• Title/Summary/Keyword: 화재 거동

Search Result 291, Processing Time 0.025 seconds

Ventilation Effects on Smoke Behavior in Rescue Station for Tunnel Fires (철도터널 화재시 구난역 내의 연기거동에 미치는 배연효과에 관한 수치연구)

  • Jang, Won-Cheol;Kim, Dong-Woon;Ryou, Hong-Sun;Lee, Seong-Hyuk
    • Proceedings of the KSR Conference
    • /
    • 2008.06a
    • /
    • pp.2130-2138
    • /
    • 2008
  • The present study investigates the ventilation effects on smoke spreading characteristics in railway tunnels with the rescue stations. Experiments were carried out for n-heptane pool fires with a square length 4 cm at different fire locations, and the heat release rates (HRR) were obtained by the measurement of burning rates. In addition, using the commercial code (FLUENT), the present article presents numerical results for smoke behavior in railway tunnels with rescue station, and it uses the MVHS (Modified Volumetric Heat Source) model for estimation of combustion products resulting from the fire source determined from the HRR measurement. As a result, it is found that smoke propagation is prevented successfully by the fire doors located inside the cross-passages and especially, the smoke behavior in the accident tunnel can be controlled through the ventilation system because of substantial change in smoke flow direction in the cross-passages.

  • PDF

The Behavior of Fire Damaged High Strength SRC Columns with Polypropylene Fiber (PP섬유 혼입 고강도 SRC 기둥의 화재 후 거동)

  • Choi, Eun-Gyu;Jung, Hye-Won;Shin, Yeong-Soo;Lee, Cha-Don;Kwon, Young-Jin
    • Proceedings of the Korea Concrete Institute Conference
    • /
    • 2006.11a
    • /
    • pp.33-36
    • /
    • 2006
  • The purpose of this paper is to investigate the structural behavior of fire damaged high-strength SRC columns with polypropylene fiber. When high-strength concrete is exposed to high temperature, spalling is occurred then it leads to decrease the capacity of members. Polypropylene fiber is used to reduce the spalling of the specimens and the distinction in the behavior after fire is observed. High-strength concrete specimens were exposed to high temperatures by the ISO 834 curve. Main experimental parameters were the ratio of the contained polypropylene fiver, heating time and type of loading. Reduction rate in residual strength and stiffness is observed for the mixing of PP fiber, the heating time and eccentricity of loading.

  • PDF

A Study on the Analysis of the Combustion Behavior and Carbonization Pattern of Vinyl Flooring on Which a Real-Scale Combustion Test Was Performed (실물 연소 실험이 진행된 비닐장판의 연소거동 및 탄화 패턴 해석에 관한 연구)

  • Joe, Hi-Su;Choi, Chung-Seog
    • Fire Science and Engineering
    • /
    • v.33 no.6
    • /
    • pp.120-125
    • /
    • 2019
  • A real-scale combustion test was conducted on a vinyl flooring in a divided space, with 50 mL of an inflammable liquid sprayed on it. The combustion behavior of the vinyl flooring was studied in real time, and the carbonization patterns of the surface and cross-sections of the carbonized vinyl floor were analyzed. When the flame ignited by gasoline reached its peak, a continuously flaming region, intermittent flaming region, plume region, etc., were formed. The combustion of 50 mL gasoline on vinyl flooring took 26 s, and a halo pattern was observed. This test involved spraying kerosene evenly on the vinyl flooring and attempting to ignite the flooring using a gas torch, which failed. After the combustion of the vinyl flooring was complete, its carbonized range was measured to be 600 mm in length and 380 mm in width, and the carbonized area was 1000 ㎟. Heat transformed the coated layer of surface of the carbonized vinyl flooring into a carbonized layer, which became harder. The analysis of cross-section of the boundary surface of the carbonized vinyl flooring using a stereoscopic microscope showed that the vinyl flooring was bubbling, and that the white boundary layer at the bottom of the coated layer had disappeared.

Radiation Effects on the Ignition and Flame Extinction of High-temperature Fuel (고온연료의 점화 및 화염 소화특성에 미치는 복사효과)

  • Kim, Yu Jeong;Oh, Chang Bo;Choi, Byung Il;Han, Yong Shik
    • Fire Science and Engineering
    • /
    • v.27 no.6
    • /
    • pp.50-56
    • /
    • 2013
  • The radiation effects on the auto-ignition and extinction characteristics of a non-premixed fuel-air counterflow field were numerically investigated. A detailed reaction mechanism of GRI-v3.0 was used for the calculation of chemical reactions and the optically-thin radiation model was adopted in the simulations. The flame-controlling continuation method was also used in the simulation to predict the auto-ignition point and extinction limits precisely. As a result, it was found that the maximum H radical concentration, $(Y_H)_{max}$, rather than the maximum temperature was suitable to understand the ignition and extinction behaviors. S-, C- and O-curves, which were well known from the previous theory, were identified by investigating the $(Y_H)_{max}$. The radiative heat loss fraction ($f_r$) and spatially-integrated heat release rate (IHRR) were introduced to grasp each extinction mechanism. It was also found that the $f_r$ was the highest at the radiative extinction limit. At the flame stretch extinction limit, the flame was extinguished due to the conductive heat loss which attributed to the high strain rate although the heat release rate was the highest. The radiation affected on the radiative extinction limit and auto-ignition point considerably, however the effect on the flame stretch extinction limit was negligible. A stable flame regime defined by the region between each extinction limit became wide with increasing the fuel temperature.

Effect of Aggregate on Mechanical Properties of Ultra-High Strength Concrete Exposed to High Temperature (고온을 받은 초고강도 콘크리트의 역학적 특성에 관한 골재의 영향)

  • Kim, Young-Sun;Choi, Hyoung-Gil;Ohmiya, Yoshifumi;Kim, Gyu-Yong
    • Journal of the Korea Concrete Institute
    • /
    • v.23 no.4
    • /
    • pp.431-440
    • /
    • 2011
  • Concrete structures exposed to fire produce changes in their internal structure, resulting in their service life reduction due to the deterioration of its strength and performance capacity. The deterioration level are dependent on the temperature, exposure time, concrete mix proportions, aggregate property, and material properties. This study was performed to evaluate the thermal behavior of ultra-high strength concrete for the parameters of water to cement ratio (compressive strength), fine to total aggregate ratio, and maximum coarse aggregate size. At room temperature and $500^{\circ}C$, tests of ultrasonic pulse velocity, resonance frequency, static modulus of elasticity, and compressive strength are performed using ${\varnothing}100{\times}200\;mm$ cylindrical concrete specimens. The results showed that the residual mechanical properties of ultra-high strength concrete heated to $500^{\circ}C$ is influenced by variation of a water to binder ratio, fine to total aggregate ratio, and maximum coarse aggregate size.

A Study on the Behaviour of Smoke Spread Caused by Vehicle Fire in a Road Tunnel (터널 내 차량 화재에 따른 연기 확산 거동에 관한 연구)

  • Yoon, Yong-Kyun;Ju, Eun-Hye
    • Tunnel and Underground Space
    • /
    • v.22 no.5
    • /
    • pp.365-372
    • /
    • 2012
  • This paper aims to evaluate the effects that presence, installation number and capacity of ventilation vent and presence of multiple fire sources have on the behaviour of smoke temperature induced by vehicle fire in road tunnel. Six types of scenarios were assumed and FDS was ran to simulate them. As the number of ventilation vents increases, the smoke temperature are calculated to be reduced, but it is shown that effects exerted by two ventilation vents are almost similar to ones by three ventilation vents. Capacity of ventilation vent has a greater impact on the reduction of smoke temperature than installation number of ventilation vents. Smoke temperatures computed for all scenarios except for scenario No. 1 (without ventilation vent) and scenario No. 6 (with multiple fire sources) above fire source are analyzed to be under $400^{\circ}C$ and it means that the radiation of smoke layer above fire source doesn't induce the ignition of materials around fire source.

Study on Explosion Behavior of Air-born Rice Bran Dusts according to Ignition Energy (점화에너지 변화에 따른 쌀겨분진의 폭발 거동에 관한 연구)

  • 김정환;김현우;현성호;백동현
    • Fire Science and Engineering
    • /
    • v.13 no.2
    • /
    • pp.26-32
    • /
    • 1999
  • We had investigated combustion pro야$\pi$ies of rice bran dusts. Decomposition of rice bran d dusts with temperature were investigated using DSC and the weight loss according to t temperature using TGA in order to find the thermal hazard of rice bran dusts, and the p properties of dust explosion in variation of their dust with the same particle size. Using H Hartman's dust explosion apparatus which estimate dust explosion by electric ignition after m making dust disperse by compressed air, dust explosion experiments have been conducted by v varying concen$\sigma$ation and size of rice br뻐 dust. According to the results for thermodynamic stability of rice bran dust, there are little change of initiation temperature of heat generation 때d heating value for used particle size. But i initiation temperature of heat generation decreased with high heating rate whereas d decomposition heat increased with particle size. Also, the explosion pressure was increased as t the ignition energy increased and average maximum explosion pressure was 13.5 kgv'cnt for 5 BJ/60 mesh and 1.5 뼈Ie미 dust concentration.

  • PDF

A Study on the Fire Resistance Performance of Wood Framed Lightweight Wall which Including a Middle Lintel (중인방을 포함한 목골조 경량벽체의 내화성능에 관한 연구)

  • Yeo, In-Hwan;Cho, Bum-Yean;Min, Byung-Yeol;Yoon, Myung-O
    • Fire Science and Engineering
    • /
    • v.25 no.3
    • /
    • pp.91-98
    • /
    • 2011
  • This study is about fire resistance performance of wood framed lightweight wall including a middle lintel as a traditional wall form in Korea. The target wall is non-loadbearing system which constructed with $38{\times}89$ mm ($2"{\times}4"$) wood frame and fireproof gypsum board covering, including a middle lintel made of $150{\times}150$ mm section glue-laminated timber. As a test results, all specimens have showed fire resistant performance over 90 minutes and tests were maintained until flame occuring on Specimen-l, 2, 3 at 91 min, 97 min and 98 min respectively. Fire resistance of the heat side gypsum board was 45 minutes and charring rate of middle lintel was equivalant with that of usual timber. The wood stud inside wall system showed relatively quick combution characteristic when exposed to high temperature with no temperature rising delaying time caused by moisture evaporation because of the dehydration preceded during the early period of fire side gypsum board resist to heat.

Measurement of Autoignition Temperature of n-Propanol and Formic acid System (n-Propanol과 Formic acid계의 최소자연발화온도의 측정)

  • Cho, Young-Se;Ha, Dong-Myeong
    • Fire Science and Engineering
    • /
    • v.27 no.5
    • /
    • pp.64-69
    • /
    • 2013
  • The autoignition temperatures (AITs) of solvent mixture was important index for the safe handling of flammable liquids which constitute the solvent mixtures. This study measured the AITs and ignition delay time for n-propanol and formic acid system by using ASTM E659 apparatus. The AITs of n-Propanol and Formic acid which constituted binary system were $435^{\circ}C$ and $498^{\circ}C$, respectively. The experimental AITs of n-propanol and formic acid system were a good agreement with the calculated AITs by the proposed equations with a few A.A.D. (average absolute deviation). And n- Propanol and formic acid system was shown the minimum autoignition temperature behavior (MAITB).

A Combustion Characteristics of Attached Jet Flame under the Regular Oscillation (규칙적인 진동 하에서 노즐 부착된 제트화염의 연소특성)

  • Kim, Dae-Won;Lee, Kee-Man
    • Fire Science and Engineering
    • /
    • v.23 no.1
    • /
    • pp.55-62
    • /
    • 2009
  • A general combustion characteristics of forcing nonpremixed jet in laminar flow rates have been conducted experimentally to investigate the effect of forcing amplitude with the resonant frequency of fuel tube. There are two patterns of the flame lift-off feature according to the velocity increasing; one has the decreasing values of forcing amplitude on the lift-off occurrence when a fuel exit velocity is increasing, while the other has the increasing values. These mean that there are the different mechanisms in the lift-off stability of forced jet diffusion flame. Especially, the characteristics of attached jet flame regime are concentrically observed with flame lengths, shapes, flow response and velocity profiles at the nozzle exit as the central figure. The notable observations are that the flame enlogation, in-homing flame and the occurrence of a vortical motion turnabout have happened according to the increase of forcing amplitude. It is understood by the velocity measurements and visualization methods that these phenomena have been relevance to an entrainment of surrounding oxygen into the fuel nozzle as the negative part of the fluctuating velocity has begun at the inner part of the fuel nozzle.