Abstract
This paper describes the characteristics of power loss and leakage currents flowing through new and used 18[kV] zinc oxide(ZnO) surge arrester under the mixed DC and AC voltages. The mixed DC and AC voltage generator of 50[kV] peak was designed and fabricated. The I-V curves of ZnO surge arrester were measured as a function of the voltage ratio K. The I-V curves under the mixed DC and AC voltages lay between the pure DC and AC characteristics, and the cross-over phenomenon in both I-V curves and R-V curves was observed at the low current region. As a result, the increase of DC component in the mixed voltages causes the increase of resistive component of total leakage current of ZnO surge arrester. Also, in the case of same applied voltage, the leakage current flowing through the used ZnO surge arrester was higher than that of the new ZnO surge arrester.
이 논문은 직류+60[Hz] 교류 중첩전압에서 신품과 노후된 18[kV] 산화아연 서지피뢰기의 누설전류와 전력손실에 대하여 기술하였다. 최대 50[kV]의 직류+60[Hz] 교류를 발생시킬 수 있는 중첩전압발생장치가 설계되고 제작되었다. 피뢰기의 I-V 특성곡선은 전압중첩률 K의 함수로 측정된다. DC와 AC 전압이 중첩된 I-V, R-V 특성곡선은 순수한 직류와 교류곡선 사이에 있고 저전류 영역에서 교차현상이 나타난다. 그 결과 중첩 전압에서 직류 성분의 증가는 ZnO 피뢰기의 전체 누설전류의 저항성분의 증가를 유발한다. 또한 같은 인가전압에서 피뢰기를 통해 흐르는 누설전류는 상용전원에서 장시간 스트레스 받은 피뢰기가 신품 피뢰기에 비해서 높게 나타났다.