Smoke Control Experiment of a Very Deep Underground Station Where Platform Screen Doors are Installed (I) - Analysis on Smoke Control Performance on the Platform

스크린도어가 설치된 대심도 지하역사의 제연 실험 I - 승강장에서의 제연의 효과 분석

  • Received : 2018.04.16
  • Accepted : 2018.06.08
  • Published : 2018.07.31

Abstract

In this paper, the smoke behavior in an underground station on operation of the fans in the ventiliation of the station was measured by the experimental method when the fire occurred in the underground station platform where the platfrom screen door was installed. The ventilation characteristics were compared when the ventilation system was operated and when the ventilation system was not operated when a fire occurred at the platform where the clean door was closed. To simulate the fire smoke, the smoke generated from the smoke generator was heated using a hot air fan. The transmittance was measured using a smoke density meter to quantitatively measure fire smoke. If the screen door is closed and the ventilation system of the underground station does not work, it is confirmed that if a fire occurs in the platform, smoke accumulates inside the platform, evacuating passengers is very difficult and can lead to a very dangerous situation. On the other hand, under the condition that the ventilation facility of the subway station is operated, the smoke evacuates to the outside through the ventilation facility of the underground station, and airflow is formed in the direction from the waiting room to the waiting area, so that the passenger located on the platform can safely evacuate toward the concourse. In the following paper, we will discuss the concurrent effect of tunnel ventilation through tunnel vent near the platform.

본 논문에서는 스크린도어가 설치되어 있는 지하역사 승강장에서 화재가 발생시 승강장 환기실에 설치된 송풍기의 작동에 따른 연기거동을 실험적인 방법으로 측정하였다. 스크린도어가 닫힌 승강장에서 모의화재 발생시 승강장의 제연설비가 작동하지 않은 경우와 작동하는 경우에 제연 특성을 비교하였다. 화재연기를 모사하기 위하여 연기발생기에서 발생한 연기를 열풍기를 이용하여 가열하였다. 화재연기를 정량적으로 측정하기 위하여 연기농도계를 이용한 광투과도를 측정하였다. 스크린도어가 닫혀져있고 지하역사의 제연설비가 작동되지 않는 경우 승강장에 화재가 발생하면 연기가 승강장 내부에 축적되어 승객의 피난이 매우 어려우며, 매우 위험한 상황으로 연결될 수 있음을 확인할 수 있었다. 반면에 역사의 제연설비를 가동한 조건에서는 승강장 화재에 의해 발생한 연기가 역사의 제연설비를 통하여 외부로 빠져나가며, 대합실에서 승강장 방향으로 기류가 형성되어 승강장 승객이 대합실 방향으로 대피하는 것이 가능함을 확인할 수 있었다. 후속 논문에서는 승강장 인접부에 위치한 터널환기구를 통한 터널 제연의 병행효과에 대하여 다룰 예정이다.

Keywords