• Title/Summary/Keyword: AC railway feeding

Search Result 39, Processing Time 0.039 seconds

Investigation of Autotransformer Configuration to Enhance Collecting Voltage in Train (집전 전압 향상을 위한 교류급전시스템의 단권변압기 구성 검토)

  • Kim, Joo-Rak;Kim, Jung-Hoon
    • Journal of the Korean Society for Railway
    • /
    • v.13 no.1
    • /
    • pp.65-70
    • /
    • 2010
  • AC traction power supply system has adopted autotransformer (AT) feeding method. This system has an advantage as long feeding distance. However, the countermeasure for voltage drop should be considered, because load capacity grows larger and headway grows shorter in recent electric railway system. This paper proposes the improved system configuration to enhance voltage drop in ac railway system without additional power electronic device. That is to increase turn ratio between contact wire and rail of AT. By modifying turn ratio of AT at SSP or SP, collecting voltage on train will be enhanced.

A Study of LA Counter Over-activation in AC Electric railway Substation (AC 전철변전소의 피뢰기카운터 과동작에 관한 연구)

  • Cheon, Hee-Seung;Jang, Woo-Jin
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.132-139
    • /
    • 2008
  • In an electric railway feeding system, transient over-voltage often appears due to the feeder's direct lightning and induced lightning, while switching over-voltage also frequently occurs during operation of electric feeding in substation facilities. Such over-voltage is several times larger than the regular power, and accordingly leads to the dieletric breakdown of eletric power products such as invasion transformers and circuit breakers. Arresters are installed to protect these machines, while arrester counters are installed to observe the arrester's activation. This thesis aims to explore the status of an arrester counter that is being activated several thousand times, determine whether the arrester has actually been activated in relation to the counter, and investigate the over-heatedness and risks of the arrester.

  • PDF

Analysis for Catenary Voltage of The ATs-Fed AC Electric Railroad System (교류전기철도 급전시스템의 전차선 전압해석)

  • 이승혁;정현수;김진오
    • Proceedings of the KSR Conference
    • /
    • 2002.10a
    • /
    • pp.490-496
    • /
    • 2002
  • This paper presents exact Autotransformers(ATs)-fed AC electric Railroad system modeling using constant current mode far locomotives. An AC electric railroad system is rapidly changing single-phase load, and at a feeding substation, 3-phase electric power is transferred to paired directional single-phase electric power. As the train moves along a section of line between two adjacent ATs. The proposed AC electric railroad system modeling method considers the line self-impedances and mutual-impedances. The constant current mode model objectives are to calculate the catenary and rail voltages with the loop equation. When there are more than one train in the AC electric railroad system, the principle of superposition applies and the only difference between the system analyses for one train. Finally, this paper shows the general equation of an AC electric railroad system, and that equation has no relation with trains number, trains position, and feeding distance.

  • PDF

Parametric Study for Variable Tap of Autotransformer Neutral in AC Feeding (전기철도 단권변압기 중성점 탭절환 특성연구)

  • Han, Moonseob;Lee, Chang-Mu;Kim, Jae-Won;Chang, Sang-Hoon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.1
    • /
    • pp.137-141
    • /
    • 2018
  • The voltage drop is important in electric railway for feeding a huge power of train on fixed feeding area. Nowadays it is tried to operate a high speed trains on conventional lines and there is problem on the voltage drop too. It is simulated on the conditions increased the turn ratio of trolley, installed autotransformer neutral line with variable taps. In result, it is compensated the voltage drop between ATs and better on last AT, not on the position of AT. And it is decreased a return current and neutral current of AT because of unbalance between trolley and feeder. It should be studied faster and more controllable the solid state switchs instead of the mechanical one in order to utilize this system.

A Study on the Countermeasures to Suppress Harmonics in the Traction Power Supply System (철도 급전시스템에서의 고조파 해석 및 대책 연구)

  • 오광해;이장무;창상훈;한문섭;김길상
    • Proceedings of the KSR Conference
    • /
    • 1999.11a
    • /
    • pp.318-325
    • /
    • 1999
  • Modern AC electric car has PWM(Pulse Width Modulation)-controlled converters, which give rise to higher harmonics. The current harmonics injected from AC electric car is propagated through power feeding circuit, As the feeding circuit is a distributed constant circuit composed of RLC, the capacitance of the feeding circuit and the inductance on the side of power system cause a parallel resonance and a magnification of current harmonics at a specific frequency. The magnified current harmonics usually brings about various problems. That is, the current harmonics makes interference in the adjacent lines of communications and the railway signalling system. Furthermore, in case it flows on the side of power system, not only overheating and vibration at the power capacitors but also wrong operation at the protective devices can occur. Therefore, the exact assessment of the harmonic current flow must be undertaken at design and planning stage for the electric traction systems. From these point of view, this study presents an approach to model and to analyse traction power feeding system focused on the amplification of harmonic current The proposed algorithm is applied to a standard AT(Auto-transformer)-fed test system in which electric car with PWM-controlled converters is running.

  • PDF

Test results of small scale changeover system using in neutral section for AC feeding system (축소형 교류급전시스템 절연구간 자동절체장치 성능시험)

  • Jang, Dong-Uk;Han, Moon-Seob
    • Proceedings of the KSR Conference
    • /
    • 2011.05a
    • /
    • pp.948-953
    • /
    • 2011
  • In AC railway feeding system, three phase received from the network is changed to two phase power sources with different phases. The main circuit breaker installed train is automatically open by track signal when the train passes the neutral section. In order to continuously supply power source to train, the changeover system was used in Japan. Therefore, the train is able to operate under powering condition when it was passing through the neutral section. We investigated the control method to reduce the inrush current flowing main transformer in train. To examine the inrush current and operate the static semiconductor switch such as thyristor, we manufactured the small scale the changeover system and carried out performance tests.

  • PDF

The Analysis of 4-Conductors Catenary System of AC Railway Feeding System and Calculation of Induced Voltage near Rail Track using the FDTD Method (교류 전기철도 급전계통 4도체군 전차선로 분석 및 FDTD 방법을 이용한 선로 주변 유도전압 계산에 관한 연구)

  • Ryu, Kyu-Sang;Yeom, Hyoung-Sun;Cho, Gyu-Jung;Lee, Hun-Do;Kim, Cheol-Hwan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.12
    • /
    • pp.1958-1964
    • /
    • 2016
  • AC railway feeding system use single phase to supply power to the railway vehicles. And the system use the rail track as a return current path, so that current flows in the rail. In this situation inductive interference on communication system and unsafe environment can appear on railway system. Therefore knowing the current distribution of catenary system and analysing the return current is required. In this study detail return current distribution was analyzed by modeling the catenary system as 4-conductors group. The distribution characteristics and trends of return current were studied by using the PSCAD/EMTDC and FDTD method that based on Maxwell equation was used to calculate the induced voltage. Simulation code was made by MATLAB. Using this study result data, we can suggest the proper installation location of digital device and these data can be used for additional studies related to return current or induced voltage as a base data.

An analysis of the power quality problem at an electric train according to dead section (절연구간 통과시 전기철도 차량에 유입되는 전력 품질 분석)

  • Lee, Bong-Yi;Kim, Jae-Chul;Moon, Jong-Fil;Han, Seong-Ho;Lee, Su-Gil
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.51-53
    • /
    • 2005
  • At the railway feeding system, a role of dead section is very important. Because, dead section is essential installation that AC feeding system meets DC feeding system or phase is changed between AC feeding systems. But, in dead section it is possible that an electric train meets interruption. In Korea, a study on the dead section isn't yet accomplished in depth. Accordingly. In this paper, when electric train is in dead-section power quality problem on electric train was dealt. Modeling and simulation using PSCAD/EMTDC was accomplished to analyze.

  • PDF

Evaluation of the variable TAB Autotransformer for ascending collecting Voltage (집전전압 향상을 위한 가변탭 단권변압기 검토)

  • Lee, Chang-Mu;Han, Moon-Seub;Lee, Han-Min
    • Proceedings of the KSR Conference
    • /
    • 2009.05a
    • /
    • pp.1426-1430
    • /
    • 2009
  • AC AT feeding method consists return circuits of electric train inserting in parallel between trolly line and feeding line and connecting neutral line to rail and FPW. Due to increasing electric load at feeding system, collecting voltage of train and end voltage are going down. So to increase voltage between trolly line and rail, the usefulness of new autotransformer are considered which variation of short impedance and change of line voltage is simulated with modified winding ratio of autotransformer from 1:1 to variable tab.

  • PDF