• Title/Summary/Keyword: 용융단선

Search Result 6, Processing Time 0.02 seconds

A Study on Bond Wire Fusing Analysis of GaN Amplifier and Selection of Current Capacity Considering Transient Current (GaN증폭기의 본드 와이어 용융단선 현상분석과 과도전류를 고려한 전류용량 선정에 대한 연구)

  • Woo-Sung, Yoo;Yeon-Su, Seok;Kyu-Hyeok, Hwang;Ki-Jun, Kim
    • Journal of IKEEE
    • /
    • v.26 no.4
    • /
    • pp.537-544
    • /
    • 2022
  • This paper analyzes the occurrence and cause of bond wires fusing used in the manufacture of pulsed high power amplifiers. Recently GaN HEMT has been spotlight in the fields of electronic warfare, radar, base station and satellite communication. In order to produce the maximum output power, which is the main performance of the high-power amplifier, optimal impedance matching is required. And the material, diameter and number of bond wires must be determined in consideration of not only the rated current but also the heat generated by the transient current. In particular, it was confirmed that compound semiconductor with a wide energy band gap such as GaN trigger fusing of the bond wire due to an increase in thermal resistance when the design efficiency is low or the heat dissipation is insufficient. This data has been simulated for exothermic conditions, and it is expected to be used as a reference for applications using GaN devices as verified through IR microscope.

Study on the Fire Investigation by Damaged Pattern Analysis of Incandescent Lamps (백열전구의 소손 패턴 분석을 통한 화재조사 연구)

  • Kim, Hyang-Kon;Kim, Dong-Woo;Moon, Hyun-Wook;Choi, Chung-Seog;Choi, Hyo-Sang
    • Fire Science and Engineering
    • /
    • v.22 no.5
    • /
    • pp.22-28
    • /
    • 2008
  • In this paper, we conducted experiments on damaged patterns of incandescent lamps by external stress, such as external flame or external impact. Glass bulbs were melted and filaments were evaporated by external flame when the bulbs were lit, and finally molten marks were recognized at the filaments. Also, there were some differences in absorption patterns of evaporated filament elements according to set-up directions, and evaporated filament elements were absorbed in lead-in wires, support, inside of glass. In case the bulbs were lit and they were damaged by external impacts, filament burned out. Filaments were not evaporated but melted. We expect that this results could be used to judge whether electric current flew through incandescent lamps or not in fire site.

An Accelerated Life Test for Burnout of Tungsten Filament of Incandescent Lamp (텅스텐 백열전구의 필라멘트 단선에 대한 가속수명시험)

  • Kim Jin-Woo;Shin Jae-Chul;Kim Myung-Soo;Lee Jae-Kook
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.29 no.7 s.238
    • /
    • pp.921-929
    • /
    • 2005
  • This paper presents an accelerated life test for burnout of tungsten filament of incandescent lamp. From failure analyses of field samples, it is shown that their root causes are local heating or hot spots in the filament caused by tungsten evaporation and wire sag. Finite element analysis is performed to evaluate the effect of vibration and impact for burnout, but any points of stress concentration or structural weakness are not found in the sample. To estimate the burnout life of lamp, an accelerated life test is planned by using quality function deployment and fractional factorial design, where voltage, vibration, and temperature are selected as accelerating variables. We assumed that Weibull lifetime distribution and a generalized linear model of life-stress relationship hold through goodness of fit test and test for common shape parameter of the distribution. Using accelerated life testing software, we estimated the common shape parameter of Weibull distribution, life-stress relationship, and accelerating factor.

The Study on Demage Mechanism Analysis of Insulation wire on the Line Post Insulator Using 22.9 kV-Y Overhead Distribution Line (22.9kV-Y 가공선로 지지애자에서의 절연전선의 손상 메커니즘 규명 연구)

  • Lee, Byung-Sung;Park, Chul-Bae;Na, Dong-Chae;Lee, Jae-Bong
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.2081_2082
    • /
    • 2009
  • 국내 가공배전 선로는 절연전선을 사용하고 있으며, 절연을 위해 세라믹 재질과 폴리머 재질의 지지애가가 사용되고 있다. 지지 애자 위의 전선은 진동에 따라 종방향 및 횡방향의 기계적 마찰력을 받고 있으며, 전기적으로 누설전류 및 서지의 영향을 받아 절연피복이 손상된다. 본 연구에서는 지지애자를 통해 흐르는 누설전류에 의해 전선이 손상되는 메커니즘을 규명하여 고장을 예방하고자 하였다. 절연전선은 손상된 부위에서 전류가 집중되어 내부 도체가 용융 단선되었다. 전선단선에 영향을 주는 열화 인자로서 지지애자의 표면 열화상태, 절연전선 피복 손상, 바인드선의 종류 등이 복합적으로 작용하였다.

  • PDF

A Study on the Ignition Characteristics of the Electric Mosquito Repellent Mat (화재사례를 통한 전자 모기향의 발화특성에 관한 연구)

  • Choi, Jae-Sung;Choi, Seung-Bok;Min, Se-Hong;Choi, Don-Mook
    • Fire Science and Engineering
    • /
    • v.23 no.5
    • /
    • pp.196-205
    • /
    • 2009
  • Electric mosquito repellent mats can be ignited by damage of cables, partial disconnection, overload. tracking and so on. In this study, we examined the structure of mosquito repellent mat, positive temperature coefficient(PTC) thermistor, used for heating element and phenomenological characteristics of remains, obtained on the scene of fires. After reappearance ignition test of PTC thermistors, we did comparison analysis them. And we could confine that the feature of heating plate and the shape of bursting were same.

A study on the cause Analysis and solution of an overheated NGR of the Main Transformer (변압기 중성점 접지리액터 과열원인분석 및 해소방안에 관한 연구)

  • Park, Gil-Soo;Park, Soo-Hong
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.6 no.2
    • /
    • pp.262-267
    • /
    • 2011
  • In the power system, the transformer's neutral earth reactor line 1 grounding failure may occur. By limiting the magnitude of the failure grounding current flow, it will aid to reduce the failure of the transformer. Consequently, this also may avoid the failure of the disconnection of the industrial insulator line that cause by melting. Besides, utilizing the decreasing circuit breaker or others related equipment can use to avoid the possibility of explosion of the transformer. If the failure happen during the operation of the power system, a huge interference will definitely may occur. Therefore, by installing the DONGBUSAN S/S #3M.Tr neutral earth reactor among TOP and BOTTOM BRACE part in the power system, the causes of the rising temperature and reason of the over-current flow that cause by over-current can be analyze.