• Title/Summary/Keyword: 토출각도

Search Result 18, Processing Time 0.038 seconds

Study on Indoor Flow According to Vane Angle of Square Ceiling Type Louver Diffuser (사각 천장형 루버 디퓨저의 토출 각도에 따른 실내유동에 관한 연구)

  • Jang, Heon-Deock;Lee, Dae-Hui;Lee, Jin-Ho
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.36 no.7
    • /
    • pp.683-687
    • /
    • 2012
  • The purpose of this paper is to numerically study the characteristics of the indoor air flow of a square ceiling type diffuser according to the vane angle and flow rate. The CFX of ANSYS 13.0 was used for the CFD tool. The size of the room is $6m(X){\times}6m(Y){\times}2.7m(Z)$. The exhaust diffuser was positioned diagonally to the supply diffuser. This diffuser was designed to have many holes, so the air supply had long throw patterns with low velocity decay. The characteristics of the indoor air flow was studied at volume flow rates of 5.1 CMM and 7.4 CMM, and a vane angle from $30^{\circ}$ to $60^{\circ}$, every $10^{\circ}$.

Performance Variation of the Air Curtain for Various Discharge Angles in Feating Space (난방공간에서 에어커튼의 토출각도 변화에 따른 성능 변화)

  • Sung, Sun-Kyung
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.22 no.2
    • /
    • pp.57-63
    • /
    • 2010
  • Air curtains are widely used for gates of shopping mall, warehouse, cold stores and refrigerated display cabinets. The purpose of the air curtain is to reduce the infiltration of outdoor air and heat loss from the air conditioning space to ambient air. The discharge angle of air curtain is very important as the sealing efficiency is affected by it. This paper presents a performance of single jet air curtain in heating space when the discharge angle of nozzle changes. A numerical simulation is used to study the influence of various parameters on the efficiency of the downward-blowing air curtain device which is installed inside of the wall above the door. The performance of the air curtain is evaluated by sealing efficiency which provides the assessment of the energy savings. A condition of discharge angle that has the highest sealing efficiency is proposed.

A Study on High Viscosity Phosphor Dispensing Process for Implementation of High-Efficiency White LED (고효율 백색 발광다이오드 구현을 위한 고점도 형광체 정량 토출 공정 연구)

  • Yang, Young-Jin;Kim, Hyung-Chan;Ko, Jeong-Beom;Yang, Bong-Su;Dang, Hyun-Woo;Doh, Yang-Hoi;Cho, Kyung-Ho;Choi, Kyung-Hyun
    • Clean Technology
    • /
    • v.20 no.2
    • /
    • pp.97-102
    • /
    • 2014
  • Currently various studies are underway for dispensing high-viscosity phosphor. These studies have reported limitations and challenges in the dispensing process. The discharged amount of phosphor was approximately the same each time which is important for the implementation of high-efficiency white LED technology. This paper present high-viscosity phosphor dispensing process for white LED implementation by using electrostatic printing technology. The voltage controlled DOD (Drop-On-Demand) discharge experiment was studied to determine angle of drop meniscus at nozzle and dot diameter. With increase in Discharge voltage, the discharge angle of meniscus increased while dot diameter decreased. Therefore it can be concluded that we can control the discharge rate by controling the discharge angle of meniscus.

A Study for Numerical Analysis of Flow Variation on Low Pressure Fuel Pump Fluid using Excavator Engine (굴삭기 엔진용 저압연료펌프 유체의 유동변화에 대한 수치해석적 연구)

  • Lee, IL Kwon;Kim, Seung Chul
    • Journal of the Korean Institute of Gas
    • /
    • v.19 no.6
    • /
    • pp.47-53
    • /
    • 2015
  • This paper is to study applying for numerical analysis method for flow field, velocity and pressure of fuel on the low pressure pump using excavator. The pressure distribution of fuel pump certified the linear variation according to rotation angle of rotor. Especially, it knew the fact that the pressure in rotation angle $40^{\circ}$ appeared high outlet and low inlet of fuel pump. Also, this range angle can seek the fact that the leakage flow and velocity are the most increasing. And the more rotor rotation of fuel pump, the more mean outlet flow rate increased in linear. Whenever the gap size decrease with rotor and housing, the discharge flow rate could seek the approaching 0.0712kg/s that consider with theory discharge flow rate calculated from displacement between rotor gear and idle gear.

A Study on the Burner Structure for Efficient Improvement of Steam Reforming (수증기 개질 반응기의 효율 향상을 위한 버너 구조 연구)

  • Sung, Bong-Hyun;Han, Jae-Chan;Shin, Jang-Sik;Lee, Seung-Young;Yang, Hye-Kyong;Shin, Seok-Jae;Park, Jong-Won;Kim, Doo-Hoon
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2007.06a
    • /
    • pp.20-23
    • /
    • 2007
  • 가정용 연료전지 수소 공급용 연료변환 장치는 LNG, LPG를 이용하여 수소를 제조하는 수증기 개질과 제조된 합성가스의 정제공정으로 저온/고온 전이 반응 및 선택적 산화 반응을 포함하게 된다. 이중 전체 연료변환 장치 효율은 공정중의 유일한 흡열 반응인 수증기 개질 반응기 구조와 반응열 공급용 버너에 의해 결정된다. 반응열 공급용 버너의 형식, 구조 등의 변수를 통해 본 연구진에 의해 개발된 반응구조의 최적 열원 공급 방식을 산출하고자 하였다. 이를 위하여 본 연구에서는 원통형 개질 반응기에 적용 가능한 버너의 구조, 토출 각도, 토출구의 수 등의 버너 설계 변수가 버너의 성능의 미치는 영향에 대하여 연구하였다. 연구에 사용된 버너는 적용 연료의 혼합 특성을 증가시키기 위해 혼합공간을 충분히 유지 하였으며, 버너의 구조와 연소용 기체의 토출각 및 토출구의 위치 변화를 통한 불꽃의 형태를 변화 시켜 반응기 내의 온도 분포 특성을 비교 분석하였으며, 분석 결과에 의해 원통형 개질 반응기에서 최대 효율을 가지는 버너의 구조로부터 수증기 개질 반응을 평가하였다.

  • PDF

Numerical Study on Variations in the Sealing Performance of Air Curtains in Large-Scale Factory Opening Considering Various Design Factors (대형 공장 개구부용 에어커튼의 설계 인자에 따른 차단 성능 변화에 대한 전산해석 연구)

  • Moon, Jongmin;Rhee, Gwang Hoon
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.39 no.8
    • /
    • pp.703-711
    • /
    • 2015
  • In large-scale factories, there are usually openings in the building to increase the efficiency of workers. However, if the factory is heated during winter, openings significantly increase the heating load. Therefore, there is a need for air curtains to be installed at the top of openings in factories to reduce the heating load due to the cold air entering from outside. The main design variables of these air curtains are the discharge angle, speed, and temperature, etc. While there have already been many studies focusing on these design variables, the distance from the opening and the width of the discharge have not been studied even though they also affect the sealing performance. As a result, when the distance from the opening decreases and the width of the discharge increases, we realize an optimum air curtain performance. However, if the distance from the opening is about 1.5 m, by adjusting the discharge angle and the distance from the opening, the sealing performance of the air curtain is improved by 13.7%.

Evaluation of Indoor Thermal Comfort for Ceiling Type System Air-Conditioner with Various Discharge Angles (천장형 시스템 에어컨의 토출방향 변화에 따른 실내 열쾌적성 평가)

  • Lee, Jin-Hyung;Kim, You-Jae;Choi, Weon-Seok;Park, Sung-Kwan;Youn, Baek;Kim, Youn-Jea
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.1180-1185
    • /
    • 2006
  • Modern people spend most of time at indoor space, such as office or classroom. Especially, occupants are exposed to the airtight indoor air quality (IAQ) for a long time, At present, many studies on the air-conditioning systems are more focused on the individual thermal comfort than the thermal efficiency due to increase of the concern of health. There are several factors which are influenced thermal comfort, such as temperature, humidity, convection and air movement, etc. Also, the individual factor, such as age, gender, Physical constitution and habit, should be considered. The 4-way cassette type air conditioner is known to bring out better performance about thermal comfort than the traditional one. This study is performed on the higher ceiling environment than the common buildings or classrooms. Also, this study analyzed on the Indoor thermal comfort by diffusing direction of 4-way cassette air conditioner with various discharge angles, $45^{\circ},\;50^{\circ},\;55^{\circ}$ and $60^{\circ}$. Using a commercial code, FLUENT, three-dimensional transient air thermal flow fields are calculated with appropriate wall boundary conditions and standard $k-{\epsilon}$ turbulence model. Results of velocity and temperature distributions are graphically depicted with various discharge angles.

  • PDF

Thermal Environment Analysis by the Diffusion Direction with Ceiling Type Air Conditioner of the Classroom (학교 교실의 천장형 에어컨 토출각도에 따른 온열환경 해석)

  • AHN, Chul-Lin;KIM, Dong-Gyue;KUM, Jong-Soo;PARK, Hee-Ouk;CHUNG, Yong-Hyun
    • Journal of Fisheries and Marine Sciences Education
    • /
    • v.17 no.2
    • /
    • pp.145-154
    • /
    • 2005
  • It is necessary to develop new air-conditioning method which can be satisfied individual separated space and request of occupants. The indoor thermal environment and flow field are investigated both experimentally and numerically. This study concentrated on analysis of indoor thermal environment by diffusion direction of ceiling type air conditioner of the classroom. The velocity and temperature distribution of air in the room calculated by 3-dimensional method, which include the effect of insulation of the building and outdoor state. This analysis shows that optimum diffusion direction is $30^{\circ}$ to increase thermal comfort in winter and optimum diffusion direction is $15^{\circ}$ to increase thermal comfort in summer.

A Study on the Optimum Design for the Discharge Port of a R410A Rotary Compressor (R410A 로타리 압축기의 토출구 최적설계에 관한 연구)

  • 김현진;이태진;박신규;황인수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.12
    • /
    • pp.1245-1254
    • /
    • 2001
  • For a R410A-rolling piston type rotary compressor model which was modified by reducing the cylinder height and shaft eccentricity from R22-compressor version, numerical simulation has been carried out and simulation results have been found to be compared fairly well with those of measurements. EER of this first version of R410A compressor was 4.8% lower than that of R22 compressor. To improve the performance of the R410A compressor model, parametric study on the design parameters related to the discharge port system has been performed by using the numerical simulation program, and optimum conditions for the highest EER have been obtained with the aid of Taguchi method. With the optimized discharge port configuration, EER has been improved by 1.7%.

  • PDF