• Title/Summary/Keyword: 제트 화재

Search Result 70, Processing Time 0.021 seconds

Assessment of Thermal Protection Performance of Firefighting Garments for Hydrogen Jet Fire (수소제트화재에 대한 특수 방화복의 열 방호 성능시험 평가)

  • UNGGI YOON;BYOUNGJIK PARK;YANGKYUN KIM;SUNGWOOK KANG;OHKKUN LIM
    • Journal of Hydrogen and New Energy
    • /
    • v.35 no.3
    • /
    • pp.310-317
    • /
    • 2024
  • In this study, Aimed to develop technology to ensure the safety of firefighters responding to hydrogen incidents and to review the performance of protective super absorbent polymer (SAP) that could help maintain the thermal protection performance of equipment with protective properties. Tests were conducted, including bench-scale and full-scale thermal exposure tests, to review the protective performance of SAP using firefighting garments commonly used by firefighters. The results showed that without SAP application, 2nd degree burn areas were measured at 9.4%, and 3rd degree burn areas at 7.7%. In contrast, when SAP was applied, the percentage of 2nd degree burn areas decreased to 7% on the lower body, and there was no temperature rise causing 3rd degree burns. Therefore, it is expected that by applying SAP to the outer surface of firefighter garments, even under temporarily high temperature conditions such as hydrogen jet flames, thermal damage to firefighters could be protected for a certain period.

An experimental study on the smoke-spread region before reaching the critical velocity for the case of fires in tunnels employing longitudinal ventilation system (종류식 환기 시스템에서 임계속도 도달 전 스모크 확산 영역에 관한 실험적 연구)

  • Ki, Young-Min;Yoon, Sung-Wook;Yoon, Chan-Hoon;Kim, Jin
    • Tunnel and Underground Space
    • /
    • v.16 no.6 s.65
    • /
    • pp.526-535
    • /
    • 2006
  • An experimental study was carried out on a reduced scale tunnel model to grasp the behavioral feature of fire-induced smoke in the long tunnels. Based on Froude modeling, the 1/50 scaled tunnel model (20 m long) was constructed by acrylic tubes and paraffin gas was released inside the tunnel to simulate the 20 MW fire-induced smoke. me test results show, that after approximately 2 minutes of fire generation, was descended from the tunnel ceiling through the decrease of buoyancy, then it was symmetrically propagated about 90 meters for 4 minutes before jet fans were operated. The smoke was effectively controlled when the jet fans were operated and an air stream velocity was getting closed to reach a critical velocity (the minimum air velocity that requires to suppress the smoke spreading against the longitudinal ventilation flow during the tunnel fire situations). It was also found out that a range of smoke was spreaded about 3 meters from the origin of fire but the range was not propagated to the escape direction anymore. The early stage of the In operation, however, showed that the smoke was hardly controlled. It means that the operation of emergency ventilation system has many dangerous factors such as an intercepting breathing zone.

Hazard Distance from Hydrogen Accidents (수소가스사고의 피해범위)

  • Jo, Young-Do
    • Journal of the Korean Institute of Gas
    • /
    • v.16 no.1
    • /
    • pp.15-21
    • /
    • 2012
  • An analysis was completed of the hazards distance of hydrogen accidents such as jet release, jet fire, and vapor cloud explosion(VCE) of hydrogen gas, and simplified equations have been proposed to predict the hazard distances to set up safety distance by the gas dispersion, fire, and explosion following hydrogen gas release. For a small release rate of hydrogen gas, such as from a pine-hole, the hazard distance from jet dispersion is longer than that from jet fire. The hazard distance is directly proportional to the pressure raised to a half power and to the diameter of hole and up to several tens meters. For a large release rate, such as from full bore rupture of a pipeline or a large hole of storage vessel, the hazard distance from a large jet fire is longer than that from unconfined vapor cloud explosion. The hazard distance from the fire may be up to several hundred meters. Hydrogen filling station in urban area is difficult to compliance with the safety distance criterion, if the accident scenario of large hydrogen gas release is basis for setting up the safety distance, which is minimum separation distance between the station and building. Therefore, the accident of large hydrogen gas release must be prevented by using safety devices and the safety distance may be set based on the small release rate of hydrogen gas. But if there are any possibility of large release, populated building, such as school, hospital etc, should be separated several hundred meters.

Analysis of effect of hydrogen jet fire on tunnel structure (수소 제트화염이 터널 구조체에 미치는 영향 분석)

  • Park, Jinouk;Yoo, Yongho;Kim, Whiseong
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.23 no.6
    • /
    • pp.535-547
    • /
    • 2021
  • A policy to expand the hydrogen economy has been established in Korea and the supply of FCEV is being expanded to realize a hydrogen society. Therefore, the supply of FCEV is expected to increase rapidly, and a solution to respond to accidents of FCEV is required. In this study, an experimental study was conducted to analyze the effect of the hydrogen jet flame generated by a FCEV on the inner wall of the tunnel and the characteristics of the internal radiant heat. For the experiment, the initial pressure of hydrogen tank was set to 700 bar, and the injection nozzle diameter was set to 1.8 mm in order to make the same as the conditions generated in the FCEV. In addition, a tunnel fire resistance test specimen having the same strength as the compressive strength of concrete applied to general tunnels of 40 MPa was manufactured and used in the experiment. The results were analyzed for the separation distance (2 m and 4 m) between the hydrogen release nozzle and the tunnel fire resistance test concrete. As the result, the maximum internal temperature of the test concrete was measured to 1,349.9℃ (2 m separation distance), and the radiant heat around the jet flame was up to 39.16 kW/m2.

Retraction: A numerical study on the fire smoke behavior by operating the fire prevention system in tunnel-type structure (논문 취소: 터널형 구조물의 방재시설 가동에 따른 화재연기 거동에 관한 수치 해석적 연구)

  • Lee, Ho-Hyung;Choi, Pan-Gyu;Lee, Sang-Don;Heo, Won-Ho;Jo, Jong-Bok
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.21 no.1
    • /
    • pp.189-199
    • /
    • 2019
  • In this study, behaviors of fire smoke in the operation of disaster prevention facilities (smoke damper, jet fan) in a tunnel-type structure (soundproof tunnel) were investigated numerically and results of the investigation were compared and analyzed. Through the simulation and analysis, it was found that there was a significant change in the patterns of fire smoke between the opening of the ceiling of a fire vehicle and the closing, and it was shown that the critical temperatures of PC and PMMA, main materials of a soundproof tunnel were not exceeded. In addition, the simulation of installation intervals of smoke dampers showed that the maximum temperature of a soundproof tunnel without smoke dampers was $552^{\circ}C$ while it reached $405^{\circ}C$ when smoke dampers were installed at the installation interval of 50 m. The simulation of the operation of a jet fan showed that the maximum temperature of a soundproof tunnel without a jet fan was $549^{\circ}C$ while it reached only $86^{\circ}C$ when a jet fan was operating. Therefore, it is highly expected that they could create a favorable environment for evacuation and protection of soundproofing materials, and it would be necessary to promote basic studies on tunnels serving various functions and purposes.

미세현미경 성대수술시 Weerdar개폐식 후두경을 통한 고빈도 제트환기

  • 김현정;이국현;이상철;김광현
    • Proceedings of the KOR-BRONCHOESO Conference
    • /
    • 1995.04a
    • /
    • pp.92.1-92
    • /
    • 1995
  • Weerdar 개폐식 후두경은 Kleinsasser 후두경과 Killian-Lynch 현가 후두경의 장점을 혼합하여 개발한 것으로서 광학장치, 흡인관, injection cannula 등을 후두경에 부착할 수 있다. 그리고 후두경 내강에 injection cannula를 장치하여 고빈도 제트환기법, 고빈도 진동법, 고빈도 양압환기법을 시행할 수 있다. 이 경우 기관내 삽관을 배제하여 cannula선단이 성대 위에 위치하기 때문에 성대의 후교련까지 시야를 확보할 수 있고, 후두경 양측에 넓은 틈이 있기에 수술조작이 용이하며, 레이저 사용시에 화재의 위험을 최소로 할 수 있다. 이에 성대수술시 cannula를 통한 제트환기 중 시간 경과에 따른 활력징후, 동맥혈산소화, 이산화탄소의 배출상태 변화를 관찰하였다. 그 결과 수슬시간 30분까지 동맥혈 산소분압의 감소나 이산화탄소 축적은 관찰되지 않았기에 30분 이내의 성대수술시 기관내 삽관없이도 시행할 수 있는 안전한 마취관리의 한 방법이라 생각한다.

  • PDF

The Risk Assessment of Tunnel Fire Through Real Scale Fire Test (실물터널 화재실험을 통한 터널화재 위험도 평가)

  • 최준석;최병일;김명배;한용식;장용재;이유환;황낙순;김필영
    • Fire Science and Engineering
    • /
    • v.16 no.3
    • /
    • pp.71-76
    • /
    • 2002
  • The real scale tunnel fire tests are carried out for the first time in domestic range to assess the extent of risk in the tunnel fire. The tunnel dimension is 465 m in length, 9.2 m in width and 6.5 m in height. Gasoline pools with 0.25 MW∼2.5 MW size and a 1500CC passenger car are used as fire sources. Six jet fans are used to change the flow velocity inside the tunnel. Temperatures at total 86 points in the tunnel are measured to find the temperature distribution and smoke behavior in the real tunnel fire. In the experiment, it is examined that the important parameters to assess the extent of risk in tunnel fire such as back layering of smoke front, descending of smoke layer and the fire size of a real passenger car.

An Investigation of Hazard Distance in a Series of Hydrogen Jet Fire with the Hyram Tools (수소 누출 시 제트화재 피해 범위에 대한 분석)

  • KANG, BYOUNG WOO;LEE, TAECK HONG
    • Journal of Hydrogen and New Energy
    • /
    • v.28 no.2
    • /
    • pp.166-173
    • /
    • 2017
  • For commercialization of hydrogen refuelling station (HRS), we need to reduce the clearance distance for jet fire in the real entities in the HRS. Thus, we revisited the current regulations of clearance distance for jet fire in the law. The law in korea has been set up by replica of japan, not by our own scientific basis. Recently, sandia lab developed Hydrogen Risk Assessment Model (HyRAM) tools and we simulated a series of circumstances such as 10 to 850 bar with several leak hole sizes. In 850 bar with 10 mm diameter hole leak cases, it shows $4,981kW/m^2$ at 12 m separation from leak source and $1,774kW/m^2$ at 17 m separation from leak source. In 850 bar with 1 mm diameter leak hole, it shows $0.102kW/m^2$ at 12 m separation and $0.044kW/m^2$ at 17 m separation. Current law may be acceptable with 1 mm hole size with 850 bar.

The Effects of Parameters Affecting the Results in the Jet Fire for the Vapor Release Accident (증기누출사고의 영향평가에서 제트화재에 미치는 매개변수의 영향)

  • 조지훈;하정호;함병호;윤대건;김태옥
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1996.11a
    • /
    • pp.53-56
    • /
    • 1996
  • In order to propose the method of the consequence analysis for fire accidents by the heavy gas release and to obtain optimum conditions of parameter selections, the consequence analysis for jet fire by the accident of xylene vapor release were performed. And the effect and the sensitivity analysis of parameters affecting the consequence were investigated. Simulation results showed that important parameters affecting results of the xylene vapor release accident were mainly hole diameter, interested distance, wind speed, and so on. For the jet fire, the accident result and the sensitivity of thermal radiation were increased with the decrease of interested distance and the increase of hole diameters, and the accidental result was increased as the increase wind speed, but the sensitivity of thermal radiation was decreased.

  • PDF

A Study on the extent of damage from fire accident Caused by Unloading of LPG Bulk Lorry (LPG 벌크로리 충전중 화재사고에 따른 사고피해영향범위에 관한 연구)

  • Lee, Myoung Ho;Lee, Su-Kyung
    • Journal of the Korean Institute of Gas
    • /
    • v.19 no.2
    • /
    • pp.1-4
    • /
    • 2015
  • The study analyses secondary damage of surrounding facilities from the fire accident by Unloading of LPG Bulk Lorry. Potential risk and extent of damage from jet flame and radiation heat is estimated with PHAST-RISK v6.7 program of DNV. According to above study, supplies can predict the damage range from gas release by Unloading, and be able to respond quickly.