• Title/Summary/Keyword: 차압 해석

Search Result 84, Processing Time 0.035 seconds

A Numerical Study Of Flow Control Valve to Flow Characteristics by Pressure Difference for Hydrogen Station (수소충전소용 유량제어 밸브의 차압에 따른 유동특성에 대한 수치해석적 연구)

  • Nam, Chung-Woo;Kim, Rak-Min;Kim, Hyun-Hyo
    • Journal of the Korean Institute of Gas
    • /
    • v.25 no.2
    • /
    • pp.28-33
    • /
    • 2021
  • With the recent growing interest in eco-friendly cars, as interest in eco-friendly cars increases, interest and purchase of hydrogen fuel cell vehicles that do not emit pollutants are increasing. Recently, the government is supporting the expansion of hydrogen charging station and localization of core parts according to the government's hydrogen energy dissemination policy. In this study, the flow characteristics of the hydrogen flow control valve were investigated. As the differential pressure increases, the mass flow rate and flow coefficient tend to be different from the volume flow rate. And it was confirmed that it affects the hydrogen temperature due to the nozzle effect in the bottleneck section, and the change in density affects the mass flow rate.

월성원자력발전소 비상노심냉각계통의 수격현상 해석

  • 이중섭;오광석;김선철;오종필;김도현
    • Proceedings of the Korean Nuclear Society Conference
    • /
    • 1996.05b
    • /
    • pp.67-72
    • /
    • 1996
  • 수격현상(Waterhammer)으로 인한 과도압력하중은 월성원자력발전소 비상노심냉각계통 (Emergency Core Cooling System : ECCS) 설계의 주요 고려사항이다. 비상노심냉각계통은 특수안전계통으로서 냉각재상실사고(Loss of Coolant Accident : LOCA)후 일차열수송계통을 다시 채워주고 핵연료 손상을 막기위해 노심으로부터 잔열 및 붕괴열을 제거한다. 일차열수송계통으로의 비상냉각수 주입은 고압주입, 중압주입, 저압주입 3 단계로 주입된다. 과도압력이 발생될 것으로 예상되는 고압주입과 중압주입에 대한 6가지 사례들이 ECCS의 배관과 지지대 설계를 위해 고려되었다. 모든 사례에 대한 비상노심냉각계통의 과도압력 현상은 PTRAN 코드에 의해 해석 되었고 해석된 최고과도압력은 설계압력보다 작음을 알게 되었다. 모든 사례의 최고압력과 최고차압은 비상노심냉각계통 배관 및 지지대 설계를 위한 응력해석 자료로서 사용될 것이다.

  • PDF

Performance Analysis of Emergency Shut-Off Safety Valve (긴급차단용 안전밸브의 성능해석)

  • Song, H. Y.;Park, K. A.;Ko, S.
    • 유체기계공업학회:학술대회논문집
    • /
    • 2001.11a
    • /
    • pp.413-418
    • /
    • 2001
  • Emergency shut-on valve was developed to shut off natural gas at the front of a gas meter in the house. The shut-off flow rate and differential pressure of this valve was controlled by adjusting the distance between the spool and magnet. Also the spool shape was an important factor in the performance of this valve. The experimental and computational results will be useful for the design having better performance.

  • PDF

Basic Study on the Proportional Control System Development of Air Supply Damper (급기댐퍼의 비례제어시스템 개발에 관한 기초 연구)

  • Lee, Dong-Myung;Yu, Byung-Ku
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2012.04a
    • /
    • pp.97-100
    • /
    • 2012
  • 본 연구는 비례제어시스템의 개발에 관한 기초 연구로서 건축물 화재에서 연기이동의 원인이 되는 압력수두손실, 굴뚝효과, 바람의 영향 등과 피난시 과압방지를 효율적으로 제어하여 제연구역에 균일한 허용차압을 유지시킬 수 있는 제연구역 급기댐퍼의 비례제어시스템을 개발하여 화재실로부터 발생된 연기가 다른 공간으로 침입 확산되는 것을 방지하고 피난안전성을 확보하여 인명과 재산피해를 최소화하는 것이며, 비례제어시스템의 로직 정립과 공학 해석에 의한 시스템 설계에 관한 것이다.

  • PDF

Flow Analysis of the Oxidizer Manifold for a Liquid Rocket Combustor using OpenFOAM (OpenFOAM을 이용한 액체 로켓 연소기의 산화제 매니폴드 내 유동 해석)

  • Joh, Mi-Ok;Han, Sang-Hoon;Kim, Seong-Ku;Choi, Hwan-Seok
    • Journal of the Korean Society for Aeronautical & Space Sciences
    • /
    • v.40 no.9
    • /
    • pp.781-788
    • /
    • 2012
  • Flow in the oxidizer manifold of a liquid rocket combustor has been analysed using an open source CFD toolbox, OpenFOAM. The applicability of OpenFOAM to the problems with complex geometries involving porous media zones for simulating the pressure drop induced by the injectors has been evaluated by performing turbulent, incompressible steady-state flow analysis. The usefulness and applicable area of the OpenFOAM as a design evaluation and analysis tool will be confirmed and enlarged by further evaluation with various computational cases representing major physical phenomena in rocket combustion devices.

The Influence of Zoning at Shafts of Super-tall Buildings on the Stack Effect and Stairwell Pressurization (초고층건물 샤프트의 수직구획이 연돌효과 및 급기가압 성능에 미치는 영향)

  • Kim, Beom-Kyue;Kim, Hak-Jung;Yeo, Yong-Ju;Leem, Chae-Hyun;Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.26 no.5
    • /
    • pp.92-98
    • /
    • 2012
  • This study analyzed the effect of zoning on the distribution of pressure differentials caused by stack effect and air pressurization in a center core type of 80 story super-tall building. The results showed that maximum pressure difference more than 250 Pa can be generated by stack effect without zoning. Zoning of stairwell only resulted in 10 Pa reduction of maximum pressure difference, however, zoning of both stairwell and EV shaft especially at the same floor revealed 50 % reduction in stack effect. It was also analysed that the minimum required air flow rate occurred when the stairwell temperature reached 50 % of temperature difference between indoor and outdoor.

A Numerical Study on the Stack Effect and the Neutral Plane of a Single Simplified Shaft (단일 단순수직통로의 연돌효과와 중성대에 관한 수치해석 연구)

  • Jeon, Heung-Kyun;Choi, Young-Sang;Choo, Hong-Lok
    • Fire Science and Engineering
    • /
    • v.23 no.5
    • /
    • pp.143-152
    • /
    • 2009
  • The numerical analyses for each single simplified shaft with three type openings were carried out by using computational fluid dynamics model for the calculation of the pressure difference and the location of the neutral plane and the visualization of stack effect. As the height of shaft heighten, the pressure difference of stack effect is much deviated against the theoretical value. For the Type A models shorter than 30 m height of shaft and the Type B models longer than 30m, the simulation results for the location of the neutral plane are well agreed to the theoretical values with 5% less deviations just after the beginning of simulation (t = 10s). For the Type B models longer than 30m with multiple openings, therefore, it is possible to calculate the location of the neutral plane by using a CFD model. The phenomenon of the air flow of stack effect can be easily understood with the visualization of stack effect.

Design and Evaluation of Vaned Pipe Bends of Liquid Propellant for Satellite Launch Vehicles (소형위성 발사체용 액체 추진제 곡관 배관 설계 및 유동 성능 해석)

  • Lee Hee Joon;Han Sang Yeop;Ha Sung Up;Kim Young Mog
    • Journal of the Korean Society of Propulsion Engineers
    • /
    • v.9 no.1
    • /
    • pp.53-60
    • /
    • 2005
  • The use of pipe-bends brings about non-uniform flows at the exit of them due to the velocity difference between inner and outer flows inside the bend. These phenomena may cause turbopump of satellite launch vehicle to run off-design and reduce its efficiency, and also introduce unstable influx of propellants to engine manifold after passing through a turbopump. In order to improve the uniformity of flow at the bend exit, certain turning vanes are set up in the bend pipe normally. Correspondingly the design is an $90^{\circ}\;and\;45^{\circ}$ bend pipes that incorporate with the maximum three turning vanes. All designs were analyzed with numerical analysis by solving the Navier-Stokes equations in three dimensions in case of each respective fuel and oxidizer. Evaluations of the vaned pipe bends designs were accomplished by the velocity magnitude distributions and the predicted pressure drops. We could find that the more vaned bend pipe and larger angle pipe under consideration effectively, the more uniform velocity magnitude of the bend and pressure losses.

Numerical Analysis on Features of Airflow through Open Door in Pressure Differential System (급기가압 제연시스템의 방연풍속 형성특성에 대한 수치해석적 분석)

  • Kim, Jung-Yup;Rie, Dong-Ho;Kim, Ha-Young
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.463-468
    • /
    • 2008
  • The fact that the major cases of life casualties are from smoke in the fire accidents and the expected steep increase of skyscrapers, huge spaces, multiplexes and huge scaled underground spaces demand establishment of efficient smoke countermeasure. In pressure differential systems for smoke management, the speed of airflow through open door between accommodation and lobby should be maintained over 0.5m/s on the whole area of door to prevent smoke from infiltrate into evacuation root when the door is open for refuge. The numerical analysis on features of airflow through open door are carried out and the results are presented.

  • PDF