• 제목/요약/키워드: 1 MVA

검색결과 132건 처리시간 0.026초

Assembling and Insulation Test of 1MVA Single Phase HTS Transformer for Power Distribution

  • Kim, S. H.;Kim, W. S.;Kim, J. T.;Park, K. D.;H. G. Joo;G. W. Hong;J. H. Han;Lee, S. J.;S. Hahn
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제5권3호
    • /
    • pp.30-33
    • /
    • 2003
  • 1MVA high temperature superconducting (HTS) transformer with double pancake windings made of BSCCO-2223 HTS tapes was designed and manufactured. And prototype transformer with the same capacity was manufactured also. The each rated voltage of the HTS transformer is 22.9 kV and 6.6 kV. Four parallel BSCCO-2223 HTS tapes were wound in the double pancake windings of low voltage side. In order to distribute the currents equally in each HTS tapes, the three times transposition was performed between the double pancake windings. The windings of prototype transformer were wound using copper tape with the same size as BSCCO-2223 HTS tape. The core of the transformer was designed and manufactured as a shell type core made of laminated silicon steel plate. The several characteristics tests for the prototype transformer were performed in liquid nitrogen and insulation tests were accomplished also.

2[MVA] 배전용 몰드변압기의 글라스넷 형상 최적설계 (Optimum Design of Glass Net in 2[MVA] Mold Transformer)

  • 전문호;김창업
    • 조명전기설비학회논문지
    • /
    • 제25권1호
    • /
    • pp.107-112
    • /
    • 2011
  • In this paper, the optimum design of the glass net shape was studied to minimize the electric field of mold transformer. The glass net is used for reinforcement in structure between coils and epoxy, but it can cause to increase the electric field and the partial discharge. Therefore, the optimum design of glass net is required to minimize the electric field. In this paper, the objective function was approximated by using response surface method and then Zoom-in method was used for optimal design to minimize the electric field. The electric field was analysed using finite element method for each shape of glass nets.

전위를 고려한 고온초전도 변압기용 병렬권선의 설계 및 제작 (Design and Fabrication of Parallel Wounded HTS Transformer Windings with Transpositions)

  • 김우석;김성훈;최경달;주형길;홍계원;한진호;박정호;송희석;한송엽
    • 한국초전도저온공학회:학술대회논문집
    • /
    • 한국초전도저온공학회 2003년도 학술대회 논문집
    • /
    • pp.203-205
    • /
    • 2003
  • Parallel wounded windings with BSCCO-2223 HTS tape for 1MVA HTS transformer were designed and prototype windings were fabricated in double pancake type. The parallel HTS tapes were transposed between the pancakes via non-superconducting joints because it is hard to make transpositions inside the pancake windings. The prototypes were wound using copper tape with same size as BSCCO-2223 tape, which will be used in 1MVA HTS transformer. The windings will be used for high voltage test and insulation test of the transformer Parallel HTS windings are going to be fabricated and tested for current distribution in near future.

  • PDF

벡터제어를 이용한 전동차 구동 시스템 (Development of Vector Controlled Traction System)

  • 배본호;설승기;김상훈;이일호;한성수
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 1999년도 추계학술대회 논문집
    • /
    • pp.288-295
    • /
    • 1999
  • This paper presents an application of vector control strategy for 1.2MVA IGBT traction drive for electric railway vehicle. The vector control requires the control of the phase and amplitude of output voltage vector[5]. But in case of traction system far railway vehicle, the one-pulse mode is used in order to utilize the link voltage fully[8]. So it is impossible to control the flux axis current and the torque axis current instantaneously and independently. So this paper proposes the vector control strategy with slip-frequency control at one-pulse mode. And precise switching technique between the two different control structures has been proposed. And the strategy was verified by experimental result with 1.2MVA IGBT inverter with four 210㎾ induction motors.

  • PDF

22.9kV, 50MVA급 초전도 전력케이블의 표준화 추진 방안 (The propulsive plan on the standardization in 22.9kV, 50MVA HTS power cable)

  • 최석진;이상진;심기덕;조전욱;이수길
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제10권1호
    • /
    • pp.48-51
    • /
    • 2008
  • The standardization on superconducting application techniques has been focused only in testing method or material itself, but, recently, it is actively proceeded by superconducting technical committee(TC) of international electro technical commission(IEC). In this paper, the standardization organization and its necessary process is introduced and the standardization technique for 22.9kV, 50MVA HTS power cable is prescribed. Throughout this research, it is possible to take priorities on the standardization technique in HTS power cable application. And moreover it can also contributes to the commercialization of HTS power cable.

22.9kV, 50MVA급 초전도 전력케이블 DC $I_c$ 측정에 관한 연구 (The study on the DC Ic measurement in the 22.9kV, 50MVA HTS power cable)

  • 최석진;이상진;심기덕;조전욱;장현만;이수길;손송호;황시돌
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제10권1호
    • /
    • pp.28-31
    • /
    • 2008
  • 22.9kV 50MVA HTS power cable has been developed and tested by Korea Electrotechnology Research Institute and LS Cable Company and it was supported by a grant from Center for Applied Superconductivity Technology of the 21st Century Frontier R&D Program. In this paper, DC Ic of 100m HTS cable which is installed at Kochang testing station was measured and analyzed. A measurement technique of DC Ic used by resistance and inductance removal method is established.

단위 인버터 병렬운전에 의한 발전소 해수펌크 적용 (Studies on the Application of Unit-inverter Parallel Operation to Sea-water Lift Pump in Power Plant)

  • 김수열;류홍우
    • 전력전자학회논문지
    • /
    • 제3권1호
    • /
    • pp.1-7
    • /
    • 1998
  • 발전설비의 대형화로 인하여 전력절감 문제가 크게 대두되었고, 팬이나 펌프를 부하 변화에 따라 속도제어하므로써 전기 에너지를 절약 할 수 있다. 1MVA급 단위 인버터 2대를 병렬 운전하여 대용량 2MVA GTO 인버터를 구현하였으며, 단위 인버터의 병렬 운전은 2대의 출력변압기 2차측 결선을 직렬 연결하여 구현하였다. 개발된 시스템은 제어반, 정류기반, 2대의 인버터반으로 구성되어 있으며, 이 시스템은 한국전력공사 성인천복합화력발전처 해수펌프 구동 유도전동기(6.6KV 1500KW)에 적용되어 전력절감에 기여하고 있다. 또 단위 인버터가 상호 180$^{\circ}$위상차를 갖도록 병렬 운전하므로써 고조파 성분을 저감시키면서 대용량을 구현하였다.

4병렬 팬케이크 권선을 사용한 1 MVA 단상 고온초전도 변압기의 설계 및 제작 (Design and Fabricate a 1 MVA Single Phase HTS Transformer with Four Parallel Pancake Windings)

  • 김우석;김성훈;이상진;최경달;주형길;홍계원;한진호;한송엽;송회석;박정호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 B
    • /
    • pp.723-725
    • /
    • 2003
  • The result of design and Partial fabrication of a 1 MVA single phase high temperature superconducting(HTS) transformer for power distributions are presented in this paper. The HTS windings are wound as double pancake windings which have advantages of uniform distribution of high voltage over the windings. the rated primary and secondary voltages are 22.9 kV and 6.6 kV respectively. Four HTS tapes are wound in parallel for secondary windings considering the rated currents of the transformer. The HTS windings will be cooled down to 65 K by natural convection of sub-cooled liquid nitrogen using a single-staged GM-cryocooler in order to make the stability of the HTS windings better. The iron core is designed as shell type and isolated from the liquid nitrogen by an FRP cryostat which have a room temperature bore. After the complete fabrication of the total HTS transformer system, performance test of the transformer will be carried out.

  • PDF

완전차폐시 50MVA급 HTS-케이블 샘플의 교류손실 (AC loss of a 50MVA HTS-cable sample in perfect shielding)

  • 마용호;이주영;진홍범;류경우;임지현;손송호;황시돌
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.296_297
    • /
    • 2009
  • 다층구조의conductor와 shield로 구성되는 HTS-cable의 교류손실 특성 연구를 위하여 2005년부터 실증시험 중에 있는 22.9kV, 50MVA, 100m급 KEPCO HTS-cable system에 사용된 케이블과 동일한 두개의 short-sample에 대하여DC 및 AC 특성을 실험적으로 조사하였다. KEPCO HTS-cable system에서처럼 shield전류를 conductor와 크기는 같게 하고 방향을 반대로하여 수주기동안 AC pulse전류를 인가했을 때, shield의 임계전류가 conductor보다 작음에도 불구하고 conductor-lead에 대하여 측정된 AC loss가 shield의 것과 비교하여 약 1.5배 큰 것을 알 수 있었다

  • PDF