• Title/Summary/Keyword: AC arrester

Search Result 36, Processing Time 0.023 seconds

Deterioration Characteristics of ZnO Surge Arrester Blocks for Power Distribution Systems Due to Impulse Currents (임펄스전류에 의한 배전용 ZnO 피뢰기 소자의 열화특성)

  • Lee, Bok-Hee;Cho, Sung-Chul;Yang, Soon-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.3
    • /
    • pp.79-86
    • /
    • 2013
  • In order to analyze the electrical performance of ZnO surge arresters stressed by the combined DC and AC voltages that are generated in DC/AC converter systems, the leakage current properties of ZnO surge arrester blocks deteriorated by impulse currents were investigated. The test specimens were deteriorated by the 8/$20{\mu}s$ impulse current of 2.5kA and the leakage currents flowing into the deteriorated zinc oxide(ZnO) arrester blocks subjected to the combined DC and power frequency AC voltages are measured. As a result, the leakage currents flowing through deteriorated ZnO surge arrester blocks were higher than those flowing through the fine ZnO surge arrester blocks and the larger the injection number of 8/$20{\mu}s$ impulse current of 2.5kA is, the greater the leakage current is. The leakage current-voltage curves(I-V curves) of the fine and deteriorated ZnO surge arrester blocks stressed by the combined DC and AC voltages show significant difference in the low conduction region. Also the cross-over phenomenon is observed at the voltage close to the knee of conduction on plots of I-V curves.

Electrical Characteristics of ZnO Surge Arrester Elements Subjected to the Mixed DC and 60[Hz] AC Voltages (직류+60[Hz] 교류 중첩전압에 대한 ZnO 피뢰기 소자의 전기적 특성)

  • Lee, Bok-Hee;Yang, Soon-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.4
    • /
    • pp.41-47
    • /
    • 2012
  • This paper deals with the electrical characteristics related to power loss, equivalent resistance, and leakage currents flowing through new and deteriorated zinc oxide(ZnO) arrester elements subjected to the mixed DC and 60[Hz] AC voltages. The test specimens were deteriorated by 8/20[${\mu}s$] impulse current of 2.5[kA]. The leakage current-applied voltage($I-V$) characteristic curves of ZnO surge arrester elements were measured as a parameter of the ratio of the peak of 60[Hz] AC voltage to the peak of total voltage. As a consequence of test results, in case of the same applied voltage, the leakage currents flowing through the deteriorated ZnO arrester elements were higher than those flowing through the new ZnO surge arrester elements. The cross-over phenomenon in $I-V$ curves of ZnO surge arrester elements measured as a parameter of the mixed ratio of DC and AC voltages was observed at the low current domain. The effect of DC voltage on the leakage current flowing through ZnO surge arrester elements is pronounced at the same magnitude of test voltages. In addition, the larger the applied number of 8/20[${\mu}s$] impulse current of 2.5[kA] is, the greater the power loss is, in particular, the more severe the power loss increases at higher applied voltages.

Electrical Properties of 18[kV] ZnO Surge Arrester Stressed by the Mixed DC and 60[Hz] AC Voltages (직류+60[Hz]교류 중첩전압에 대한 18[kV] ZnO 피뢰기의 전기적 특성)

  • Lee, Su-Bong;Lee, Seung-Ju;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.10
    • /
    • pp.66-72
    • /
    • 2007
  • This paper describes the characteristics of power loss and leakage currents flowing through new and used 18[kV] zinc oxide(ZnO) surge arrester under the mixed DC and AC voltages. The mixed DC and AC voltage generator of 50[kV] peak was designed and fabricated. The I-V curves of ZnO surge arrester were measured as a function of the voltage ratio K. The I-V curves under the mixed DC and AC voltages lay between the pure DC and AC characteristics, and the cross-over phenomenon in both I-V curves and R-V curves was observed at the low current region. As a result, the increase of DC component in the mixed voltages causes the increase of resistive component of total leakage current of ZnO surge arrester. Also, in the case of same applied voltage, the leakage current flowing through the used ZnO surge arrester was higher than that of the new ZnO surge arrester.

Characteristics and Change of Electrode Surface in Moisture Absorption on the Series Gap Surge Arrester (직렬 갭 피뢰기의 흡습시 전극표면의 변화 및 특성)

  • Cho, Han-Gu;Kim, Hyang-Suk
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07b
    • /
    • pp.1172-1175
    • /
    • 2003
  • The characteristics and change of electrode surface about Gap type surge arrester for protect DC subway rail were investigated with moisture absorption. Compared that tested about DC/AC discharge commencement voltage, residual voltage, Impulse, square wave impulse for DC rail surge arrester about Gap type surge arrester of moisture absorption state. The AC discharge commencement voltage acted greatly effect of moisture absorption than the DC discharge commencement voltage test.

  • PDF

The Characteristic of Data Transmission for Power Line Communication using an AC Arrester for Electric Railway (전철 피뢰기를 이용한 전력선 통신 데이터 전송 특성)

  • Kim, Jae-Moon;Ahn, Seung-Ho;Kim, Yang-Su;Kim, Chul-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.3
    • /
    • pp.497-502
    • /
    • 2012
  • Power line communication(PLC) is a kind of communication technology, was made use of controling a frequency narrow band, but as the PLC technology developing, in the near future get to the commercial step that is broadband PLC upto 30 MHz. This paper deals with the PLC of electric railway using capacitive signal coupler. An AC arrester for catenary is used as a capacitive signal coupler, has the characteristic of capacitor. As a result of field test, a messenger wire used PLC contain much of conducted noise about overall frequency band and also signal attenuation rate increased with increasing frequency between two points. and the communication speed of PLC used messenger wire is 793kbps at a distance of 40m. Experimental results show the possibility of PLC using a messenger wire and an AC arrester for catenary at electric railway.

Arrester Design of High power Converter (대용량 컨버터의 Arrester 설계)

  • Kim Chan-Ki;Lee Won Kyo;Shin Jin Chul;Ryu Hong U
    • Proceedings of the KIPE Conference
    • /
    • 2004.07a
    • /
    • pp.461-464
    • /
    • 2004
  • 본 논문은 대용량 컨버터에 이용되는 Arrester에 대한 설계기법을 보여주고 있다. 본 논문에는 Arrester의 설계방법과 일반적인 AC계통에서 사용하는 Arrester와 다른 열방산 특성을 다루었다.

  • PDF

A Study of LA Counter Over-activation in AC Electric railway Substation (AC 전철변전소의 피뢰기카운터 과동작에 관한 연구)

  • Cheon, Hee-Seung;Jang, Woo-Jin
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.132-139
    • /
    • 2008
  • In an electric railway feeding system, transient over-voltage often appears due to the feeder's direct lightning and induced lightning, while switching over-voltage also frequently occurs during operation of electric feeding in substation facilities. Such over-voltage is several times larger than the regular power, and accordingly leads to the dieletric breakdown of eletric power products such as invasion transformers and circuit breakers. Arresters are installed to protect these machines, while arrester counters are installed to observe the arrester's activation. This thesis aims to explore the status of an arrester counter that is being activated several thousand times, determine whether the arrester has actually been activated in relation to the counter, and investigate the over-heatedness and risks of the arrester.

  • PDF

A study on analysis of thermal and electrical parameters of the ZnO arrester block (배전용 ZnO 피뢰기 소자의 열적/전기적 파라미터 분석에 관한 연구)

  • Lee, Bok-Hee;Lee, Su-Bong;Lee, Seung-Ju;Jeon, Byung-Wook;Kim, Dong-Sung
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2007.05a
    • /
    • pp.353-356
    • /
    • 2007
  • This paper presents the thermal and electrical characteristics of ZnO arrester blocks under the AC voltages. The leakage currents of ZnO arrester blocks were measured as a function of time. The temperature distributions of ZnO arrester blocks were observed by the forward looking infrared camera The degradation and thermal runaway of ZnO arrester blocks were closely related with the temperature limit of ZnO arrester blocks which decided heat generation and dissipation As a result, the degradation and thermal runaway of ZnO arrester blocks depend on the temperature and leakage current of ZnO arrester blocks.

  • PDF

The electrical properties of in 18kV ZnO surge arrestor with mixed direct and 60Hz Alternating Voltage (중첩전압(직류 +60Hz 교류)에서 18kV 배전용 피뢰기의 전기적 특성)

  • Lee, Bok-Hee;Lee, Seung-Ju;Lee, Su-Bong;Jung, Dong-Cheol;Baek, Young-Hwan
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2007.05a
    • /
    • pp.291-294
    • /
    • 2007
  • This paper preserts the characteristics of leakage currents flowing through 18 kV zinc oxide (ZnO) surge arrester under the mixed DC and AC voltages. The I-V curves of ZnO surge arrester were measured as a function of the voltage ratio K The I-V curves under the mixed DC and AC voltages lay between the pure DC and AC characteristics, and the cross-over phenomenon in I-V curves was observed at the low current region As a result, the increase of DC component to mixed voltages causes the increase of resistive component of total leakage current th ZnO surge arrester.

  • PDF

Degradation Properties of ZnO Surge Arresters Due to Lightning Impulse Currents (뇌임펄스전류에 의한 ZnO 피뢰기의 열화특성)

  • Lee, Su-Bong;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.4
    • /
    • pp.79-85
    • /
    • 2009
  • This paper describes the degradation properties of ZnO surge arresters impressed by lightning impulse currents. To investigate the deterioration behaviors of ZnO surge arresters due to lightning surges, the 8/20[${\mu}s$], 2.5[kA] standard lightning impulse currents were injected to the ZnO surge arrester under test. The power frequency AC and DC leakage currents flowing through the ZnO surge arresters with and without the injection of lightning impulse currents were measured. As a result, the leakage currents are increased and the asymmetry of the AC leakage current is pronounced as the number of injection of the impulse current increases. The ZnO grain of the surge arrester without the injection of lightning surges are uniform but the ZnO grain of the ZnO surge arrester with the injection of lightning impulse currents are deformed. Also, it was found that the decrease of the $Bi_2O_3$ due to the lightning impulse current leads to the lack of grain boundary layer and the current concentrated by the lack of grain boundary layer play an important role to degrade nonlinear property of ZnO surge arrester blocks.