• Title/Summary/Keyword: 열 감지기

Search Result 96, Processing Time 0.036 seconds

An Analysis of False Alarm Threshold Value by Heat Detector Using Heat Release Rate (열방출률을 이용한 열감지기의 오동작 경계값 분석)

  • 홍성호;김두현
    • Fire Science and Engineering
    • /
    • v.17 no.3
    • /
    • pp.26-30
    • /
    • 2003
  • This paper presents a study on the analysis for false alarm of heat detector using HRR(Heat Release Rate). And it is represented to threshold value and domain of false alarm. The HRR threshold value of false alarm is calculated to use parameters obtained by small scale fire-experiment. The experiment is conducted to measure detector activation time and flame spread of wood cribs fire, etc. The results show that HRR threshold value of Fixed type detector is 20.24 kW and rate of rise type detector is 13.59 kW, respectively.

Sensing Characteristics of Fire Detectors in Railway Tunnel by Using Numerical Analysis (수치해석을 이용한 화재감지기 철도터널 화재 감지특성 연구)

  • Park, Won-Hee
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.11
    • /
    • pp.7964-7970
    • /
    • 2015
  • In enclosed areas such as railway tunnels, the heat and smoke generated by a fire can pose a tremendous risk to the life of passengers. To prevent or mitigate such scenarios, fire detectors are installed for early fire detection. This numerical study is preformed for establishing the method of detecting performance of fire detectors installed on railway tunnels. Numerical analysis are conducted using the fire dynamics simulator, developed by the NIST. The temperature of the tunnel walls is determined using the assumed exterior structure of the tunnel. In addition, the detection times of detectors installed at different locations in the tunnel are obtained for different sizes of the fire source, and the results are compared and analyzed.

The Development of Fire Detection System Using Fuzzy Inference (퍼지추론을 사용한 화재감지시스템 개발)

  • 홍성호;김두현;김상철;박양범
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2002.05a
    • /
    • pp.82-87
    • /
    • 2002
  • 지금까지의 화재감지시스템은 하나의 입력요소에 대하여 화재, 비화재로 판단하는 단순한 형태의 신호를 발신하여 하나의 요소로만 화재를 판단하여 왔다. 또한 기존의 화재감지시스템은 화재 시에 발생되는 열, 연기, 불꽃 등에 대하여 감지기회로에서의 미리 지정한 고정값과의 비교를 통하여 정해진 기준을 넘을 경우 화재로 판정한다. 그러나 고정값을 기준으로 신호를 발신하게 되어있는 화재감지기의 동작은 상황에 따라 불확실한 경우가 발생한다.(중략)

  • PDF

Automatic Fire Detector Spacing Calculation for Performance based Design (성능위주설계를 위한 화재감지기배치의 공학적연구)

  • Yoon, Myong-O;Park, Dong-Ha
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2010.10a
    • /
    • pp.180-189
    • /
    • 2010
  • 현재의 화재안전기준에서 규정하는 화재감지기의 배치방법은 면적에 따라 규정된 숫자를 적정하게 배치하는 수준이다. 이 기준은 과학적인 근거는 가지고 있지 못하다. 외국의 기준을 도입하여 그에 따라서 설치하고 있을 뿐이다. 소방시설을 설계하는 방법에는 화재안전기준과 같이 명문화 된 규정에 따르는 규범위주설계(Prescriptive-Based)와 화재역학, 구조역학, 재료역학, 유체역학, 열역학 등 공학적 지식을 바탕으로 하는 성능위주설계(Performance-Based Design)가 있다. 현재로서는 성능위주설계가 활성화 되지 않았지만, 최근 소방시설공사업법은 성능위주설계방법을 이용하여 소방시설을 설계 할 수 있도록 개정('05. 8. 4)되었으며 그 시행령('07, 1. 24)에서 성능위주설계를 적용할 특정소방 대상물의 범위를 정하고 있다. 이러한 시점에서 자동화재탐지설비의 화재감지기를 최적의 위치 및 거리에 설치하기 위하여 그에 대한 공식의 도입과 공식을 Software로 계산할 수 있도록 시뮬레이터를 제작하여 계산하고 규범위주설계에 따라 배치한 화재감지기의 상태와 비교 분석하며 향후 성능위주설계 방법으로서 정착시키기 위하여 연구를 시도하였다.

  • PDF

Technology for Real-Time Identification of Steady State of Heat-Pump System to Develop Fault Detection and Diagnosis System (열펌프의 고장감지 및 진단시스템 구축을 위한 실시간 정상상태 진단기법 개발)

  • Kim, Min-Sung;Yoon, Seok-Ho;Kim, Min-Soo
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.34 no.4
    • /
    • pp.333-339
    • /
    • 2010
  • Identification of a steady state is the first step in developing a fault detection and diagnosis (FDD) system of a heat pump. In a complete FDD system, the steady-state detector will be included as a module in a self-learning algorithm, which enables the working system's reference model to "tune" itself to its particular installation. In this study, a steady-state detector of a residential air conditioner based on moving windows was designed. Seven representative measurements were selected as key features for steady-state detection. The optimized moving-window size and the feature thresholds were decided on the basis of a startup-transient test and no-fault steady-state test. Performance of the steady-state detector was verified during an indoor load-change test. In this study, a general methodology for designing a moving-window steady-state detector for applications involving vapor compression has been established.

Development of the Low Power Stand-Alone Smoke and Heat Detector for the Reliability Improvement (신뢰성 개선을 위한 저전력 열연 복합식 단독경보형 감지기 개발)

  • Jee, Seung-Wook;Kim, Si-Kuk;Lee, Jae-Jin;Kim, Pil-Young;Lee, Chun-Ha
    • Fire Science and Engineering
    • /
    • v.26 no.1
    • /
    • pp.74-79
    • /
    • 2012
  • This study is described for development of the stand-alone smoke and heat detector (SASHD) according to the revised in 2011 type approval and performance inspection code for detector. The main improvement of the revised regulation is source. CMOS microcontroller with nano watt technology is use for development of the workable SASHD over 10 years. The low-power SASHD is developed by using the power-saving sleep mode of microcontroller, by making the low-power source voltage checker, heat detector and smoke detector. The stand-alone detector is developed by smoke and heat detector type for reduce false fire alarm. User can choose type of work between the heat detection mode and smoke & heat detection mode. The SASHD can communicate with each them using RS-485 communication supported from microcontroller. So, this study can develop the SASHD that is able to alarm more wide area when fire occurs and reduce a flash fire alarm.

Fuzzy Measure를 이용한 화재감지기의 기본설계

  • 백동현;김기화
    • Fire Science and Engineering
    • /
    • v.10 no.3
    • /
    • pp.19-28
    • /
    • 1996
  • This paper present the way the fire detector determines whether a fire has broken out or not using the fuzzy measure. This method is based on Dempster's combination rule using the belief measure. The detector indicate a 'Fire'(F) or 'Nonfire'(N) when it determines whether a fire has broken out or not. To determine this, the fuzzy rule is applied in the setting value for the heat and smoke detector which is used. As a result, It is proved that the final decision can be determined more exactly whether a fire has broken out or not in proportion to the frequency of the fuzzy measure and the value of Bel (F).

  • PDF

Implementation of Wireless Fire Detection System using Zigbee (Zigbee를 이용한 무선 화재감지시스템의 구현)

  • Kim, Tae-Sun;Park, Seng-Sik;Kim, Yong-Chan;Kim, Eun-Gyeong
    • Proceedings of the Korean Society of Computer Information Conference
    • /
    • 2018.07a
    • /
    • pp.289-290
    • /
    • 2018
  • 본 과제는 각종 센서를 활용하여 빠르고 정확하게 화재를 감지하고 스프링클러를 활용한 초기진압과 동시에 어플리케이션을 통한 자동신고 기능을 포함하고 있다. 열/연기 감지센서를 통해 빠르게 화재 발생을 감지하고 화재감지기에 부착되는 Zigbee통신으로 스프링클러 시스템과 통신하여 초기진압을 하며, 고유 번호로 정확한 화재진원지를 파악하여 소방원들의 화재진압에 도움이 된다. 또한 연동되어있는 어플리케이션의 자동 신고기능을 통해 소방서에 정보를 제공하여 빠른 출동이 가능하게 되고 스피커를 통해 화재발생시 화재경보로 알려주어 신속한 대피를 할 수 있다.

  • PDF