Abstract

In the power system, the transformer's neutral earth reactor line 1 grounding failure may occur. By limiting the magnitude of the failure grounding current flow, it will aid to reduce the failure of the transformer. Consequently, this also may avoid the failure of the disconnection of the industrial insulator line that cause by melting. Besides, utilizing the decreasing circuit breaker or others related equipment can use to avoid the possibility of explosion of the transformer. If the failure happen during the operation of the power system, a huge interference will definitely may occur. Therefore, by installing the DONGBUSAN S/S #3M.Tr neutral earth reactor among TOP and BOTTOM BRACE part in the power system, the causes of the rising temperature and reason of the over-current flow that cause by over-current can be analyze.

본 연구에서 동부산S/S #3M.Tr 및 부민S/S #1,2M.Tr의 중성선에 설치 사용 중인 NGR 과열원인을 분석하고 해소방안을 제시하여 안정적 전력공급에 이바지하고자한다. 전력계통에 사용 중인 변압기 중성점 접지리액터는 1선지락 고장시 변압기에 유입되는 지락고장전류의 크기를 제한하여 변압기 고장을 감소시키는 역할을 하며 가공절연전선의 용융단선고장방지 일단접지변압기 폭발가능성방지 차단기 차단용량감소 등에 기여하는 설비로 고장발생시 전력계통운용에 막대한 지장을 초래할 수 있다. 따라서 전력계통에 설치 운전 중인 동부산S/S #3M.Tr 중성점 접지리액터 TOP&BOTTOM BRACE부의 온도 상승원인분석과 부민S/S 중성점 접지리액터에 흐르는 과전류로 인한 과열원인 분석을 하였다.

Keywords

References

  1. K. Komatsugi et al, "Harmonic Current Compensator Composed of Static Power Converter", PESC 86 RECORD, pp. 283-290, 1986.
  2. R. Dwyer, H. V. Nguyen, S. G. Ashmore, "C Filters for Wide-bandwidth Harmonic Attenuation with Low Losses", IEEE Power Engineering Society Meeting Conference, pp. 534-536, 12, 2000.
  3. (주)피에스디테크, "기술자료 PSD-H13", pp. 5-25, 2006.
  4. (주)보성파워텍, "건식접지리액터 과열원인 분석", pp. 3-8, 2007.