASTM E659 apparatus for n-hexadecane. The experimental AIT of n-hexadecane was $200^{\circ}C$. The calculated lower and upper explosion limit by using measured lower $128^{\circ}C$ and upper flash point $180^{\circ}C$ for n-hexadecane were 0.42 Vol.% and 4.70 Vol.%.

Measurement and Prediction of Combustion Properties of Styrene (스티렌의 연소특성치 측정 및 예측)

  • Ha, Dong-Myeong;Na, Byeong-Gyun
    • Journal of the Korean Institute of Gas
    • /
    • v.17 no.4
    • /
    • pp.70-76
    • /
    • 2013
  • For the safe handling of styrene, this study was investigated the explosion limits of styrene in the reference data. The flash points and AITs(auto-ignition temperatures) by ignition delay time were experimented. As a results, the lower and upper explosion limits of styrene recommended 0.9 Vol.% and 8.0 Vol.%, respectively. The lower flash points of styrene by using closed-cup tester were experimented $29^{\circ}C{\sim}31^{\circ}C$. The lower flash points of styrene by using open cup tester were experimented $32^{\circ}C{\sim}36^{\circ}C$. This study measured relationship between the AITs and the ignition delay times by using ASTM E659 tester for styrene. The experimental AIT of styrene was $460^{\circ}C$.

The Measurement and Investigation of Combustible Properties for n-Hexane (노말헥산의 연소특성치의 측정 및 고찰)

  • Ha, Dong-Myeong
    • Journal of the Korean Society of Safety
    • /
    • v.26 no.2
    • /
    • pp.36-41
    • /
    • 2011
  • For the safe handling of n-hexane, the explosion limit at $25^{\circ}C$, the temperature dependence of the explosion limits and the lower flash point were investigated. And AITs(auto-ignition temperatures) by ignition delay time for n-hexane were experimented. By using the literatures data, the lower and upper explosion limits of n-hexane recommended 1.0 Vol% and 8.0 Vol%, respectively. In this study, the lower flash points of n-hexane recommended $-23^{\circ}C$. This study measured relationship between the AITs and the ignition delay times by using ASTM E659-78 apparatus for n-hexane, and the experimental AIT of n-hexane was $240^{\circ}C$. The new equations for predicting the temperature dependence of the explosion limits of n-hexane is proposed. The values calculated by the proposed equations were a good agreement with the literature data.

A Study of the Evaluation of Combustion Properties of Tetralin (테트랄린의 연소특성치 평가에 관한 연구)

  • Ha, Dong-Myeong
    • Journal of the Korean Society of Safety
    • /
    • v.33 no.4
    • /
    • pp.8-14
    • /
    • 2018
  • In the industrial chemical process involving combustible materials, reliable safety data are required for design prevention, protection and mitigation measures. The accurate combustion properties are necessary to safely treatment, transportation and handling of flammable substances. The combustion parameters necessary for process safety are lower flash point, upper flash point, fire point, lower explosion limit(LEL), upper explosion limit(UEL)and autoignition temperature(AIT) etc.. However, the combustion properties suggested in the Material Safety Data Sheet (MSDS) are presented differently according to the literatures. In the chemical industries, tetralin which is widely used as a raw material of intermediate products, coating substances and rubber chemicals was selected. For safe handling of tetralin, the lower and flash point, the fire point, and the AIT were measured. The LEL and UEL of tetralin were calculated using the lower and upper flash point obtained in the experiment. The flash points of tetralin by using the Setaflash and Pensky-Martens closed-cup testers measured $70^{\circ}C$ and $76^{\circ}C$, respectively. The flash points of tetralin using the Tag and Cleveland open cup testers are measured $78^{\circ}C$ and $81^{\circ}C$, respectively. The AIT of the measured tetralin by the ASTM E659 apparatus was measured at $380^{\circ}C$. The LEL and UEL of tetralin measured by Setaflash closed-cup tester at $70^{\circ}C$ and $109^{\circ}C$ were calculated to be 1.02 vol% and 5.03 vol%, respectively. In this study, it was possible to predict the LEL and the UEL by using the lower and upper flash point of tetralin measured by Setasflash closed-cup tester. A new prediction method for the ignition delay time by the ignition temperature has been developed. It is possible to predict the ignition delay time at different ignition temperatures by the proposed model.