• Title/Summary/Keyword: 연기제연

Search Result 111, Processing Time 0.022 seconds

시뮬레이션 기법을 이용한 장대터널의 제연기술

  • Kim, Dong-Seok
    • 방재와보험
    • /
    • s.111
    • /
    • pp.20-27
    • /
    • 2006
  • 피난길이가 긴 장대터널에서 화재가 발생되면 생성된 연기가 상승하고 천장을 만나 터널의 길이방향으로 전파된다. 연기의 독성가스에 의해 질식하게 되는 인명피해를 줄이기 위해서는 발생한 화재의 크기에 따라 제연유속이 필요하며, 제연 팬의 용량과 신뢰성을 확보해야 한다.

  • PDF

Simulation of Ventilation Capability Effect on The Smoke Spread in Railway Station (제연 팬 용량이 철도역사 연기확산에 미치는 영향 분석)

  • Jang, Yong-Jun;Koo, In-Hyuk;Kim, Hag-Beom;Kim, Jin-Ho
    • Proceedings of the KSR Conference
    • /
    • 2011.05a
    • /
    • pp.7-13
    • /
    • 2011
  • Simulation study were performed for ventilation capability effect on the smoke spread in the deeply-underground subway station(DUSS). Singeumho station(The line # 5, Depth: 46m) was modeled and were analyzed for smoke-spread speed difference between the originally-designed-ventilation-capacity and the measured-ventilation-capacity. Field test data for actual fan in DUSS was applied as a boundary condition of a simulation. The whole station was covered in this analysis and total of 4 million grids were generated for this simulation. The fire-driven flow was analyzed case by case to compare the smoke-spread effects. In order to enhance the efficiency of calculation, parallel processing by MPI was employed and large eddy simulation method in FDS code was adopted.

  • PDF

Smoke Control Experiment of a Very Deep Underground Station Where Platform Screens Doors are Installed - Analysis on Smoke Control Performance by Fans equipped in Tunnel (스크린도어가 설치된 대심도 지하역사의 제연 실험 - 터널 송풍기에 의한 제연의 효과 분석)

  • Park, Won-Hee;Kim, Chang-Yong;Cho, Youngmin
    • Asia-pacific Journal of Multimedia Services Convergent with Art, Humanities, and Sociology
    • /
    • v.9 no.9
    • /
    • pp.721-736
    • /
    • 2019
  • In this paper, the behavior of the fire smoke due to the operation of the ventilation systems when the fire occurred in the underground station (6 basement floors) and the tunnel at the great depth was measured. Fire smoke was generated by using a smoke generator which realized heat buoyancy effect by using hot air blower. The two locations of the fire were selected on the platform and on the platform of the tunnel located outside the screen door. A ventilation mode is generally used in which smoke is exhausted through a vent hole provided in a platform when a platform fire occurs. The tests were performed by operating the exhaust through the ventilation holes of the tunnel part located at both ends of the platform. The smoke density and the wind speed/velocity were measured at various positions, and the videos were taken to analyze the movement and smoke of the smoke. In both cases for fire inside the platform and in the railway tunnel, due to the ventilation mode operation of the fan for the platform and the exhaust of the fans in the tunnel smoke were well exhausted and the smoke propagation to the area near the smoke zone was suppressed. The smoke-control mode, which is applied to both fans for the platform and fans for in the tunnel at both ends of the platform, can provide a safer evacuation environment to the passengers from the fire smoke when the platform fire or fire train stops.

Simulation of a Clean Room Fire II. Needs of Smoke Control System and Springkler System (청정실 화재의 시뮬레이션 II. 제연설비와 스프링클러설비의 필요성)

  • Park, Woe-Chul;Lee, Man-Geun;Park, Hun-Sik
    • Fire Science and Engineering
    • /
    • v.20 no.2 s.62
    • /
    • pp.8-13
    • /
    • 2006
  • Numerical simulations were carried out for a fire in a clean room to confirm needs of a smoke control system and a sprinkler system, and to investigate a possible smoke spread-out. For a 1 MW methanol fire in a space of $39m{\times}13m$ floor and 4 m high, smoke spread-out was scrutinized for failure of the sprinkler system and/or the smoke control system. It was shown that the smoke control system removes smoke safely without the sprinkler system and that the sprinkler system is required to suppress smoke generation and spread of the fire, and to remove the smoke quickly. It was also confirmed that highly reliable sprinkler heads and automatic fire detection system are required for the sprinkler and smoke control systems.

Smoke Control Experiment of a Very Deep Underground Station Where Platform Screen Doors are Installed (I) - Analysis on Smoke Control Performance on the Platform (스크린도어가 설치된 대심도 지하역사의 제연 실험 I - 승강장에서의 제연의 효과 분석)

  • Park, Won-Hee;Kim, Chang-Yong;Cho, Youngmin;Kwon, Tae-Soon;Lee, Duck-Hee
    • Asia-pacific Journal of Multimedia Services Convergent with Art, Humanities, and Sociology
    • /
    • v.8 no.7
    • /
    • pp.485-496
    • /
    • 2018
  • In this paper, the smoke behavior in an underground station on operation of the fans in the ventiliation of the station was measured by the experimental method when the fire occurred in the underground station platform where the platfrom screen door was installed. The ventilation characteristics were compared when the ventilation system was operated and when the ventilation system was not operated when a fire occurred at the platform where the clean door was closed. To simulate the fire smoke, the smoke generated from the smoke generator was heated using a hot air fan. The transmittance was measured using a smoke density meter to quantitatively measure fire smoke. If the screen door is closed and the ventilation system of the underground station does not work, it is confirmed that if a fire occurs in the platform, smoke accumulates inside the platform, evacuating passengers is very difficult and can lead to a very dangerous situation. On the other hand, under the condition that the ventilation facility of the subway station is operated, the smoke evacuates to the outside through the ventilation facility of the underground station, and airflow is formed in the direction from the waiting room to the waiting area, so that the passenger located on the platform can safely evacuate toward the concourse. In the following paper, we will discuss the concurrent effect of tunnel ventilation through tunnel vent near the platform.

A Numerical Simulation of Smoke Control in Daegu Subway Stations I. Smoke Control System (대구 지하철역 제연의 문제점과 대책 I. 제연방식)

    • Fire Science and Engineering
    • /
    • v.17 no.4
    • /
    • pp.98-104
    • /
    • 2003
  • Smoke control in il space 10 m${\times}$3 m floor and 5.4 m high around the stairway of a subway station platform was simulated by using FDS to investigate problems of smoke control in Daegue subway stations. Distributions of temperature and smoke particles, and variation of the number of particles with time for a 200 ㎾ polyurethane fire were compared. It was shown that the purge system fails to remove smoke efficiently and that the extraction system has the highest perfor-mance among the three smoke control systems for the given situations. Simply switching the purge system into extraction mode might improve much the smoke removal performance.

Full-Scale Test of Smoke-Control Performance of a Subway Tunnel (지하철 본선터널 제연성능 실물 실험)

  • Park, Won-Hee;Lee, Duck-Hee;Jung, Woo-Sung
    • Fire Science and Engineering
    • /
    • v.25 no.4
    • /
    • pp.94-102
    • /
    • 2011
  • Hot smoke test is done in a subway tunnel. Alcohol trays of 1.0 MW and smoke generators are used for generating hot smoke. The fans equipped with the tunnel are successively run 9 min after smoke generation. It is verified how hot smoke is controlled by fans. Velocity and direction of flow, temperature and smoke density are measured and analyzed for smoke control performance of the tunnel with fans and analyzed from the fire-safety-point of view. Velocity of smoke flow is obtained by using measured velocity and temperature at the ceiling of the tunnel. The time when smoke-control flow is builded up is different for the different positions. Velocity distributions at various positions will be used for the boundaries and the comparison data in numerical simulations for evaluation on smoke-control facilities of subway tunnel.

A Study on the Performance Improvement of Smoke Control with Smart Dampers (스마트 댐퍼를 적용한 제연 성능 개선에 관한 연구)

  • Choi, Hyun-Jun
    • Proceedings of the Korean Society of Disaster Information Conference
    • /
    • 2023.11a
    • /
    • pp.159-160
    • /
    • 2023
  • 화재가 발생할 때 연기로부터 안전하게 피난과 소방관의 소화활동을 위해 제연설비가 설치되어 있다. 기존의 자동차압·과압 조절형 급기댐퍼는 화재층과 비화재층을 구분하지 못하므로 화재가 발생하지 않는 층에서 피난을 할 경우 화재층이 연기로부터 보호받지 못한다. 스마트 댐퍼를 적용하면 화재층과 비화재층을 구분하므로 화재층을 연기로부터 보호가 가능하다.

  • PDF

A Study on the Adequacy of the Installation Location of the Air Supply Damper of the Attached Actual Smoke Facility (부속실제연설비 급기댐퍼의 설치위치 적정성 연구)

  • Yang, Sung-Hoon
    • Proceedings of the Korean Society of Disaster Information Conference
    • /
    • 2022.10a
    • /
    • pp.193-194
    • /
    • 2022
  • 본 연구에서는 특별피난계단의 전실에 설치되는 부속실제연설비가 화재 시 발생한 연기가 부속실 내로 역류하지 않는 급기댐퍼의 적정한 설치위치를 알아보고자 하였으며, 이를 확인하기 위하여 FDS(Fire Dynamics Simulator)을 사용 하였다. 시뮬레이션 Case 총 15가지로 구분하고, 방연풍속은 총 64개의 지점에서 측정하는 시뮬레이션을 수행하였다. 시뮬레이션 결과 출입문 상부 및 하부에서 역 기류가 발행하는 Case가 있었으며, 대부분 출입문 하부에서의 연기 유입이 예상되는 경우가 많았다. 방연풍속은 측정 포인트 64점에서 관련기준에 단 한 곳도 미달하지 않고 만족하는 경우는 총 단 4가지 Case로서 매우 제한적인 것을 알 수 있었다. 그만큼 급기댐퍼의 위치 및 급기방향에 따라 부속실 제연설비의 성능이 다양하게 나타날 수 있다는 것이다. 본 연구를 바탕으로 앞으로 실물실험을 통하여 구체적인 자료가 입증되길 바라고, 더불어 부속실 제연설비의 성능을 개선하는 데 있어 도움이 되었으면 한다.

  • PDF

A Study on the Risk Assessment of the Underground Space -The Estimation of Smoke Reservoir Screen for Smoke Control in Subway Station Platform (지하공간의 위험성평가에 관한 연구 -지하철 역사내의 연기제어를 위한 제연경계벽의 효용성 평가)

  • Roh Sam-Kew;Hur Jun-Ho
    • Fire Science and Engineering
    • /
    • v.18 no.4
    • /
    • pp.103-109
    • /
    • 2004
  • The risk of underground space become an important issue of life safety thought the Taeku subway line Accident. It is essential to study of smoke control screen to minimize the damage of human life because of smoke passage and passenger evacuation routes are on the same vertical and dispersion movement. The Fire modeling result shows the effect of fire control screen can save the evacuation time about 2-2.5 times compare to existing the system However, The designs of fire control screen need to be complied with smoke control ventilation system to present optimum design and the position of installation.